7. Usage
7.1 In order to guarantee the cleanliness to clean area. The Self-cleaner should be
on 15 minutes before operation.
7.2 He clean air blowing crosscut should face to the work area needed purifying and
prevent hold up from large articles.
7.3 In order to assure the cleaning flow track in the working range not to be
disturbed. In the cleaning operating range any obvious action to disturb the flow track
is not allowed.
7.4 According to purifying environment practical cubage and clean requirement,
calculate the change air times and self-cleaner numbers at air quantity rate specified
by the self-cleaner.
7.5 The mounting position should have proportional spacing. When rebuilding the
vertical type clean room.
8. Maintenance.
8.1 According to environmental clean extent, the coarse filter cloth should be
regularly (generally every 3-6months) cleaned by removing (non-woven cloth) or
replacing.
8.2 the self-cleaner
’
s cleanliness should be regularly (generally twice per year)
checked by the CLJ-03A type dust particle counter, if it is not conform to technology
parameter, can regulate work condition of fan, or replace HEPA filter.
8.3 AFTER replacing HEPA filter, REMOVE the press border in the front of the
self-cleaner, take out HEPA filter, WHEN changing the new HAPA filter, should pay
attention to arrow sign pointed to air movement direction.
8.4 AFTER replacing filter, check leakage by CLJ-03A type dust particle counter, pay
attention to sealing for frame and press frame in the front of self-cleaner whether good
or not.
8.5 After proceeding system test, we make sure technology specification to reach
requirement, we can operate the self-cleaner.
8.6 The electric appliance should be regularly (generally twice per year) checked