INSTALLATION
SETUP/PHYSICAL INSTALLATION
2 - 4
I-E96-410A
®
Cable Installation
Remove (pull off) the front cover of the termination module
before trying to install cables. Use the following procedures
when installing cables.
NKTU02, NKTU12 AND NKTM01 CABLES
This cable connects the IDI termination module to a master or
slave module. To install the cable:
1. Pull the master or slave module out several inches from the
MMU backplane.
2. If round type cables are already installed in the termination
mounting unit, remove the cable retaining bracket.
Table 2-2. NIDI01 Cable Applications
Nomenclature/
Description
Application
Connections
Maximum
Length
NKTU02 PVC
Termination Cable
Connects the IDI module to the
master or slave module.
P1 of the IDI module to P3 of
the master or slave module.
61 m
(200 ft)
NKTU12 non PVC
Termination Cable
NKTM01 Ribbon
Communication Cable
Connects the IDI module to the
master or slave module.
P1 of the IDI module to P3 of
the master or slave module.
30 m
(100 ft)
Standard 14 to 22 AWG
Wire
Connects field and power (18
AWG) wiring to the IDI module.
Field or power source to the
IDI terminal strip.
N/A
CAUTION
Remove modules (slave, master or termination) from their
assigned slots before installing a cable to that slot. Also,
remove stations from their housing before installing a cable to
that housing. Failure to do so could result in damage to the
module or station.
ATTENTION
Retirer les modules (asservi, maître ou carte de raccordement)
de leur position assignée avant d'installer un câble à cette
position. Egalement, retirer les postes de commande de leur
boîtier avant d'installer un câble dans ce boîtier. Des dom-
mages au module ou au poste pourraient résulter d'un man-
quement à cette procédure.