Stationary VRLA Batteries,
Installation and Operation Instructions
Page 16 of 16
w w w. b a e b a t t e r i e s u s a . c o m
R e v : 0 2 1 9
terminals has been exceeded. During this operation, the individual cell voltages
may be 0.2V below the allowable final discharge voltage.
11.0.7
The measured capacity is the product of the discharge current and the discharge
time. If the initial temperature was not 25°C (77°F) the measured capacity must
be corrected to compensate, please reference IEEE 1188 or contact BAE USA or
your local representative.
11.0.8
If the target capacity is not achieved, we request that you contact BAE USA or
your local representative. It is generally recommended that if the measured
capacity of the battery is less than 80% the battery should be considered for
replacement.
11.0.9
Recharge the battery in accordance with the charging procedure as previously
stated in the operating instructions immediately after the capacity test.
Please reference IEEE 1188 for additional guidance.
For any situation not covered in these instructions, please contact BAE Batteries USA or your
local representative immediately for guidance.