User Manual
Sensor
Series 735 Plastic Tee Type Flow Sensor
SEN-UM-01665-EN-04 (October 2015)
Страница 1: ...User Manual Sensor Series 735 Plastic Tee Type Flow Sensor SEN UM 01665 EN 04 October 2015 ...
Страница 2: ...lectronic Types 4 IR Sensor 4 Series 735 4 Mechanical Installation 4 Electrical Installation Guidelines 5 Flow Sensor Installation 6 Additional Information 7 Calibration 8 Calibration Table 8 Dimensions 9 Specifications 10 Ordering Matrix 11 Sensor Series 735 Plastic Tee Type Flow Sensor Page ii October 2015 SEN UM 01665 EN 04 ...
Страница 3: ...uld result in severe personal injury or death Indicates a hazardous situation which if not avoided is estimated to be capable of causing minor or moderate personal injury or damage to property Considerations THE IMPELLER STYLE FLOW SENSOR DESCRIBED IN THIS MANUAL IS NOT INTENDED FOR USE IN SAFETY CRITICAL APPLICATIONS USE OF THE DEVICE IN THIS MANNER IS DONE AT THE SOLE DISCRETION OF THE CUSTOMER ...
Страница 4: ...eature a modified PVC tee with solvent weld socket end connections and a removable PPS sensor insert Available sizes are 1 2 in 12 7 mm 3 4 in 19 05 mm and 1 in 25 4 mm BSP threaded adapters are available MECHANICAL INSTALLATION DEPRESSURIZE AND VENT PIPING SYSTEM PRIOR TO ANY INSTALLATION OR MAINTENANCE OF THE FLOW SENSOR The accuracy of flow measurement for all flow measuring devices is highly d...
Страница 5: ...ke sure the epoxy is hardened before inverting the splice or dropping it in standing water Do not make an underground splice unless absolutely necessary Route the cable from the sensor to a Badger Meter flow monitor or endpoint The cable may be extended up to 2000 ft using two conductor shielded 20 AWG or larger stranded copper wire with appropriate ratings Leave enough flexibility in the cable or...
Страница 6: ...ate primer and cement according to the manufacturer s instructions Do not use or leave excess glue Glue build up in the tee can affect the measurement performance of the unit and or prevent the impeller from turning Do not let the glue or primer contact the bore where the O rings seal 4 Insert the sensor into the tee carefully lining up the locating hole in the sensor with the locating pin in the ...
Страница 7: ...edule 40 Keep all parts as clean as possible Do not let the glue or primer contact the surfaces where the O rings make their seal Although the meter can measure at velocities up to 20 ft sec do not exceed velocities above 7 5 ft sec Flow Sensor Installation Page 7 October 2015 SEN UM 01665 EN 04 ...
Страница 8: ...ibration Table Size Schedule K Offset 1 2 S40 0 078000 0 9 1 2 SDR 13 5 0 120119 0 1 3 4 S40 0 156300 0 9 3 4 SDR 21 0 197000 0 6 1 S40 0 261119 1 2 1 SDR 21 0 321739 0 6 Input the information in the table above into the following equation to determine the frequency of the Series 735 Impeller flow sensors Freq gpm K offset This information is required when calibrating an output board when using th...
Страница 9: ...P Optional 1 2 in Ø 0 840 3 85 in 97 8 mm 3 06 in 77 7 mm 6 086 in 154 6 mm 3 4 in Ø 1 050 3 85 in 97 8 mm 3 31 in 84 1 mm 6 775 in 172 1 mm 1 in Ø 1 315 3 94 in 100 1 mm 3 50 in 88 9 mm 6 775 in 172 1 mm Dimensions Page 9 October 2015 SEN UM 01665 EN 04 ...
Страница 10: ...ll scale over recommended design flow range Repeatability 1 5 of full scale over recommended design flow range Linearity 1 5 of full scale over recommended design flow range Transducer Excitation 8 35V DC max input source limited to 100 mA Quiescent current 600 uA 8 35V DC max Quiescent voltage Vhigh Supply Voltage 600 uA Supply impedance ON State Vlow Max 1 2V DC 40 mA current limit 15 Ω 0 7V DC ...
Страница 11: ... 1 Sch 40 only PV SIZE 0 5 05 0 75 07 1 10 0 5 with BSP Adapters 06 0 75 with BSP Adapters 08 1 with BSP Adapters 11 ELECTRONICS HOUSING PPS 0 ELECTRONICS IR Irrigation 6 O RING EPDM 1 SHAFT Tungsten Carbide 2 IMPELLER 300 SST 0 BEARING UHMWPE 1 Ordering Matrix Page 11 October 2015 SEN UM 01665 EN 04 ...
Страница 12: ...eter de las Americas S A de C V Pedro Luis Ogazón N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 México DF México 52 55 5662 0882 Europe Middle East and Africa Badger Meter Europa GmbH Nurtinger Str 76 72639 Neuffen Germany 49 7025 9208 0 Europe Middle East Branch Office Badger Meter Europe PO Box 341442 Dubai Silicon Oasis Head Quarter Building Wing C Office C209 Dubai UAE 971 4 371 2503 C...