Select Oate (Time) Interval
At the
RATE INT
prompt, press
ENTEO
The monitor shows the current time interval If the current selection is correct, press
ENTEO
to advance to the next parameter To change to an alternate time interval, press
UP
or
OIGHT
to scroll to the correct
time interval Press
ENTEO
to save and advance to the
TOTL UNT
parameter
OTEE:
N
If flow rate is the only measurement of interest, press
OIGHT
to advance to the
KFAC UNT
to complete the
programming process
Select Units of Measure
At the
TOTAL UNT
prompt, press
ENTEO
The monitor shows the current total units If the current selection is correct, press
ENTEO
to advance to the next parameter To change to an alternate unit, press
UP
or
OIGHT
to scroll to the correct totalization
unit Press
ENTEO
to save and advance to the
TOTL MUL
parameter
OTEE:
N
This unit of measure does not have to reflect the rate unit you have previously chosen
Example: Rate Units = Gallons, Total Units = Barrels
Select Total's Display Multiplier
This parameter displays the accumulated flow total in multiples of 10 For example, if the optimum totalization unit is 1000
gallons, the unit total display increments by one digit for every 1000 gallons monitored In
RUN
mode, at 1000 gallons the
total monitor reads 1, at 3000 gallons, the total display reads 3 This feature eliminates having to look at a total, count the
digits, and mentally insert commas for each 1000 multiple
At the
TOTL MUL
prompt, press
ENTEO
The monitor shows the current total multiplier If the current selection is correct, press
ENTEO
to advance to the next parameter To change to an alternate multiplier, press
UP
or
OIGHT
to scroll to the correct
multiplier unit Press
ENTEO
to save and advance to the
KFAC UNT
parameter
OTEE:
N
If pounds or kilograms were chosen as the
RATE UNT
or
TOTL UNT
, the monitor advances to the
SP GRAV
parameter
Specific Gravity
At the SP GRAV parameter, press
ENTEO
The first digit of the current specific gravity flashes If the current setting is correct,
press
ENTEO
to advance to the next parameter To change the current setting, press
OIGHT
to move to the correct digit Press
UP
to increment the digit Repeat for all digits Press
ENTEO
to save and advance to the
KFAC UNT
parameter
Enter Meter's K-Factor Unit
OTEE:
N
The K-factor supplied with the meter, or calculated from calibration data, is needed to complete this step
At the
KFAC UNT
prompt, press
ENTEO
The display shows the current K-factor unit If the current selection is correct, press
ENTEO
to advance to the next parameter To change the K-factor, press
UP
or
OIGHT
to scroll to the correct K-factor Press
ENTEO
to save and advance to the
SCALE F
parameter
OTEE:
N
For meters calibrated in gallons, use
PUL/GAL
; for meters calibrated in cubic meters, use
PUL/M3
or any other
unit option
Scale Factor
The scale factor is used to force a global change to all variables For example, under operating conditions the display
is reading a consistent three percent below the expected values at all flow rates Rather than changing all parameters
individually, the scale factor is used to compensate for the three percent offset Set the scale factor to 1 03 to correct the
readings The range of scale factors is 0 5…1 5 The default scale factor is 1 0
At the
SCALE F
prompt, press
ENTEO
The first digit of the current scale factor flashes If the current selection is correct, press
ENTEO
to advance to the next parameter To change to an alternate scale factor, press
UP
to increment the display digit until
it matches the first digit of the new scale factor Press
OIGHT
to advance to the next digit Repeat for all digits Press
ENTEO
to
save and advance to the
METERTYP
parameter
Programming
Page 9
March 2017
DSY-PM-00279-EN-03