INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-420A
2 - 3
To install the cable follow these steps.
1. Pull the slave module in the calibration slot several inches
from the MMU backplane.
2. If round type cables are already installed in the TMU card
cage, remove the cable retaining bracket (Bailey part number
258436A1). Use NKTU02, NKTU12 or NKTM01 cables.
Figure 2-1. Cable Connections for the NIAC02 Module
Table 2-1. NIAC02 Cable Applications
Nomenclature/
Description
Application
Connector
Maximum
Length
NKTU02 cable
(PVC Jacket)
Connects NIAC02 module
to calibration slot
P1 on NIAC02 module to
MMU backplane
61
(200 ft)
NKTU12 cable
(non-PVC Jacket)
NKTM01 cable
(ribbon)
Connects NIAC02 module
to calibration slot
P1 on NIAC02 module to
MMU backplane
30 m
(100 ft)
Twisted wire pair
Connects NIAC02 module
to NIAM02
TB1 terminal 3 and 4 on
NIAM02 module to TB1 1
and 2 on NIAC02 module
—
CAUTION
Remove modules from their module mounting unit slots before
installing or removing a cable assigned to that slot. Failure to
do so could result in damage to the module.
ATTENTION
Retirer le module de son emplacement dans le chassis de
montage des modules avant d'installer ou de retirer un câble
assigne a cet emplacement. Un manquement à cette procédure
pourrait endommager le module.
IMAMM03
IMASM02
(IN MMU CALIBRATION SLOT)
NKTM01
NKTU02/12
NKTM01
NKTU02/12
NIAM02
NIAC02
HARD-
WIRED
P1
P1
P2
P2
P3
P3
P1
P1
J3
J1
J4
J2
–1
–1
–3
–3
+4
+4
+2
+2
T00615A
EXTERNAL
CALIBRATION
MILLIVOLT
SOURCE