BTU CONFIGURATION
Btu rate units = [0-5] – set the Btu rate units:
0: kBtu/hr
1: Btu/min
2: kW
3: TR
4: J/s
5: Custom
Btu rate ndigits = [2-10] – number of decimal digits to display
Btu rate custom label = [string] – Btu rate custom unit label
Btu rate custom conv = [0-100] – custom unit conversion
factor
Btu total units = [0-6] – Btu totalizer units:
0: BTU
1: kBTU
2: MBTU
3: kWh
4: MWh
5: kJ
6: Custom
Btu total ndigits = [2-10] – number of decimal digits to
display
Btu total custom label = [string] – Btu totalizer custom
unit label
Btu total custom conv = [0-100] – custom unit
conversion factor
Btu total mode = [0-2] – totalizer mode:
0: Heating
1: Cooling
2: Heating & Cooling
Btu sensor type = [0-4] – temperature sensor type:
0: DI Thermistor
1: DI RTD
2: Custom Thermistor
3: Custom RTD
4: No sensor
Btu sensor correct_k = [0-10] – correction factor
Btu sensor temp_unit = [0-1] – temperature units to
display
0: deg F
1: deg C
Btu sensor t2adj = [-10-10] – t2a
RELAY OUTPUT CONFIGURATION
relay [1-5] func = [0-9] – relay function; relay 5 is the pulse
output
0: Totalizer
1: Alarm
2: Manual Control
relay [1-5] input = [0-8] – relay input; depends on source
for totalizer:
0: Flow 1 Total
for alarms:
0: Flow 1 Rate
relay [1-5] units = [0-19] – units on setpoints/rates; depends on
src/input
flow units: same as 'flow [1-2] rate units' above
volume units: same as 'flow [1-2] total units'
relay [1-5] manual = [on/off] – manually set relay on or off, if in
manual mode
relay [1-5] rate = [x] – totalizer rate
relay [1-5] ctime = [0-10000] – pulse width in milliseconds
relay [1-4] latch = [on/off] – turn on/off relay latching
relay [1-4] setpoint = [x]
relay [1-4] releasepoint = [x]
ANALOG OUTPUT CONFIGURATION
analogout [1-2] func = [0-3]
0: Flow rate
1: BTU rate
2: Temperature
3: PID control
analogout [1-2] src = [0-4]
for flow rate:
0: Flow 1 rate
1: Flow 2 rate
2: Flow sum
3: Flow 1-2
4: Flow 2-1
for Btu rate: not used
for temperature:
0: Flow rate
1: Temp 2
2: Temp Delta
for PID control:
0: Flow 1 rate
1: Flow 2 rate
analogout [1-2] range – [0-1]
0: 0-20mA
1: 4-20mA
analogout [1-2] low = [x] – value corresponding to 0 (or 4) mA
analogout [1-2] high = [x] – value corresponding to 20mA
analogout [1-2] setpoint = [x] – PID setpoint
analogout [1-2] P = [x] – PID constants
analogout [1-2] I = [x] – PID constants
analogout [1-2] D = [x] – PID constants
Содержание Impeller Data Industrial 3050 Series
Страница 2: ...Series 3050 Btu Monitor Page ii 6 11...
Страница 4: ...Series 3050 Btu Monitor Page iv 6 11...
Страница 18: ...Page 18 6 11 Series 3050 Btu Monitor Page 13 Programming Flow Chart...
Страница 19: ...Page 19 6 11 Installation Operation Manual...
Страница 20: ...Page 20 6 11 Series 3050 Btu Monitor Page 15...
Страница 21: ...Page 21 6 11 Installation Operation Manual Page 16...
Страница 22: ...Page 22 6 11 Series 3050 Btu Monitor Page 17...
Страница 23: ...Page 23 6 11 Installation Operation Manual Page 18...
Страница 30: ...Page 30 6 11 Series 3050 Btu Monitor Intentionally blank page...
Страница 31: ...Page 31 6 11 Installation Operation Manual Intentionally blank page...