This will prevent any possible mold build up.
4. Check the operation of the condensate pump, and make sure the water
misting fitting is acting properly, by allowing water to flow thru it.
Clean with vinegar if clogged and change the water filter.
5. Check the electronic controller for any alarm conditions
6. Check the refrigerant level and system operating pressures.
7. Clean the water solenoid on a yearly basis, and change it out every two years.
Warning: If the water solenoid sticks open, overflow can result.
Troubleshooting
Alarm conditions on the electronic controller, Call BCS Tech Services at 937-665-0424
Unit will not reach temperature
Call your installation contractor to Determine proper refrigerant
charge. Dirty condenser?
Unit has shut off
Call BSC tech services or field Service; could be bad Compressor,
fans, controller or Pump
Alarm Signaling
Message
Cause
Outputs
“P1”
Thermostat probe failure
compressor and heating outputs off
(on dehumidification system only)
“P3”
Humidity probe failure
humidity regulation off
“HA”
High temp alarm
outputs unchanged
“LA”
Low temperature alarm
outputs unchanged
“HHA”
High humidity alarm
outputs unchanged
“HLA”
Low humidity alarm
outputs unchanged
In the instance of any of these alarms, call Bacchus Tech Services, or your local service contractor
Dimensional /Electrical
BCS1000 BCS1000 BCS1500 BCS1500 BCS2000 BCS3000
Cond. Unit Evap.
Con. Unit Evaporator Con. Unit Con. Unit
Dims.
17”D x 13.3”W 18”D x 29.25”W 19”D x 16.2”W
18”D x 29.25”W
19”D x 21’W
25” D x 20”W
x 11.8”H
x 6.5”H
x 14”H
x 6.5”H
x 16.5”H
x 16”H
Weight
51 lbs.
49 lbs.
62 lbs.
51 lbs.
81 lbs.
135 lbs.
Refrigerant
3/8” suc.
3/8”sw
3/8” suc
3/8” sw x 3/8” suc
½
” suc
Connection
1/4” dis.
¼
” dis
½
” sw
5/16” dis
3/8” dis
Water Supply
¼
”
¼
”
Connection
compression
compression
Condensate
¼
mpt
¼
” mpt
Connection
7