background image

HGM-MZ to N2 Communications Adapter 

Rev 1 (P/N 3015-5514) 

 

7.  Alarm Acknowledge Options 

Two alarm acknowledge options are supported.  DIP switch A1 on the adapter board selects which alarm 

acknowledge option is used. 

 

Auto Acknowledge   

(A1 On) 

 

Manual Acknowledge  

(A1 Off) 

 

In the Auto Acknowledge mode, the HGM-MZ will clear its alarm outputs the next time the alarmed zone is 

sampled and its PPM has dropped below the alarm thresholds.  No intervention from the Metasys network is 

necessary. 
In the Manual Acknowledge mode, the HGM-MZ will never clear its alarm outputs until the Metasys network 

connection has acknowledged the Change-of-State alarms reported to Metasys.  Once Metasys has 

acknowledged  the alarm messages, the HGM will clear its alarm outputs the next time the alarmed zone is 

sampled and its PPM has dropped below the alarm thresholds.  Please note that the Metasys acknowledgement 

is a field-level acknowledgement that takes place automatically (typically within a few seconds).  It is not a 

human operator acknowledging that the alarm was seen on a console.  The Metasys acknowledgement does, 

however, mean that the system has caught the alarm and that it will be reported to some higher level. 

8.  Setting up the Metasys Database 

The Metasys Point Map included with this document will provide the information needed to set up AI (analog 

input), BI (binary input), and ADI (internal integer) points in the Metasys database.  Additional comments are 

provided below to supplement the map.  The HGM-MZ can support up to 16 zones in groups of 4 zones, but a 

particular HGM-MZ  may not have all zones installed.  It is not necessary  to  include points in the Metasys 

database for zones that are not installed in the HGM-MZ. 
Each monitored zone in the HGM supports three levels of alarming:  Leak, Spill, Evacuate.  Since the Metasys 

N2 architecture does not support three different levels of high alarming per AI point, each HGM zone is set up 

as THREE AI points.  The first AI point for a zone supports a Leak Alarm, the second AI point for a zone 

supports a Spill Alarm, and the third AI point for a zone supports an Evacuate Alarm.  All three AI points for a 

zone return the same PPM reading, it’s the alarm thresholds that differ. 
Alarm thresholds in PPM are set through Metasys by setting each AI point’s “High Alarm Limit.”  Each alarm 

threshold may be set to a value of 1-65535 PPM.  Please note that for a particular zone, the Spill threshold must 

be set higher than the Leak threshold, and the Evacuate threshold must be set higher than the Spill threshold.  

All Metasys warning/alarm limits other than “High Alarm Limit” are ignored.  Because the HGM samples 

slowly, alarm “differential” to prevent alarm chattering is not needed.  Therefore the Metasys “Differential” 

parameter for each AI may be written but will be ignored. 
Certain HGM faults will cause various points to be marked unavailable/unreliable.  For example, a global flow 

fault will cause ALL AI PPM values to be marked unreliable, whereas a flow fault on a single zone will only 

cause the three AI PPM values associated with that zone to be marked unreliable.  Note that any time power is 

cycled to the HGM, it goes through a 15-minute warm-up cycle (even if it was already warm!).  During this 

time, all AI PPM values will be marked unreliable.  Don’t cycle HGM power needlessly if you would like to get 

valid PPM readings with the next 15 minutes! 
There are several ADI points which can provide useful information such as type of refrigerant programmed for 

each zone, number of zones actually installed in the HGM, the number of zones in alarm, HGM operating 

mode, etc. 

Содержание HGM-MZ

Страница 1: ...g through Metasys Leak Spill Evacuate Each alarm threshold can be set through Metasys The N2 Communications Adapter can be used in conjunction with the MZ RD Remote Display if desired Wiring details and operational limitations when using the MZ RD are discussed below CAUTION The adapter is powered from the 120 240V Universal Power Supply connection on the HGM main board 120 240V is present on the ...

Страница 2: ...L approved wire Wire polarity does not matter 3 If an MZ RD remote display is NOT used with the adapter refer to Figure 1 for wiring details In this case all wiring between the HGM MZ and the only external cable is the N2 communications cable 4 If an MZ RD remote display IS to be used with the adapter refer to Figure 2 for wiring details Note that when the MZ RD is used TWO RS 485 cables must be r...

Страница 3: ... the BAS BUS N terminal block screw Connect the N2 wire to the BAS BUS N terminal block screw Connect the N2 REF wire to the BAS BUS REF terminal block screw Shield connection practices vary Refer to Johnson Controls Metasys N2 documents for Johnson recommended practices Options are to hard terminate the shield to the case soft terminate through a small value capacitor the shield to the case or le...

Страница 4: ...ee Figure 3 for the location of adapter DIP switches A and B Switches 5 8 on the adapter s A DIP switch are used to match the node address set on the HGM s address DIP switch on the HGM main board Values from 0 15 are possible Refer to the table that follows Figure 3 HGM MZ to N2 Communications Adapter DIP Switches ...

Страница 5: ...he HGM MZ with MZ RD or Laptop PC The only HGM parameters that are changeable through Metasys are the alarm thresholds Configuring the HGM for refrigerant type and length of tubing for each zone zero length to disable a zone must be done with the MZ RD remote display or a laptop PC Refer to the appropriate Bacharach instructions for configuring these items HGM s are commonly custom configured at t...

Страница 6: ... 13 On On Off On 6 Off On On Off 14 On On On Off 7 Off On On On 15 On On On On 3 Take the value 0 15 from above and multiply that times 16 4 Subtract the result from the desired N2 address 5 This gives another number 0 15 Use this number and the table to set switches B5 B8 N2 Address Lower Half B5 B6 B7 B8 N2 Address Lower Half B5 B6 B7 B8 0 Off Off Off Off 8 On Off Off Off 1 Off Off Off On 9 On O...

Страница 7: ...n the HGM MZ Each monitored zone in the HGM supports three levels of alarming Leak Spill Evacuate Since the Metasys N2 architecture does not support three different levels of high alarming per AI point each HGM zone is set up as THREE AI points The first AI point for a zone supports a Leak Alarm the second AI point for a zone supports a Spill Alarm and the third AI point for a zone supports an Eva...

Страница 8: ...mm from Metasys N2 directed to ANY N2 slave not necessarily this one Under normal conditions you would expect to see a lot of activity on LED 4 since the N2 master is continually polling all N2 slaves on the line LED 3 will show activity based on how often the N2 master is polling the adapter versus other N2 slaves on the line If there are few N2 slaves on the line a lot of polls will be directed ...

Страница 9: ...ort try swapping the communications wires on the N and N terminal block screws The HGM port uses the same labels as the HGM main board so if you match the wires to the labels polarity should not be an issue there If the adapter seems to not be functioning correctly it can be restarted without restarting the HGM simply by pressing the CPU RST button just below the A DIP switch If you restart the ad...

Страница 10: ... 3015 5514 Headquarters 621 Hunt Valley Circle New Kensington PA 15068 7074 Toll Free 1 800 736 4666 Tel 1 724 334 5000 Fax 1 724 334 5001 Website www MyBacharach com E mail help MyBacharach com Printed in U S A Registered Trademark of Bacharach Inc ...

Отзывы: