Auto Tuning Procedure

For PM Closed Loop Control Type:

1) Press MENU.
Scroll to BASIC PARAMS.
Press ENTER.

At this point the display shows 
CONTROL TYPE F1601,– the 
default value is "PM Closed 
Loop" – press DOWN arrow to 
continue tuning.

2) PM MOTOR TYPE - 
Default value is Int PM. Press 
DOWN arrow to continune 
or press ENTER then UP or 
DOWN to change MOTOR 
TYPE to SURFACE PM - press 
ENTER to select then DOWN 
arrow to continue.

3) Enter values from the motor 
nameplate for each of the 
following "MOTOR DATA" 
parameters. Press ENTER to 
begin editing – after each value 
is programmed, press ENTER 
then DOWN arrow for the next 
item.

• MOTOR RATED VOLT
• MOTOR RATED AMPS
• MOTOR RATED SPD
• MOTOR RATED FREQ

4) FEEDBACK SOURCE – 

(Standard VS1SD drives factory 

setting is "Daughter FDBK") – 
press DOWN arrow.

5) ENCODER COUNTS 
– Press  DOWN arrow to skip 
this parameter to continue. 
Note: Contact Baldor if an 
encoder must be used for your 
application.

6) Scroll to CALC MOTOR 
MODEL – press ENTER – select 
YES – press ENTER.

7) After CALC MOTOR MODEL 
is complete, press F2 to exit 
MOTOR DATA and BASIC 
PARAMS to return to the menu.

8) ENABLE DRIVE, (Close J2-8 
– J3-24 circuit).

9) Scroll to ADVANCED PROG 

– press ENTER.

10) Scroll to LEVEL 2 BLOCKS 

– press ENTER

(Note: Procedure requires that load be decoupled from motor shaft. See details below if this is not possible.

11) Scroll to AUTO TUNE  – 
press ENTER

12) Skip ANA OFFSET TRIM – 

Scroll to ONE-STEP TUNING 

– press ENTER – select Yes – 
press ENTER. 

The ONE-STEP TUNING will 

take approx. 3-4 minutes to 
complete.

13) After the static portion of 
AUTO TUNE is complete, the 
display will alternately show 
STATIC TEST DONE – ROTARY 
FOLLOW and PRESS ENTER 

FOR FEEDBACK ALIGN. Select 

one of the following: 
a) if the motor is coupled to the 

load, press F2 to exit AUTO 

TUNING

b) If the motor is not coupled 

to the load, press ENTER to 
begin rotation tuning. The first 

test is "FEEDBACK ALIGN" – 

press ENTER.

14) After "FEEDBACK ALIGN" 

TEST PASSED – press ENTER 
for "FLUX CUR TUNE".

15) After "FLUX CUR TUNE" 
TEST PASSED – press ENTER 
for "SPD LOOP TUNE".

16) After "SPD LOOP TUNE" 
TEST PASSED – press ENTER   
for "END OF TEST".

17) Press F2 to return to the 
MENU – press F1 to return to 
the STATUS display.

18) It may be possible to 
improve the speed loop after  
the motor is coupled to the load 
by manual tuning of the Speed 

Prop Gain (P1635), Speed Int 
Gain (P1636) and Speed Diff 
Gain (P1637).

Note: It is not recommended to 
perform SPEED LOOP Autotune 
while the load is coupled to the 
motor.

BASIC  

MOTOR CONTROL

CONTROL TYPE

PM Closed Loop

STATUS 

F1601T1  

BACK

BASIC  

MOTOR CONTROL

MOTOR RATED VOLT

230.0 V

STATUS 

F2401T1  

BACK

BASIC  

MOTOR DATA

FEEDBACK SOURCE

Daughter

 FDBK

STATUS 

F2409T1  

BACK

BASIC  

MOTOR DATA

ENCODER COUNTS

1024 PPR

STATUS 

F2408T1  

BACK

MS766 

 Jan. 

2012 

           

BASIC  

MOTOR CONTROL

PM MOTOR TYPE

Int PM

STATUS 

F1677T1  

BACK

BASIC  

MOTOR CONTROL

PM MOTOR TYPE

Surface PM

STATUS 

F1677T1  

BACK

BASIC  

MOTOR DATA

CALC MOTOR MODEL 

Y

ES

STATUS 

F2414T1  

BACK

PROG  

AUTO TUNE

ONE-STEP TUNING

Y

es

BASIC 

F2902  

BACK