For V/F Control Type:

1) Press MENU.
Scroll to BASIC PARAMS.
Press ENTER.
At this point the display shows CONTROL 
TYPE F1601, – the default value is "V/F 
Control" – press ENTER to change the 
setting to Open Vector C1601, – press 
ENTER.

2) Press the DOWN Arrow key and enter 
values from the motor nameplate for each 
of the following "MOTOR DATA" parame-
ters. Press ENTER to begin editing – after 
each value is programmed, press ENTER 
then DOWN arrow for the next item.
• MOTOR RATED HP
• MOTOR RATED VOLT
• MOTOR RATED AMPS
• MOTOR MAG AMPS*
• MOTOR RATED SPD
• MOTOR RATED FREQ
*If this is not shown on the motor name-
plate, use the formula:
MOTOR MAG AMPS = 0.4 X MOTOR 
RATED AMPS.

3) CALC MOTOR MODEL – press ENTER 
– select "Yes" – press ENTER

4) After CALC MOTOR MODEL is com-
plete, Press F2 to exit MOTOR DATA and 
BASIC PARAMS to return to the MENU.

5) ENABLE DRIVE, (close J2-8 – J3-24 
circuit).

6) Scroll to ADVANCED PROG – press 
ENTER.

7) Scroll to LEVEL 2 BLOCKS – press 
ENTER

8) Scroll to AUTO TUNE – press ENTER.

9) Skip ANA OFFSET TRIM – Scroll to ONE-
STEP TUNING – press ENTER – select "Yes" 
– press ENTER. The ONE-STEP TUNING will 
take approx. 3-4 minutes to complete.

10) After the static portion of AUTO TUNE 
is complete, the display will alternately 
show STATIC TEST DONE – ROTARY 
FOLLOW and PRESS ENTER FOR FLUX 
CUR TUNE. Select one of the following: 
a) if the motor is coupled to the load, 
press F2 to exit AUTO TUNING
b) If the motor is not coupled to the load, 
press ENTER to begin rotation tuning. 
The first test is "FOR FLUX CUR TUNE" – 
press ENTER.

11) After "FLUX CUR TUNE" TEST 
PASSED – press ENTER for "MEASURE 
Xm(ROT)"

12) After "MEASURE Xm(ROT)" TEST 
PASSED – press ENTER for "END OF 
TEST".

13) PRESS F2 three times to return to 
MENU – press F1 to show STATUS display.

14) Couple motor to load and run " 
SPEED LOOP TUNE" to get a better 
response or manually tune the speed loop 
using Speed Prop Gain (P1635), Speed Int 
Gain (P1636) and Speed Diff Gain (P1637)

OPEN VECTOR AUTO TUNE COMPLETE

1) Press MENU.
Scroll to BASIC PARAMS.
Press ENTER.
At this point the display shows CONTROL 
TYPE F1601,  – the default value is "V/F 
Control" – If needed, press ENTER to 
change the setting to V/F Control C1601, 
– press ENTER.

2) Press the DOWN Arrow key and enter 
values from the motor nameplate for each 
of the following "MOTOR DATA" parame-
ters. Press ENTER to begin editing – after 
each value is programmed, press ENTER 
then DOWN arrow for the next item.
• MOTOR RATED HP
• MOTOR RATED VOLT
• MOTOR RATED AMPS
• MOTOR MAG AMPS*
• MOTOR RATED SPD
• MOTOR RATED FREQ
*If this is not shown on the motor name-
plate, use the formula:
MOTOR MAG AMPS = 0.4 X MOTOR 
RATED AMPS.

3) CALC MOTOR MODEL – press ENTER 
– select YES – press ENTER

4) After CALC MOTOR MODEL is com-
plete, Press F2 to exit MOTOR DATA and 
BASIC PARAMS to return to the MENU.

5) ENABLE DRIVE, (close J2-8 – J3-24 
circuit).

6) Scroll to ADVANCED PROG – press 
ENTER.

7) Scroll to LEVEL 2 BLOCKS – press 
ENTER

8) Scroll to AUTO TUNE – press ENTER.

9) Skip ANA OFFSET TRIM – Scroll to 
STATOR R1 TUNE – press ENTER – se-
lect "Yes" – Press ENTER. After STATOR 
R1 TUNE is complete – (TEST PASSED), 
press ENTER to END (This is a static 
tune, motor will not rotate).

10) PRESS F2 three times to return 
to MENU – press F1 to show STATUS 
display.

V/F CONTROL AUTO TUNE COMPLETE

 

STATUS

 

BASIC PARAMS

 

ADVANCED PROG

 

EVENT LOG

 

DIAGNOSTICS

STATUS    

BACK

 

STATUS

 

BASIC PARAMS

 

ADVANCED PROG

 

EVENT LOG

 

DIAGNOSTICS

STATUS    

BACK

 

LEVEL 1 BLOCKS

 

LEVEL 2 BLOCKS

 

LEVEL 3 BLOCKS

 

MODIFIED PARAMS

 

LINEAR LIST

STATUS    

BACK

 BASIC PARAMS

 LEVEL 2 BLOCKS

 ADVANCED PROG

BASIC  

MOTOR CONTROL

CONTROL TYPE

Open Vector

STATUS 

C1601T1  

BACK

BASIC  

MOTOR DATA

MOTOR RATED HP

0.5 HP

STATUS 

C2416T1  

BACK

BASIC  

MOTOR DATA

CALC MOTOR MODEL

Yes

STATUS 

F2414  

BACK

PROG  

AUTO TUNE

ONE-STEP TUNING

Yes

BASIC 

F2902  

BACK

 

STATUS

 

BASIC PARAMS

 

ADVANCED PROG

 

EVENT LOG

 

DIAGNOSTICS

STATUS    

BACK

 

STATUS

 

BASIC PARAMS

 

ADVANCED PROG

 

EVENT LOG

 

DIAGNOSTICS

STATUS    

BACK

 

LEVEL 1 BLOCKS

 

LEVEL 2 BLOCKS

 

LEVEL 3 BLOCKS

 

MODIFIED PARAMS

 

LINEAR LIST

STATUS    

BACK

 BASIC PARAMS

 LEVEL 2 BLOCKS

 ADVANCED PROG

BASIC  

MOTOR CONTROL

CONTROL TYPE

V/F Control

STATUS 

C1601T1  

BACK

BASIC  

MOTOR DATA

MOTOR RATED HP

0.5 HP

STATUS 

C2416T1  

BACK

BASIC  

MOTOR DATA

CALC MOTOR MODEL

Yes

STATUS 

F2414  

BACK

PROG  

AUTO TUNE

STATOR R1 TUNE

No

BASIC 

F2903  

BACK

Auto Tuning Procedures for Open Vector and V/F Control

For Open Vector Control Type:

(Note: All procedures require that load be decoupled from motor shaft. See details below if this is not possible.

MS764 

10/10 TCP 5000

*MS764-1010*