     This will prevent any possible mold build up.
4.  Check the operation of the condensate pump, and make sure the water
     misting fitting is acting properly, by allowing water to flow thru it. 
     Clean with vinegar if clogged and change the water filter.
5.  Check the electronic controller for any alarm conditions
6.  Check the refrigerant level and system operating pressures.
7.  Clean the water solenoid on a yearly basis, and change it out every two years. 

Warning: If the water solenoid sticks open, overflow can result.

Troubleshooting

Alarm conditions on the electronic controller, Call BCS Tech Services at 937-665-0424

Unit will not reach temperature  

Call your installation contractor to Determine proper refrigerant

 

 

 

 

 

charge.  Dirty condenser?

Unit has shut off    

 

Call BSC tech services or field Service; could be bad Compressor,

 

 

 

 

 

fans, controller or Pump

Alarm Signaling
Message 

 

 Cause    

 

 

Outputs

“P1”  

 

 

Thermostat probe failure    

compressor and heating outputs off

 

 

 

 

 

 

 

 

(on dehumidification system only)

“P3”  

 

 

Humidity probe failure  

 

humidity regulation off

“HA”  

 

 

High temp alarm    

 

outputs unchanged

“LA”  

 

 

Low temperature alarm  

 

outputs unchanged

“HHA”   

 

 High humidity alarm  

 

 

outputs unchanged

“HLA”    

 

Low humidity alarm  

 

 

outputs unchanged

In the instance of any of these alarms, call Bacchus Tech Services, or your local service contractor

Dimensional /Electrical
 

 

 

BCS1000  BCS1000  BCS1500  BCS1500  BCS2000  BCS3000

 

 

Cond. Unit  Evap. 

 

Con. Unit  Evaporator Con. Unit  Con. Unit 

Dims. 

  

17”D x 13.3”W      18”D x 29.25”W  19”D x 16.2”W 

18”D x 29.25”W 

19”D x 21’W 

25” D x 20”W

 

 

x 11.8”H 

 

x 6.5”H 

 

x 14”H 

 

x 6.5”H 

 

x 16.5”H 

 

x 16”H

Weight    

51 lbs.  

 

49 lbs.  

 

62 lbs.  

 

51 lbs.  

 

81 lbs.  

 

135 lbs.

Refrigerant 

3/8” suc.   

3/8”sw 

 

3/8” suc   

3/8” sw x  3/8” suc   

½

” suc

Connection 

1/4” dis.   

 

 

¼

” dis 

 

½

” sw 

 

5/16” dis   

3/8” dis

Water Supply 

 

 

¼

” 

 

 

 

¼

Connection 

 

 

compression 

 

 

compression

Condensate 

 

 

¼

 mpt 

 

 

 

¼

” mpt

Connection

7

Содержание BCS2000

Страница 1: ...yboard and master to slave control jumper 6 Condensing unit pad Condensing Unit Set Up 1 Place a suggested model on a firm level location pad for outdoor applications or add 4 anti vibration pads to each corner of the condensing unit for indoor use Place in an area with adequate air flow 2 Braze in suction and liquid lines to condensing unit 3 Bring 3 8 copper tubing from the liquid line of the co...

Страница 2: ... the back wall for adequate air distribution 2 Run the 1 4 drain line from the pump in the evaporator through the ceiling cap and out to a suitable location Heat tape any portion susceptible to freezing 3 Attach template to the ceiling Remove the stainless steel outer enclosure from the base of the unit Attempt to locate any mounting holes below ceiling joists for secure attachment with 8 wood scr...

Страница 3: ...th outlets hold each 14 6 jumper cable that is also color coded These run to each evaporator slave module inside of each stainless steel enclosure 6 Make sure that the unit is covered tightly with each cover Slave Control Module 7 From left to right The first two terminals should be connector to the 18 2 leads from port one in the master control module Terminals 3 4 5 one white lead 7 8 9 and 10 w...

Страница 4: ...of the green condensate pump in each evaporator 11 For indoor applications run 1 4 vinyl condensate drain tube from the evaporator to a suitable location 12 Do not replace cover until unit test is complete Controller Display Set Up 1 Install double gang box and cut out the blank plate to accept the Bacchus Temp Humidity Keyboard VH620 The keyboard can be mounted inside or outside of the room Run 1...

Страница 5: ...d and are not intertwined or crossed XH10P Humidity Sensor 8 The microprocessor has been preprogrammed for 55F and 50 RH To change either setting E Depress the up and down v keys together for more than three seconds to unlock the keyboard F Push the Temp or Humidity Set Key and immediately Release 18NB1 G Use the up and down v keys to change the value H Push the appropriate set key again and wait ...

Страница 6: ... pressure drop Take the difference between actual temperature and your reading from a PT chart to calculate 4 System Start up Before replacing stainless steel enclosure cover power up the system to make sure water solenoid is opening correctly The misting nozzle will be open Remove power and replace the cover Power up the evaporator and let the system pull down At temp set point the refrigerant so...

Страница 7: ...e could be bad Compressor fans controller or Pump Alarm Signaling Message Cause Outputs P1 Thermostat probe failure compressor and heating outputs off on dehumidification system only P3 Humidity probe failure humidity regulation off HA High temp alarm outputs unchanged LA Low temperature alarm outputs unchanged HHA High humidity alarm outputs unchanged HLA Low humidity alarm outputs unchanged In t...

Страница 8: ...tage 208 230 1v Electrical compressor rla 10A 11A 8A 12 1A compressor lra 53A 51A 43A 49A cond Unit MFS 20A 30A 15A 17 6A cond Unit mca 13 4A 13 4A 11 3A 12 1A BTU capacity 40F 4857 6250 10200 100 amb 12 185 suc 110 amb Phone 937 665 0424 Fax 937 890 6664 8 ...

Отзывы: