Air Conditioning & Refrigeration
Single Zone
Fixed Refrigerant Monitors
F E AT U R E S
• Small in size, big in value
• False alarms are virtually eliminated with the use of
infrared detection technology
• Capable of detecting 30 of the most commonly used
refrigerants and halon gases
• Three gas alarm levels can be individually set by
the user
• Logging feature enables 200 gas readings to be stored
at user-selectable time intervals
• Two year warranty
H G M S Z
The Bacharach
®
HGMSZ (Halogen Gas Monitor Single
Zone) is an infrared detector based unit designed for
continuous single-point monitoring of CFC, HFC, HCFC and
Halon refrigerant gases. The unit displays both the current
and peak gas levels. Gas alarms and fault conditions are
indicated by audible and visual alarms. The HGMSZ’s four
relay contacts enable external devices to be triggered
when gas alarms or fault conditions occur. A 4-20mA
output enables the unit to be integrated with remote
monitoring equipment or building management systems.
Measures:
R-11, R-12, R-21, R-22, R-23, R-113, R-114, R-123,
R-124, R-134a, R-227, R236FA, R-401a, R-402a,
R-402b, R-404a, R-407a, R-407c, R-408a, R-409a,
R-410a, R-500, R-502, R-503, R-507, R-508b, H-1211,
H-1301, H-2404, N-1230
Inputs:
Dedicated Single Zone
Output Signal:
3 SPDT, 5 Amp, 240 VAC rated alarm relays and 1SPDT,
5 Amp, 240 VAC rated system fault relay, plus a Digital
Display w/ a dedicated 4-20 mA analog output (floating
ground)
Detector Type:
Single Pass, Non-dispersive Infrared
Measuring Range:
All Gases, 0 to 10,000ppm
Sensitivity: 1ppm
Accuracy:
±10ppm from 0 to 100ppm, ±10% of reading from
100 to 10,000ppm
Front Panel Display:
Green LED indicates when unit is operating properly
Red LED indicates when any monitored point is above
any of its alarm settings
Yellow LED indicates a clogged sample line or other
system fault
Response Time:
9 to 30 seconds, depending on sample tube length
Max. Monitoring Distance: Up to 50 feet from measuring point to monitor
Power:
120 to 240 VAC, 50/60 Hz
Weight:
14” W x 18” L x 4.5” D, 7lbs. (35.6cm x 45.7cm x11.4cm/3.2Kg)
SPECIFICATIONS
HGMSZ
ORDERING INFORMATION
PART NO. DESCRIPTION
3015-4200
HGMSZ single zone monitor (includes
termination filter and 50ft. of 304-
2743 sample /exhaust / purge line
tubing)
304-2743
Sample / Exhaust / Purge line tubing
3015-3420 Termination
filter
3015-4121
120 VAC surge protector
3015-4122
220 VAC surge protector
3015-4123
4-20mA surge protector
3015-3069
120 VAC external visual alarm
3015-3070
120 VAC external audible alarm
3015-3076
120 VAC external audible / visual alarm