background image

 

Helvar 435 BACnet Gateway: Installation Guide

 

3

 

From the configuration pages, you can do the following: 

 

Identify: 

o

 

Each Helvar router in a defined workgroup. 

o

 

The required Helvar router and DALI device 
parameters. 

o

 

Which BACnet Object type is assigned to each 
parameter. 

 

Simplify the configuration of the BACnet/IP 
communication requirements and allow for connected 
routers and devices to appear on the BACnet/IP BMS. 

1.2.1.  Front panel LEDs 

The LEDs on the unit indicate the general status of the BACnet Gateway, including power, ready 
and LAN communication activity. 

 

 Power LED 

This LED shows the current status of the power applied to the unit. 

‘On’ indicates that the 24 VDC power is supplied. ‘Off’ indicates that the power is not supplied 
or has failed. 

 

 Ready LED 

This LED shows the status of the boot-up 
process. 

‘On’ indicates that the required files have been 
loaded to the RAM disk and that the unit has 
successfully booted up. ‘Off’ indicates that the unit is not ready or has failed to boot up. 

 

 Ethernet Activity LED 

This LED shows the communication between the unit and the supervisory computer or 
controller connected via the Ethernet. 

‘On’ indicates incoming communications traffic. ‘Off’ indicates outgoing communications 
traffic. 

1.2.2.  Button and switches 

The BACnet Gateway is fitted with a recessed button for rebooting the unit, and with a bank of four 
DIP switches. The bank of DIP switches is not functional in this version. 

While the reset button does not erase any configuration, we recommend that you use it only if the 
software reboot fails. 

DIP switches 

(not used) 

Reset button 

Ethernet 

Activity LED 

Status 

LEDs 

Power LED 

Ready LED 

Содержание 435

Страница 1: ...BACnet Gateway 435 Installation Guide Doc No D007500 issue 1 2017 03 30...

Страница 2: ...he respective owners The publisher and the author make no claim to these trademarks While every precaution has been taken in the preparation of this document the publisher and the author assume no res...

Страница 3: ...2 1 2 1 Front panel LEDs 3 1 2 2 Button and switches 3 1 3 SYSTEM OVERVIEW 4 1 3 1 Helvar devices and DALI networks 5 1 3 2 BACnet IP network 5 2 HARDWARE GUIDE 6 3 INSTALLATION 8 3 1 INSTALLING THE U...

Страница 4: ...iv...

Страница 5: ...and air conditioning systems etc are measured separately for CO2 accountability Therefore installing the BACnet Gateway and combining the various systems can help an effective BeMS be more energy effi...

Страница 6: ...on regarding the electromagnetic compatibility refer to the Declaration of Conformity certificate available on request 1 1 Device limits and compatibility The 435 BACnet Gateway has the following limi...

Страница 7: ...er is not supplied or has failed Ready LED This LED shows the status of the boot up process On indicates that the required files have been loaded to the RAM disk and that the unit has successfully boo...

Страница 8: ...device points appear as a BACnet object types in a single BACnet device Select Helvar points to clarify between BACnet network Router 905 1 3 System overview The BACnet Gateway provides direct interf...

Страница 9: ...rs documentation See also the D5 Recommended Best Practices document for networking and system guidelines 1 3 2 BACnet IP network Specifically designed for building automation and control networks the...

Страница 10: ...sensitive Hardware Details Button Reset DIP switch Not applicable Indicators Power System Ready Ethernet LAN Activity Ethernet 1 10 100 Mb s port via RJ45 connector with 1 5 kV magnetic isolation Seri...

Страница 11: ...1000 Polybrominated biphenyls PBB 100 Packing materials cadmium lead mercury hexavalent chromium and its components 100 PPM 100 Dispose of the product and packaging according to WEEE Directive at an...

Страница 12: ...the unit using the DIN Rail kit 1 Fit the DIN Rail kit to the bracket on each side of the unit using the fixings supplied 2 Click the unit complete with the DIN Rail kit onto the DIN Rail mounted in t...

Страница 13: ...h requires a Category 5 RJ45 to RJ45 cable assembly When connecting to the Ethernet hub switch a straight through cable is used RJ45 MALE FROM RJ45 PIN NO SIGNAL COLOUR CODE EIA TIA 568B TO RJ45 PIN N...

Страница 14: ...10 Helvar Data is subject to change without notice RJ45 MALE FROM RJ45 PIN NO SIGNAL COLOUR CODE EIA TIA 568B TO RJ45 PIN NO 8 N A Brown 8 The image shows the flat side of RJ45 plug...

Страница 15: ...Helvar 435 BACnet Gateway Installation Guide 11 4 Order Codes ORDER CODES DESCRIPTION 435 BACnet Gateway AMR1 PSU 24 VDC 1 A power supply 435 AMR1 PSU Combined above 2 items sold as a pack...

Отзывы: