background image

Impulse Tubing Length and Configuration

Impulse tubing is used to connect the sensing taps of the cone meter to the manifold connected to the differential pressure 

transmitter  One section of tubing should connect the high-pressure tap to the high-pressure side of the differential pressure 

transmitter; another section of tubing should connect the low-pressure tap to the low-pressure side of the differential 

pressure transmitter 
•  Impulse tubing should be installed with a gradient of 1:12

 

at a minimum to help prevent undesirable fluids from being 

transferred to the differential pressure transmitter 

•  If tubing is installed in a horizontal orientation, install a gas/liquid separator device 
•  Avoid abrupt bends in impulse tubing 
•  If impulse tubing sections are long, use mounting brackets to support them  
•  Tubing length must be short enough for a high degree of accuracy, and long enough for proper cooling of  

high-temperature fluids before they reach the transmitter 

•  Make sure the installation permits access to the connection tubes, valves, valve manifolds and transmitters  

for maintenance 

•  Limit the number of fittings and avoid long tubing sections that can impair measurement accuracy and increase the risk  

of plugging  

•  Avoid changes in tubing elevation  Differences in elevation will cause a difference in the hydrostatic pressure of the liquid 

column in the process lines, which can result in inaccurate differential pressure measurements  Fasten the process lines 

together, if possible, to keep their relative elevations consistent 

•  Install process lines so that they slope in only one direction (up or down)  If piping must slope in more than one direction, 

do not allow more than one bend  Install a liquid or gas trap at the lowest point in a gas service installation  Install gas trap 

at the highest point in a liquid service installation 

Straight Pipe Run Requirements

Page 12 

June 2018

DPM-UM-00206-EN-03

Содержание Preso Gemini Cone

Страница 1: ...Differential Pressure Flow Meter Gemini Cone DPM UM 00206 EN 03 June 2018 User Manual...

Страница 2: ...Differential Pressure Flow Meter Gemini Cone Page ii June 2018 DPM UM 00206 EN 03...

Страница 3: ...sics 9 Installation Checkpoints for the Transmitter 9 Mounting Location 10 Meter Orientation and Transmitter Position 10 Pressure Tap Location 10 Line Installation 11 Differential Pressure Connections...

Страница 4: ...team Service 17 Installation Options 17 Horizontal Meter Installation 17 Vertical Meter Installation 19 Transmitter Calibration 19 System Modifications 20 Square Root Error 20 Gauge Line Error 20 Elev...

Страница 5: ...SERVICE OPEN VALVES VERY SLOWLY TO AVOID SLUGGING IN THE METER RUN WARNING SECURE ALL CONNECTIONS PROPERLY BEFORE STARTING UP A SYSTEM KEEP A SAFE DISTANCE AWAY FROM THE PROCESS UPON STARTUP WARNING...

Страница 6: ...d electronic signal typically via Modbus or a 4 20 mA output to a flow computer or other process controller for interpretation and readout For compressible fluids line pressure and temperature measure...

Страница 7: ...Components Valve Manifolds A 3 way or 5 way valve manifold isolates the transmitter from the process lines A manifold allows the operator to calibrate the transmitter without removing it from the impu...

Страница 8: ...mini Cone meter be installed with zero to five pipe diameters and zero to three pipe diameters downstream 0 4 0 5 0 6 0 7 0 8 Flow B A Single Elbow A 0 0 0 1 1 B 0 0 0 1 1 Flow B A Two Elbows In Plane...

Страница 9: ...ESSURE TRANSMITTER IF HIGH TEMPERATURE FLUIDS ARE LIKELY TO BE ENCOUNTERED MAKE SURE THE CONNECTION TUBING IS RATED FOR THE ANTICIPATED TEMPERATURE RANGE Installation Checkpoints for the Transmitter B...

Страница 10: ...f flow will cause improper results and potentially damage the meter For vertical installations the location of differential pressure taps is unrestricted as long as the static pressure tap is upstream...

Страница 11: ...reads with a process compliant thread sealant prior to tightening Once tightened torque mark all fittings for future reference Transmitter Connection Tubing Before connecting the Gemini Cone meter to...

Страница 12: ...egree of accuracy and long enough for proper cooling of high temperature fluids before they reach the transmitter Make sure the installation permits access to the connection tubes valves valve manifol...

Страница 13: ...the liquid taps above the centerline can accumulate air or non condensing gases In liquid service the connecting lines from the meter shall slope downward to the transmitter with no upturns or pockets...

Страница 14: ...OW PRESSURE PORT WITH AN INERT FLUID BEFORE STARTING THE METER NOTE N Do not use downward flow piping configurations that use the standard upstream and downstream pressure ports for liquid application...

Страница 15: ...to drain away from the transmitter If the connecting tubing extending from the cone meter to the transmitter is not installed in a vertical position it should slope upward at least 1 12 for proper dra...

Страница 16: ...o the manifold see Figure 7 IF THERE IS ANY LIQUID PRESENT IN THE GAS DO NOT USE THE PIPING ARRANGEMENT SHOWN IN Figure 7 THE U CONFIGURATION COULD TRAP LIQUID IN THE CONE CHANGING THE DOWNSTREAM PRES...

Страница 17: ...ired Modern DP transmitters have very little diaphragm movement and do not require the large volume condensate chamber Horizontal Meter Installation Install the pressure taps above the horizontal cent...

Страница 18: ...8 Typical horizontal installation for steam Flow Side View Instrument Taps Not In the Same Plane HI LO By pass Valve Front View Filling Crosses Fill with water to same level DP Transmitter or Direct R...

Страница 19: ...ial pressure transmitter must be zeroed when zero flow has been established in the main line When the process is turned off particulates may settle into the low pressure port Flush the low pressure po...

Страница 20: ...han the other the hydrostatic head of the lines will vary resulting in inaccurate differential pressure measurement Similarly if the temperature of liquid in one leg is different from the temperature...

Страница 21: ...Factory 5 NACE WMP only B 10 A RF flange 150 calibration MR0103 3 5 Valve manifold C 20 B RF flange 300 Instrument Valve 2 Special X Other WMP only D 30 C RF flange 600 A 1 4 Needle valve CS calibrati...

Страница 22: ...ransmitter Calibration X Other Mounting Pipe Schedule Instrument Valve 1 Factory 2 3 Valve manifold 0 None A Standard Process Connection A 1 4 Needle valve CS calibration WMP only B 10 F NPT C 1 4 Nee...

Страница 23: ...edle valve CS Z Not required WMP only X Other C 1 4 Needle valve SS Welding 4 Mounting Pipe Schedule D 1 2 Needle valve SS Standard bracket only A Standard Instrument E 1 2 Gate w cross CS steam A Sta...

Страница 24: ...r Meter with five data points 0 5 percent accuracy Pipe schedule Standard is schedule 40 up to 10 in and 3 75 in wall at 12 in and larger www badgermeter com Preso is a registered trademark of Badger...

Отзывы: