Страница 1: ...trated Parts List 4 1 To avoid damage in transit Badger products are shipped to the customer in special shipping containers Upon receipt of the product perform the following unpacking and inspection p...
Страница 2: ...ays SPDT 1 amp at 24 VDC 0 5 amp at 120 VAC DISPLAY 2 line 24 character per line LCD display Indicates flow rate flow total and alarm trip status PROGRAMMING Front panel mounted 5 button keypad POWER...
Страница 3: ...MTG BRACKET METALLIC CONDUIT PROVIDED BY CUSTOMER J BOX PROVIDED BY CUSTOMER MAXIMUM CABLE LENGTH FROM SENSOR TO ELECTRONICS IS 1000 FT SUNSHADE FOR SENSOR PROVIDED BY CUSTOMER 2100 NOTE 4 20 mA outpu...
Страница 4: ...ench supplied in the mounting hardware package to loosen and remove all four hex bolts in the front of the housing see Figure 2 1 Separate the front and back housings CAUTION THERE IS A COAX SIGNAL WI...
Страница 5: ...12 and 14 volts When operating the meter on DC power an additional DC power source may be required to power the 4 20 mADC output Refer to the 4 20 mA signal output in the following section for instru...
Страница 6: ...relay terminal is marked NC normally closed C common and NO normally open The normally open and normally closed positions are with the relay de energized The relays are energized when they are trippe...
Страница 7: ...from that shipped by the factory The critical lengths of the cable for the component change are 150 feet and 500 feet The following shows the component value for C11 according to the sensor cable leng...
Страница 8: ...nce from a reference point on the flume or weir to the sensor Pages 2 6 through 2 9 show this dimension for the commonly used flumes and weirs Another aspect that must be considered when mounting the...
Страница 9: ...5 43 70 550 12000 31 70 24 39 25 43 47 700 16000 31 47 36 43 25 43 98 1100 25000 31 98 48 47 00 44 75 1350 35000 32 75 The H dimension is straight back from the entrance of the throat and not along th...
Страница 10: ...00 25 87 100 2100 13 87 18 38 00 28 16 85 2600 16 16 20 40 00 30 78 90 3700 18 78 24 46 00 35 07 95 7000 23 07 PALMER BOWLUS FLUME INSTALLATION Vcal FLOW H Size H Dim Vcal Full Scale GPM Full Scale H...
Страница 11: ...71 420 2100 12 71 24 26 52 600 3500 14 52 36 29 27 850 7000 17 27 48 35 17 1200 14500 23 17 60 40 69 1500 25000 28 69 72 46 78 1800 40000 34 78 84 53 17 2000 60000 41 17 96 59 54 2400 85000 47 54 V N...
Страница 12: ...98 135 250 5 98 10 20 16 180 500 8 16 12 21 06 210 700 9 06 15 23 19 250 1200 11 19 18 24 77 300 1750 12 77 21 28 45 360 3000 16 45 24 29 05 400 3600 17 05 30 34 84 500 7000 22 84 36 37 70 600 10000 2...
Страница 13: ...r covering completely around the cable making sure not to cut into the center conductor and remove the inner cover After the ends of the cable have been prepared loosen the screw on the terminal for t...
Страница 14: ...FRONT HOUSING COAX CABLE S1 BACK HOUSING POWER SUPPLY BOARD POWER OUTPUTS 4 20 MADC TEST POINTS SENSOR FIGURE 2 7 2 11...
Страница 15: ......
Страница 16: ...de and advance the screens in the Status Mode The UP DOWN and RIGHT arrow keys are used for selecting or making change sin the various screens of the meter Calibration Mode To prevent unauthorized ent...
Страница 17: ...E 14 58 IN This screen indicates the level of the fluid in the primary device and the distance from the sensor face to the fluid level This screen enables the user to verify that the sensor head mount...
Страница 18: ...n the screen The maximum level that can be simulated is the maximum level that has been programmed into the meter To leave the level simulation screen press the MENU key The display will return to the...
Страница 19: ......
Страница 20: ...of the response time of the output signal to changes in fluid level To change this value use the UP or DOWN arrow keys to change to the desired value The available values are 8 16 32 64 128 256 512 a...
Страница 21: ......
Страница 22: ...gits have been properly set press the ENTER key The following screen will appear ELEMENT FUNCTION 1 58 PWR This screen selects the power function for the primary element for which the meter is being u...
Страница 23: ......
Страница 24: ...Press the ENTER key to store the new values The screen will advance to the second set point After the second set point has been entered the following screen will appear RELAY ASSIGNMENT RELAY 01 ECHO...
Страница 25: ...key The following screen will appear DISTANCE CALIBRATION FAR DIST XX X IN This screen calibrates the meter for zero flow level If this adjustment is made the fluid surface should be smooth to assure...
Страница 26: ...9491 7333 D 16 08 67 43908 AB84 E 19 92 83 54394 D47A F 24 00 100 65535 FFFF Use the RIGHT arrow key to move the cursor under each digit and use the UP or DOWN arrow keys to change to the desired valu...
Страница 27: ......
Страница 28: ...he totalizer word is defined as follows HEX 1 000 000 x ec in Units S element primary of Flow Max Multiplier Totalizer EXAMPLE Maximum flow 1800 x 1 BPM Barrels min Totalizer multiplier BAR x 100 Tota...
Страница 29: ......
Страница 30: ...fractional part of the product by 16 to arrive at the first character in the hexadecimal equivalent Remember all numbers produced in this step are shown above Also note that the product may have no fr...
Страница 31: ......
Страница 32: ...f the next character Example 224 0 224 3 Multiply the previously found product by 16 Example 224 X 16 3584 4 Repeat steps 2 and 3 in a cyclical fashion until you have added the last hexadecimal charac...
Страница 33: ...1 400001 0025 Screw PNH S 4 40 x 3 8 SS 4 4A 400029 0002 Screw Hex shrh 1 4 AB X 75 STL 2 4B 400022 0016 Screw Hex whrh 1 4 20 ROLOK ZN 2 5 490004 O Ring 2 6A 151925 0001 AC Power Supply 115 VAC 1 6B...
Страница 34: ...ICULAR PURPOSE Badger shall not be liable for any defects attributable to acts or omissions of others after shipment nor any consequential incidental or contingent damage whatsoever NUCLEAR DISCLAIMER...