Copyright 2011 Baker Hughes Company.
English–DPS 8000 Instruction Manual | 43
Device Profile Segment
Sub-Index
001
Description
AI Input scaling 1 PV 1
Data Type
REAL32
Access
RW
PDO Mapping
No
Default Value
0.0
Sub-Index
002
Description
AI Input scaling 1 PV 2
Data Type
REAL32
Access
RW
PDO Mapping
No
Default Value
0.0
A.3.6 Object 6122h: AI Input Scaling 2 FV
This object defines the field value of the second calibration point for the analogue input channel.
It is scaled in physical unit of field value.
OBJECT DESCRIPTION
INDEX
6122
Name
AI Input scaling 2 FV
Object Code
Array
Data Type
REAL32
ENTRY DESCRIPTION
Sub-Index
000
Description
number of entries
Access
RO
PDO Mapping
No
Default Value
0.0
Sub-Index
001
Description
AI Input scaling 2 FV 1
Data Type
REAL32
Access
RW
PDO Mapping
No
Default Value
1.0
Sub-Index
002
Description
AI Input scaling 2 FV 2
Data Type
REAL32
Access
RW
PDO Mapping
No
Default Value
1.0
Содержание Druck DPS 8000 Series
Страница 1: ...Druck com DPS 8000 Series CAN bus Pressure Transducer Instruction Manual ...
Страница 2: ......
Страница 6: ...Copyright 2011 Baker Hughes Company iv DPS 8000 Instruction Manual English ...
Страница 10: ...Copyright 2011 Baker Hughes Company viii DPS 8000 Instruction Manual English ...
Страница 28: ...Copyright 2011 Baker Hughes Company 18 DPS 8000 Instruction Manual English ...
Страница 62: ...Copyright 2011 Baker Hughes Company 52 DPS 8000 Instruction Manual English Appendix C Bibliography ...
Страница 63: ......