INSTALLATION
INIIL02 INFI-NET TO INFI-NET LOCAL INTERFACE INSTALLATION
I-E96-607A
3 - 17
INIIL02 INFI-NET TO INFI-NET LOCAL INTERFACE INSTALLATION
Install the modules and termination devices and cables that
make up an INIIL02 INFI-NET to INFI-NET Local Interface. The
required modules are:
•
One INIIT03 INFI-NET to INFI-NET Transfer Module.
•
Two INNIS01 modules, one for each loop.
•
Two NTCL01 Communication Termination Units or two
NICL01 Communication Termination Modules, one for
each INNIS01 module.
•
One termination unit cable or one termination module
cable for each NTCL01 or NICL01 termination device. The
NTCL01 termination unit uses NKLS01 or NKLS11 termi-
nation cables. The NICL01 termination module uses
NKLS02 or NKLS12 termination cables.
For redundant INFI-NET to INFI-NET local interfaces, double
the required modules and termination units or modules and
cables. To install an INFI-NET to INFI-NET local interface:
1. Set the jumpers on all termination units or modules.
2. Install all the termination units or modules and their
cables.
3. Set the dipswitches and jumpers on the INNIS01 modules
and INIIT03 module.
4. Check the module mounting unit for -30 VDC and modify if
necessary.
5. Prepare an isolated module mounting unit for the INIIL02
interface.
6. Install the INNIS01 modules and INIIT03 module.
Table 3-8. Optional Digital I/O Modules
Nomenclature
Output
Document No.
IMDSM05
24 VDC
I-E96-309
IMDSO01
24 to 240 VAC
I-E96-310
IMDSO02
4 to 50 VDC
IMDSO03
5 to 160 VDC
IMDSO04
24 VDC
I-E96-313