Series 380 Impeller Btu System

Series 380 BACnet Object Map

Description

ID

Name

Units

Analog Input

AN1

TempIn

ºC, ºF

Analog Input

AN2

TempOut

ºC, ºF

Analog Value

AV1

VolFlow

gpm, gph, lpm, lps, lph, 

ft

3

/s, ft

3

/m, ft

3

/h, m

3

/s, 

m

3

/min, m

3

/h, custom

Analog Value

AV2

EnergyFlow

kBtu/min, kBtu/h, kW, 

MW, HP, Tons, custom

Analog Value

AV3

TotalVol

gallons, galx100, 

galx1000, liters, ft

3

, m

3

custom

Analog Value

AV4

TotEnergy

Btu, kBtu, MBtu, kWh, 

MWh, kJ, MJ, custom

Analog Value

AV5

TempMode

dimensionless

Analog Value

AV6

FFilterCoef

dimensionless

Analog Value

AV7

TFiltCoef

dimensionless

Analog Value

AV8

SpHtCapac

Btu/lb-F

Analog Value

AV9

Density

lb/gallon

Analog Value

AV10

SerialNum

dimensionless

BACnet Protocol Implementation Conformance Statement

BMA Doc. x – 00x 

Page 1 of 1 

BACnet Standardized Device Profile 

Device Profile 

Tested 

BACnet Smart Actuator (B-SA) 

� 

Supported BIBBs 

Supported BIBBs 

BIBB Name 

Tested 

DS-RP-B 

ReadProperty - B

� 

DS-WP-B 

WriteProperty - B

� 

DM-DDB-B 

Dynamic Device Binding - B (Who-Is, I-Am) 

� 

Standard Object Types Supported 

Object Type

Creatable 

Deletable 

Tested 

Analog Input  

No 

No 

� 

Analog Value 

No 

No 

� 

Device 

No 

No 

� 

Data Link Layer Options 

Data Link 

Options 

Tested 

MS/TP Slave 

baud rates:  9600, 19200, 

38400, 76800 bps 

� 

Segmentation Capability 

Segmentation Type 

Supported 

Window Size 

(MS/TP product limited to 1)

Tested 

Able to transmit segmented messages 

No 

 

N/A 

Device Address Binding 

Static Binding Supported 

Tested 

No 

N/A 

Character Sets 

Character Sets supported 

Tested 

ANSI X3.4 

� 

Figure 6:  BACnet Device Profile

Содержание 380CS

Страница 1: ...Series 380 Impeller Btu System 380CS HS Installation Operation Manual PN 880102 0001 Rev 4 7 11 IMPORTANT This manual contains important information READ AND KEEP FOR REFERENCE...

Страница 2: ...Series 380 Impeller Btu System Page ii 7 11...

Страница 3: ...ION 6 COMMISSIONING 7 RS 485 Network Configurations 8 RS 485 Network Configurations Modbus 8 RS 485 Network Configuration BACnet 9 SPECIFICATIONS 11 MECHANICAL 11 ELECTRICAL 11 Inputs 11 Output 11 MAT...

Страница 4: ...Series 380 Impeller Btu System Page iv 7 11...

Страница 5: ...nnection Setup includes energy measurement units measurement method communications protocol pulse output option fluid density and specific heat parameters Cold Service 380CS Designed for operating in...

Страница 6: ...low flow rates Any circumferential location is correct for installation in vertical pipes Rising flow is preferred to reduce effects of any trapped air Installing the Sensor Tee 1 Position the tee for...

Страница 7: ...f Zero parameter is the difference between T1 and T2 that will still read 0 energy rate If the Scaled Pulse Output is going to be used the user can select what the pulse is representing Energy or Flow...

Страница 8: ...ode RTU or ASCII The Series 380 uses IEEE 754 Float Data Located in Read Holding Registers The Series 380 Data Format is Float 32 where the Data is stored across two Read Holding Registers In the case...

Страница 9: ...Float Read Only Temp Coef 40017 40018 IEEE 754 Float Read Only Specific Heat 40019 40020 IEEE 754 Float Read Only Fluid Density 40021 40022 IEEE 754 Float Read Only RS 485 Network Configuration BACne...

Страница 10: ...n Analog Value AV10 SerialNum dimensionless BACnet Protocol Implementation Conformance Statement BACnet Standardized Device Profile Device Profile Tested BACnet Smart Actuator B SA Supported BIBBs Sup...

Страница 11: ...200 300 380HS 30 250 Ketron Brgs Aflas seals 220 280 380HS 30 250 Ketron Brgs Aflas seals 240 260 380HS 30 250 Ketron Brgs Aflas seals 250 230 380HS 30 250 Ketron Brgs Aflas seals Rating is based on...

Страница 12: ...m Sensor Body Sizes Tee Sizes 0 75 1 1 25 1 5 and 2 NPT Recommended Design Flow Range 1 to 15 FPS Accuracy Flow Calculation 2 of flow rate within flow range 0 5 Repeatability RTD Meets IEC751 Class B...

Страница 13: ...Page 13 7 11 Installation Operation Manual Intentional Blank Page...

Страница 14: ...e to continuous research product improvements and enhancements Badger Meter reserves the right to change product or system specifications without notice except to the extent an outstanding contractual...

Отзывы: