Masoneilan Model 4411 Electropneumatic Transducer Instruction Manual  |  4 

Copyright 2020 Baker Hughes Company. All rights reserved.

Under no circumstances should PTFE tape be used 

for sealing the fittings as this tends to shred small 

particles which may find their way into the instrument 

causing malfunctions.

The use of a soft setting anaerobic hydraulic seal is recommended, 

(e.g.  Loctite  Hydraulic  Seal  542).  Follow  the  manufacturers 

recommendations�

Do not use an excessive amount as this will not set 

and could find its way into the instrument.

If the air supply is not of adequate quality, the device performance 

can be affected. Adequate quality can normally be achieved by 

the use of air filter regulators.

Electrical Installation

The  electrical  connections  should  be  made  as  shown  in  the 

dimensional  drawing  Figure  1.  The  instrument  is  protected 

against reverse polarity to –100mA, no operation is possible in 

this condition�

The  Model  4411  approximates  a  constant  voltage  load  of  6.5 

volts across the loop terminals, therefore it is essential that the 

loop controller be capable of providing a constant current in the 

range 4-20mA with an output voltage of at least 6.5 volts. 

Voltage output controllers (e.g. variable voltage power 

supplies) are entirely unsuitable for the Model 4411 

and could severely damage the electronic circuits.

Important Note
The control electronics of the Model 4411 incorporate 

precision electronics. The calibration of the unit may be 

affected by very high voltage spikes. Consequently, in 

environments where static electricity may be present ESD 

precautions should be used.

Wiring And Cable Entry

These instruments must be installed in accordance 

with local and national codes of practice, especially for 

hazardous area installations. The instruments are fully 

isolated from ground and therefore grounding is un-

necessary for functional purposes. However, ground-

ing may be necessary to conform to installation codes.

 

Note: It is strongly recommended that shielded cable or a 

grounded conduit be used to achieve maximum RFI immunity, 

if the installation has any risk of electromagnetic interference.

Conduit Entry

The instrument has twin conduit entry threaded 1/2" NPT. For 

explosion proof installation, a sealed conduit gland conforming to 

explosion-proof specifications must be used. A ground terminal 

is provided both internally and externally and should be used if 

ground continuity is essential. 

The unit is supplied with plastic blanking plugs, which 

must be removed before operation/calibration and re-

placed with a blanking plug conforming to the hazard

-

ous area certification rating applicable.

Calibration 

The instruments are designed for continuous operation without 

the necessity for routine overhaul, with continuous monitoring, 

adequate  precautions  and  replacement  of  the  filter  no  longer 

than every 5 years.
The most common source of failure for pneumatic instrumentation 

has  been  found  to  be  inadequate  air  quality,  allowing 

contaminants  to  block  internal  orifices. Air  filtering  is  included 

within  the  instrument  but  cannot  cope  with  sustained  poor  air 

quality, which may ultimately lead to failure.
The  recommendations  in  the  Pneumatic  Installation  section 

should be rigorously observed.

Note: These instruments are factory calibrated at a supply 

pressure of 30psig (2 bar).

The  instrument  cover  must  be  unscrewed  to  obtain  access  to 

the trimpots�

Do not remove the instrument cover in a potentially 

explosive atmosphere when the instrument is powered.

An accurate current source of 4-20mA and pressure gauge are 

required. These should be of good quality with an accuracy of 

0.1% or better. The current source should be checked to ensure 

that it provides at least 6.5V at 20mA output compliance.
• 

 Connect  the  instrument  as  described  in  the  installation 

section or the test-jack section below.

• 

 Remove the instrument cover to gain access to the trimpots 

and jack-socket.

• 

 Set the current to 4.00mA – the instrument outlet should be 

3.00+/-0.05psig (0.200+/-0.003 bar). Adjust the Zero trimpot 

if necessary.

• 

 For 6-30 psig output, the output pressure should be set to 

6.00 ±.05 psig (0.400 ± .003 bar). Adjust trimpot as necessary.

• 

 Set the current source to 20.00mA – the instrument outlet 

should be 15.00 +/-0.05psig (1.00+/-0.003 bar). Adjust the 

Span trimpot if necessary.

• 

 For 6-30 psig output, the output pressure should be set to 

30.00 ±.05 psig (2.00 ± .003 bar). Adjust trimpot as necessary.

If either Span or Zero controls are adjusted it may be necessary 

to repeat the above steps until both ends are within the calibration 

limits�

Alternatively  the  Jack  Plug  can  be  connected  to  calibrate  and 

test the unit. The Jack Plug can be either set-up for Monitoring or 

Calibration/Operation set-up.

Содержание Masoneilan 4411 Series

Страница 1: ...Masoneilan 4411 Series Electropneumatic Transducer Instruction Manual Baker Hughes Data Classification Public...

Страница 2: ...CULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE ME...

Страница 3: ...tured Bleed Version 3 Pneumatic Installation 3 Electrical Installation 4 Wiring and Cable Entry 4 Conduit Entry 4 Calibration 4 Tight Shut Off Adjustment Instructions 5 Simple Functional Checks 5 Tech...

Страница 4: ...ne Warranty Items sold by Baker Hughes are warranted to be free from defects in materials and workmanship for a period of one year from the date of shipment provided said items are used according to B...

Страница 5: ...rocess control applications The units operate a closed loop system incorporating a feedback sensor ensuring long term stability and high accuracy performance with fail safe operation i e the output fa...

Страница 6: ...be blocked with paint and or plastic sheeting etc Captured Bleed Version The baffles and the baffle cover are fitted to maintain the adequate Ingress Protection IP rating of the instrument Removal of...

Страница 7: ...conforming to explosion proof specifications must be used A ground terminal is provided both internally and externally and should be used if ground continuity is essential The unit is supplied with pl...

Страница 8: ...p pressure 0psi adjust potentiometer slowly clockwise until the output pressure falls to zero Do not turn the pot beyond this point The shut off point is now set Shut off point check Increase the inpu...

Страница 9: ...accordance with ANSI ISA 51 1 1993 N B Instrument accuracy excludes calibration errors Temperature Effect Span and Zero Mean temperature coefficient over full operating range 40 to 85 C less than 0 0...

Страница 10: ...III Division 2 Group FG T6 Ta 75 C T5 Ta 85 C CSA Class I Division 1 Group BCD Class II Group EFG Class III Ta 85 C T5 Ta 65 C T6 Class I Division 1 Group ABCD Class II Group EFG Class III Ta 85 C T4...

Страница 11: ...being adversely affected thus ensuring that the type of protection is not compromised Aggressive substances e g acidic liquids or gases that may attack metals or solvents that may affect polymeric ma...

Страница 12: ...9 Baker Hughes Copyright 2020 Baker Hughes Company All rights reserved...

Страница 13: ...Masoneilan Model 4411 Electropneumatic Transducer Instruction Manual 10 Copyright 2020 Baker Hughes Company All rights reserved...

Страница 14: ...11 Baker Hughes Copyright 2020 Baker Hughes Company All rights reserved Notes...

Страница 15: ...Masoneilan Model 4411 Electropneumatic Transducer Instruction Manual 12 Copyright 2020 Baker Hughes Company All rights reserved Notes...

Страница 16: ...ormation The Baker Hughes logo and Masoneilan are trademarks of Baker Hughes Company Other company names and product names used in this document are the registered trademarks or trademarks of their re...

Отзывы: