5:  WIRING

1:  Strip 0.2 to 0.25 inches  (5 to 7 mm) of wiring

      insulation.

2:  Connect the wires as indicated.

RELAY 1 NC
RELAY 1 C
RELAY 1 NO
RELAY 2 NC
RELAY 2 C
RELAY 2 NO
RELAY 3 NC
RELAY 3 C
RELAY 3 NO

10
11
12
13
14
15
16
17
18

Relay 1 Output

Relay 2 Output

Relay 3  Output

FUNCTION

PIN

LABEL

SHIELD WIRE WARNING:   Con-

nect the shield of the power 

wires to the earth ground of the 

central control system (e.g., 

chassis, ground bus bar, etc.).

NOTE:  For connections to an external controller 

such as a Bacharach MGS or GDA, refer to the 

manual that was included with the controller.

NOTE:  For 24 VDC installations, 

the input is protected. If the 

polarity is reversed, the instru-

ment will not power-up.

POLARITY WARNING:    For 24 VAC installations 

in a daisy-chain configuration, the neutral polari-

ty must be maintained for all instruments.

WARNING:  The MGS-550 must be 

powered by either (a) a suitable UL 

60950/CSA certified power supply 

that is isolated from line voltage by 

double insulation, or (b) an appro-

priately rated UL listed/CSA Class 2 

transformer.  Failure to comply can 

result in personal injury or death.

M20 OPENINGS:  The ABS and the 

flame proof/explosion proof enclosures 

provide four M20 openings for cable 

glands or plugs.  These openings can be 

used for field wiring, direct attachment 

of a sensor or wiring of a remote sensor.  

Unused openings must be closed with a 

suitable plug and gasket, maintaining 

the IP or Ex d rating.

114A Georges Street Lower 

Dun Laoghaire • Co Dublin • Ireland 

Phone: +353 1 284 6388 • Fax: +353 1 284 6389 

PIN 10

PIN 18

PIN 9

PIN 1

Connector Style

May Vary Slightly

from Photo

NOTE:  To make wiring connections, 

you must first open the MGS-550 

housing.  The enclosure lid of the 

IP66 ABS housing has four captive 

screws.  The enclosure lid of the Ex d 

(flame proof/explosion proof) hous-

ing unscrews.

Next, carefully discon-

nect the combination 

Display Bezel and 

Processor Board (which 

remain connected) 

from the lower Inter-

face Board by unscrew-

ing the 3 captive 

screws.  Access the 

captive screws through 

holes in the Display 

Bezel.

Internal 

Display Bezel

(Top Layer)

Processor

Board

(Middle Layer)

with Keyed

Ribbon Cable

Interface Board

(Bottom Layer)

NOTE:  After wiring is completed, carefully re-as-

semble the enclosure and its components, noting 

the keyed ribbon cable and sensor connectors.  

After installation is complete, be sure to refer to 

the User Manual  

(part number 1100-1000) for 

detailed instructions on registering the sensors and 

configuring the MGS-550 for proper operation.

PWR

GND

24VAC

PWR GND

24VAC

AC

 

PO

WER

PWR

GND

24VAC

PWR

GND

24VAC

PWR

GND

24VAC

PWR

GND

24VAC

PWR GND

24VAC

SUPPLY

TRANSFORMER

4-Wire Power and Output to

Central Control System

3-Wire Power and Output to

Central Control System

mA

A OUT 1
A1 GND

PWR GND
+24VDC

-

+

mA

A OUT 1

PWR GND
+24VDC

-

+

Refer to the 

User Manual (part number 1100-1000) 

for detailed instructions on accessing the internal 

components for wiring.

+24VDC/AC
PWR GND
ANALOG 1 GND
ANALOG OUT 1
ANALOG 2 GND
ANALOG OUT 2
RS-485 GND
A
B

1
2
3
4
5
6
7
8
9

Power
(+24VDC or 24VAC)

Analog Output 1

Analog Output 2

Modbus RTU

FUNCTION

PIN

LABEL