Badger Meter ModMAG M2000 Скачать руководство пользователя страница 8

M-Bus addressing 

Page 8/14 

 

 MID_M2000_BA_MB_02_1805 

Please  note that  writing  to the configuration  area  is  under  any  circumstances 

limited to 20 times per 24 hours. Even with the above mentioned command it is 

not possible to write more often. 

 

4.8 

Send ModBus

®

 commands 

Since not all of the ModBus

®

 registers of the ModMAG

®

 M2000 are retrievable 

using  "native"  M-Bus  commands,  it  is  also  possible  to  encapsulate  "native" 

ModBus

®

 commands within a M-Bus command. It is then possible to use all the 

ModBus

®

 commands understood by the  ModMAG

®

  M2000 (0x03, 0x04, 0x06 

and 0x10, register reading and writing) with a M-Bus interface too.  

 

Request (values in hex):  

68 LL LL 68 73/53 PAddr 51 0F [ModBus] ChkS 16  

 

send ModBus

®

 command 

  

LL: Length byte of M-Bus telegram  

[ModBus]: ModBus

®

 command without CRC  

 

e.g.:  

68 0A 0A 68 73/53 PAddr 51 0F 01 03 00 43 00 05 ChkS 16  

 

The underlined part is the ModBus

®

 command for reading the address 0x0043 

(5 registers) of the ModMAG

®

 M2000.  

 

Answer (values in hex):  

68 LL LL 68 08 PAddr 72 SecAddr AccessCtr Status Signature  
0F [ModBus] ChkS 16  

 

e.g.:  

68 1D 1D 68 08 00 72 95 09 10  

19 A9 09 01 07 08 01 00 00

 Header for M-Bus RSP_UD  

0F

 Flag: manufacturer specific  

01 03 0A 31 39 31 30 30 39 39 35 00 00

 ModBus

®

 answer  

ChkS 16  

 

Please  note  however,  that  in  case  of  using  the  encapsulated  ModBus

®

 

commands, the M-Bus communication timeout should be increased (e.g. from 

50  ms  to  400  ms),  since  the  requested  registers  are  directly  read  and  the 

results are returned within the answer to the request.  

 

Please note also that these commands are compatible with M-Bus physical and 

link layers, but not completely compatible with the application layer. Therefore, 

all standard  M-Bus communication lines  will transmit the command, however, 

the software on the application side must be able to understand and interpret 

the command. 

 

4.9 

M-Bus REQ_UD2 answers 
As mentioned before, the module may answer a REQ_UD2 data request by five 

different RSP_UD answers according to its configuration:  

All: 

Contains the volumes, flow rate, flow speed, flow direction, etc.  

Instantaneous: Contains a short form of "All" with only the volumes, flow rate 

 

and flow direction (smaller telegram = faster reading)  

Testing: 

Contains  the  meter  diagnostic  counters  of  the  ModMAG

®

 

 

M2000  

Содержание ModMAG M2000

Страница 1: ...Badger Meter Europa GmbH ModMAG M2000 M Bus interface User manual May 2018 MID_M2000_BA_MB_02_1805...

Страница 2: ...ary address 6 4 5 Changing baud rate 6 4 6 Changing M Bus response telegram 7 4 7 Write configuration area to flash 7 4 8 Send ModBus commands 8 4 9 M Bus REQ_UD2 answers 8 4 9 1 M Bus REQ_UD2 answer...

Страница 3: ...primary address is saved in a non volatile memory 300 2400 and 9600 baud communication speed Automatic baud rate detection or manually programmable baud rate Standard M Bus serial communication parame...

Страница 4: ...in board The interface board is supported by a pad to the wall of the enclosure A grounding strap connect the interface board terminal 63 to the nearest screw of the main board 3 1 Electrical connecti...

Страница 5: ...e addressed using its primary address range 0 250 The default factory setting primary address of the module is 0 zero The primary address can be reconfigured using the appropriate M Bus command see be...

Страница 6: ...urs time 4 5 Changing baud rate By default factory setting the module is automatically set to detect the baud rate of the incoming M Bus request telegram Usually it is not necessary to change this set...

Страница 7: ...s are then answered with the selected telegram Please note that the RSP_UD telegram setting is not written immediately in the non volatile flash memory of the module but only On the cyclic 24 hours re...

Страница 8: ...Signature 0F ModBus ChkS 16 e g 68 1D 1D 68 08 00 72 95 09 10 19 A9 09 01 07 08 01 00 00 Header for M Bus RSP_UD 0F Flag manufacturer specific 01 03 0A 31 39 31 30 30 39 39 35 00 00 ModBus answer Chk...

Страница 9: ...for handling readout requests see also EN13757 3 chapter 8 3 4 9 1 M Bus REQ_UD2 answer All N ModBus register Description 0 0x00CF T1 T in m3 1 0x00D7 T2 T in m3 2 0x00D7 T3 TN in m3 3 0x00E7 T1 T Ro...

Страница 10: ...03 Inst Volume m3 1 1 0 0 REAL4 0 000000e 000 Inst Volume m3 2 2 0 0 REAL4 1 854350e 003 Inst Volume m3 3 0 0 0 REAL4 0 000000e 000 Inst Volume Flow 1 sec 10E3 4 0 0 0 INT2 0 Inst Control signal N Uni...

Страница 11: ...er factor 7 0x007B FACTORY Amplifier factor 8 0x007D Detector current in mA 9 0x007F FACTORY Detector current in mA 10 0x0081 Power line frequency in Hz 11 0x0082 Excitation frequency in Hz 12 0x010B...

Страница 12: ...major version 12 0x0059 Daugtherboard minor version 13 0x011C Security status N Unit Tariff Storage Data Value Funct VIB 0 0 0 0 INT2 1 Inst Model Version 1 0 0 0 Var M2000 Inst Model Version 2 0 0 1...

Страница 13: ...ction at firmware start 8 data bits 1 stop bit 1 even parity bit Phoenix IMC 1 5 11 G 3 81 connector to M2000 M Bus interface 2 wire EN13757 compatible M Bus interface 300 2400 9600 baud auto baud det...

Страница 14: ...Harmlessness declaration Page 14 14 MID_M2000_BA_MB_02_1805 6 Return of goods for repair Harmlessness declaration Please refer to our claims return form harmlessness declaration under www badgermeter...

Страница 15: ......

Страница 16: ...N rtinger Strasse 76 72639 Neuffen Germany E mail badger badgermeter de www badgermeter de Durchflu richtung r ckw Durchflu richtung r ckw Stromausg ang aktiv 0 4 20mA Vorw rts Normal offen Normal ges...

Отзывы: