background image

ˇ

FT1

FT2XP

PFT2

PFT2E FT420XP

PEPT1

Size

Type

PFT3E

PFT420

PFT3

EPT1XP

1/2"

OP

222.96

445.92

1170.54

1"

OP

76.64

153.28

402.36

2"

OP

20.56

41.12

107.94

2"

Turbo

34.72

34.72

17.36

3"

Turbo

24.80

24.80

12.40

4"

Turbo

5.12

5.12

2.56

6"

Turbo

2.16

2.16

1.08

5/8"   25 Ind RCDL

198.40

396.80

1041.60

3/4"   35 Ind RCDL

126.67

253.34

665.03

1"

  40 Ind RCDL

89.80

179.60

471.75

1"

  70 Ind RCDL

46.80

93.60

245.70

1 1/2" 120 Ind RCDL

23.80

47.60

124.95

2"

170 Ind RCDL

14.56

29.13

76.46

the second unit in order to cascade operations.

2

-

Hi and/or Low Flow Rate Signal.

 If you program hi and

low rate setpoints, this transistor output is activated
when either setpoint is exceeded. The duration of this
pulse is determined by programming function #37.
Connect to a visual or audible alarm to alert you of
irregular flow conditions.

FUNCTION # 

36: 

 PULSE OUTPUT WIDTH

Program 1 to 99 ms. Certain electromechanical devices

require wider pulse widths. Factory default is 15 ms which
should be adequate for most applications. High frequency
output pulses require narrower pulse widths.

FUNCTION #

 42:

  Default to BATCH or RATE DISPLAY

Normally, the PC100 is used to batch. Therefore, the

display will always automatically return to batch count after
a programming procedure (code 0). If the PC100 is used
mostly for rate of flow indication, program code 1 and the
display will return to flow rate instead of batch count.

FUNCTION #

 34:

  RATE MODE ENABLE

When this function is activated (code 1), the PC100 can

only be used as a rate indicator and totalizer. All batch
functions will be inactive. The display will default to rate of
flow.

FUNCTION # 

18

:  SCALE FACTOR CALCULATION

The transmitter sends out a finite number of pulses per

gallon, liter, etc. In order to display these pulses in engineer-
ing units of measure, they must be “scaled” (multiplied by a
constant.) Function #18 allows you to program this multi-

plier or SCALE FACTOR.

The table below shows the number of unscaled pulses for

each gallon of liquid flowing through the listed Badger flow
meters with selected transmitters.

If you want the PC100 to register in whole units, you must

divide 1 by the unscaled pulses. Program the decimal point
(function #53) for "0".

If you want the PC100 to register in 0.1 units, you must

divide 10 by the unscaled pulses. Program the decimal point
(function #53) for "1".

If you want the PC100 to register in 0.01 units, you must

divide 100 by the unscaled pulses. Program the decimal point
(function #53) for "2".

If you are scaling for any other unit of measure such as

pounds, liters, ounces, etc., multiply the scale factor (in
gallons) by the appropriate conversion factor.

Example:  The unscaled pulses/gallon for a 2" OP meter

with a PFT2E transmitter is 20.56. If you wish to read to the
nearest 1/10 of a gallon, divide 10 by 20.56. The scale factor
to read to the nearest 1/10 of a gallon would be 0.4864.

Note:  If you are using a gear type scaled transmitter, or

an electronic scaled transmitter, the PC100 scale factor
should be 1.0000. In this case, the scaling is done by the
transmitter.

13

Meter

Transmitter Pulses Per Gallon

Содержание PC100

Страница 1: ...n Manual BadgerMeter Inc Model PC100 SERVICE INFORMATION FILE MANUAL FOR FUTURE REFERENCE AND SERVICE Serial Number Date Installed Service Line Operator IMPORTANT Read this manual before attempting an...

Страница 2: ...2...

Страница 3: ...OPTIONAL PROGRAMMING Display FLOW RATE instead of BATCH COUNT 13 LIMIT the batch size that can be programmed 15 AUTORECYCLE to repeat batches automatically 15 AUTOADJUST to compensate for valve overr...

Страница 4: ...put 17 Start Command 35 Serial Data Output 18 Pulse Input Doubler 36 Serial Data Output CAUTION Topreventaccidents powerconnectionshould HOW TO UNPACK ASSEMBLE AND INSTALL THE PC100 4 Note K1 relay co...

Страница 5: ...a maximum humidity of 85 non condensing Select a mount ing location with proper ventilation Warning To prevent the danger of electrical shock or explosion turn off the power in any circuits that may i...

Страница 6: ...ng transmitter input 2 on terminal 10 EPT1XP PEPT1 TYPE B These models require that a special current regulator supplied with the transmitter be installed exactly as shown Reversing the polarity will...

Страница 7: ...stage for final valve shutdown OPTIONAL APPLICATIONS FEED PUMP CONNECTION Relay K1 can be connected to a feed pump to inject or add fluidstothemainbatchonapresettimebasis RefertoF32 HI AND OR LOW FLOW...

Страница 8: ...Batch Signal Can be used to totalize batches or cycle runs during a period of time or to cascade several PC100s so that one PC100 can start when the other finishes This signal duration is adjustable F...

Страница 9: ...input of the next unit Serial connection will be interrupted to all units if the power supply fails on any one of the PC100s To prevent this from happening you may want to connect a communications rel...

Страница 10: ...eturn the display to batch count The 5 key is used to display the instanta neous flow rate in GPM LPM etc The 0 key is used to RESUME operation from the point where a STOP command was received To View...

Страница 11: ...ode Enable 13 35 Serial Output Select Pulse or Information 17 36 Pulse Output Width 1 to 99 ms 13 37 Rate Output Latch 16 lower digits ProgramingthePC100isverysimple Exceptforprogram ming batch preset...

Страница 12: ...talize the number of batches run for a period of time day week year or shift If connected to terminal 17 a second PC100 it can be used to start The display will show Once all wiring has been completed...

Страница 13: ...ction is activated code 1 the PC100 can only be used as a rate indicator and totalizer All batch functions will be inactive The display will default to rate of flow FUNCTION 18 SCALE FACTOR CALCULATIO...

Страница 14: ...nctions by scrolling up or down but you will not be able to enable or disable them To operate this function press FUNCTION 41 ENTER At this point you will see the three digits to the right The two dig...

Страница 15: ...prewarn signal is used to control an alarm or a feed pump the signal duration can be programmed from 1 to 99 seconds Never use the time out if K1 is connected to the first stage of a valve FUNCTION 1...

Страница 16: ...etpoint is lower than the Hi setpoint If not the display will flash zeros and if con nected to a printer or computer an ERROR message will be transmitted FUNCTION 37 RATE OUTPUT LATCH The choices are...

Страница 17: ...1 second and 1 for 1 second FUNCTION 63 PRINT ON START AND OR STOP Program 1 to print on START Program 2 to print on STOP Program 3 to print both on START and on STOP FUNCTION 64 PRINT COMMAND Progra...

Страница 18: ...visible count on the display when scale factor 1 5 Wrong scale factor 5 Check scale factor calculation i e if programmed 0001 instead of 1 0000 unit will wait for 1000 pulses before decrementing count...

Страница 19: ...the unit is still not functioning appropriately There is the possibility that some internal component has been damaged and it is preventing normal operation At this point it is recommended that you ru...

Страница 20: ...ithout notice except to the extent an outstanding bid obligation exists BadgerMeter Inc P O Box 245036 Milwaukee WI 53224 9536 Telephone 414 355 0400 877 243 1010 Fax 414 355 7499 866 613 9305 www bad...

Отзывы: