background image

Fyrite

®

 Tech 50 & 60

Quick Start Guide 24-9429

Rev. 1 – September 2003

- 5 -

- 6 -

This Guide provides basic information about how 

to turn ON the analyzer and conduct a combustion 

efficiency test. Detailed information concerning 

the analyzer’s operation, set up, and calibration is 

contained in Instruction 24‑9428. 

Turning ON the Analyzer

1.  Place the probe tip in the area that contains 

the burner’s combustion‑air source. This 

step allows the analyzer to measure the 

combustion‑air temperature during the 

analyzer’s warm‑up period.

2.  Press analyzer’s 

I/O

 button. 

3.  Wait for the analyzer to complete its 

60 second warm‑up period. 

Performing a Combustion Test

4.  Press the

 

 or 

 

button to select the desired 

fuel and then press 

ENTER

. The fuel codes are:

 

F1 = Natural Gas 

F3 = LPG

 

F2 = Oil #2 

F4 = Kerosene

             

 

    

 

Example: “F1” denotes 

Natural Gas

Sampling Locations

Insert the probe in the areas shown in the 

following illustrations to measure stack 

temperature, flue‑gas O

2

 content, and flue‑gas CO 

content (Model 60 only).

Water Trap / Filter Maintenance

Drain the water condensate collected in the water 

trap after every test.

Replace the filter element (P/N 07‑1644) when dirty.

Atmospheric Burner or 

Gravity Vented Forced Air

Hot Water 

Tank

Atmospheric or 

Gravity Vented 

Boiler 

80% Eff. Fan Assist 

or Power Vented 

Furnace/Boiler

90% Eff. 

Condensing 

Furnace/Boiler

Bacharach, Inc.

621 Hunt Valley Circle, New Kensington, PA 15068

Ph: 724-334-5000 • Fax: 724-334-5001 • Toll Free: 800-736-4666 

Website: www.bacharach-inc.com • E-mail: [email protected]

Printed in U.S.A. 

® Registered Trademark

WATER TRAP

CHAMBER

Pull apart using a slight

twisting motion

FILTER

CHAMBER

FILTER ELEMENT

Pry apart filter chamber using

a small flat-blade screwdriver

inserted into notch

“A”

“B”

When reassembling

the trap, make sure

that surfaces “A” and

“B” are in contact 

Отзывы: