Programming Procedures
Operating Pressure (OP PRES) (Displayed for GAS Meters Only)
The
Operating Pressure
parameter is used in conjunction with
Operating Pressure Unit
s in
gas applications to compensate for the actual pressure being measured at the meter Enter
the operating pressure in either Bar or PSI units, depending on the
Operating Pressure Units
selected Edit with the
"List Item Selection Procedure" on page 15
Operating Temperature Unit (TMP UNIT) (Displayed for GAS Meters Only)
The
Operating Temperature Units
parameter is used in conjunction with
Operating
Temperature
in gas applications to compensate for the actual temperature of the gas being
measured at the meter The meter allows the selection of the operating temperature units,
°F or °C Edit with the
"List Item Selection Procedure" on page 15
Operating Temperature (OP TEMP) (Displayed for GAS Meters Only)
The
Operating Temperature
parameter is used in conjunction with
Operating Temperature
Units
in gas applications to compensate for the actual temperature of the gas being
measured at the meter Enter the operating temperature in either °F or °C, depending on
the
Operating Temperature Units
selected Edit with the
"List Item Selection Procedure" on
Specific Gravity Correction Factor (SP GRAV)
The
Specific Gravity
parameter is used to compensate for the specific gravity of the liquid
or gas being measured with the meter Edit with the
"List Item Selection Procedure" on
Damping (DAMPING)
The
Damping
factor is increased to enhance the stability of the flow readings Damping
values are decreased to allow the flow meter to react faster to changing values of flow This
parameter can range from 0…99 The factory default is 0 Edit with the
Output Mode (OUT MODE)
The MR flow transmitter has three analog output modes:
•
4…20 mA Output Signal
•
0…5V DC Output Signal
•
0…10V DC Output Signal
The
Output Mode
required is determined by the type of peripheral device being connected
to the MR flow transmitter Edit with the
"List Item Selection Procedure" on page 15
OTEE:
N
Setup prompts and descriptors for configuring and calibrating the analog output correspond
to the selected
Output Mode
Page 18