SPECIFICATIONS
Power Supply
Options
Battery Powered
One D size, 1 5V alkaline battery
Loop Powered
4…20 mA loop power
Power Consumption
Battery Powered
Less than 1 mA @ 1 5V DC
Loop Powered
25 mA (maximum)
Alphanumeric Oate
and Total Display
Eight digit, 0 5 inch high numeric display
Eight character, 0 25 inch high alphanumeric display
Pulsed Output Signal
Type
Outputs one pulse for each increment of the least significant
totalizer digit
Max Voltage
30V DC
Pulse Type
Opto-Isolated open collector transistor
Pulse Width ON State
20 mS / maximum pulse rate 20 Hz
Current (ON State)
0 9V drop @ 5 0 mA or 0 7V drop @ 0 1 A
Magnetic Pickup
Inputs
Frequency Range
0…3500 Hz
Trigger Sensitivity
30 mV p-p
Over Voltage Protected
±30V DC
Frequency Measurement
Accuracy
±0 1%
Temperature Drift
50 ppm / °C maximum
Optional Analog
Output (Loop
Powered Version)
Type
4…20 mA current loop
Resolution
1:4000
Transient Over Voltages
Category 3, in accordance with IEC664
Pollution Degree
2, in accordance with IEC664
Mounting Classification
NEMA/UL/CSA Type 4 (IP66)
Environmental
Operating Temperature
–22…158° F (–30…70° C)
Humidity
0…90% non-condensing
Certification
CSA Ordinary Locations
C22 2 No 1010-1 for Canada; ANSI/ISA S82 02 for US
CSA Hazardous Locations
Class I, Div 1 Groups B,C, D; Class II, Div 1 Groups E, F, G; Class III; Type
4X; T6 @ 70° F; C22 2 No 30; C22 2 No 25
UL 698, UL 1203
Specifications
Page 14
March 2017
DSY-PM-00277-EN-03