INTRODUCTION
REFERENCE DOCUMENTS
1 - 4
I-E96-403A
®
REFERENCE DOCUMENTS
Table
contains the reference documents for the NTAI02.
SPECIFICATIONS
Refer to Table
for the specifications of the NTAI02 Termina-
tion Unit.
Table 1-2. Reference Documents
Document
Number
Description
I-E96-205
Analog Master Module and Analog Slave Modules
(IMAMM03 and IMASM01/02/03/04)
I-E96-406
Analog Master Module Termination Unit (NTAM01)
I-E96-500
Site Planning and Preparation
Table 1-3. Specifications
Property
Characteristic/Value
Power Requirements
+24 VDC, 10mA per IMASM02.
Mounting
Mounts in the Field Termination Panel (NFTP01).
Environmental
Electromagnetic/Radio
Frequency Interference
No values available at this time. Keep cabinet doors closed. Do not use
communication equipment closer than 2 meters from the cabinet.
Ambient Temperature
0 to 70
o
C (32 to 158
o
F).
Relative Humidity
5% to 90%
±
5% up to 55
o
C (131
o
F) (noncondensing).
5% to 40%
±
5% up to 70
o
C (158
o
F) (noncondensing).
Atmospheric Pressure
Sea level to 3 km (1.86 miles).
Air Quality
Noncorrosive.
Cooling Requirements
No cooling is necessary when used in Bailey Controls cabinets and oper-
ated within stated limits.
Surge Protection
Meets IEEE-472-1974 Surge Withstand Capability Test.
Certification
CSA certified for use as process control equipment in an ordinary (nonhaz-
ardous) location.
Specifications are subject to change without notice.