Controller Display Set Up 
 

 

1. Install double gang box and cut out the blank plate to accept the 

 

    Bacchus Temp/Humidity Keyboard (VH620). The keyboard can be 

 

    mounted inside or outside of the room. Run 18-2 stat wire from 

 

    the monitor back to the evaporator above the ceiling opening, and 

 

    attach to the yellow and green lead wires indicated. The keyboard 

 

    can be mounted up to 75 feet from the microprocessor inside the 

 

    evaporator. 

 
 

2. Mount the humidity sensor (XH10P) to a discreet side wall location 

 

    @ 6ft. from the floor. Bring the two lead wires from the sensor, 

 

    and attach to the + and 

– lead wires indicated. White lead to the 

 

    #2 terminal, and Red lead to the #1 terminal on the sensor. 

Do not 

 

    mount in the air discharge (coil side) of the evaporator. 

 

 

3. Mount the temp sensor adjacent to the humidity sensor, and run 

 

    the lead wires back to the wire harness. It is best to place both 

                sensors in a location where they cannot be touched by the end 
                user, and are not in the air discharge of the evaporator. 
 
 

4. Check supply voltage before connecting to the controller/power 

                board. 
 
 

5. Do not expose to water or moisture: use the controller only  

 

    Within the operating limits avoiding sudden temperature 

 

    changes with high atmospheric humidity to prevent formation 

 

    of condensation. 

 
 

6. 

Warning: disconnect all electrical connections before any kind  

 

    of maintenance 

 

 

7. Ensure that the wires for probes leads and the power supply are 

 

 

                separated and are not intertwined or crossed. 

 

 

           

XH10P  Humidity Sensor

 

 

 

 

8. The microprocessor has been preprogrammed for 55F° 

 

    and 50% RH. To change either setting: 

            

     

 

 

 

 

 

 

 

 

 

 

                 

 

             

 

 

 

 

          

           

E.  Depress the up ^ and down v keys together for more 

 

 

     than three seconds to unlock the keyboard 

 

 

 

 

 

        

 

 

 

F.  Push the Temp or Humidity Set Key and immediately 

 

  

 

 

     Release 

 

 

 

 

 

 

 

 

18NB1 

 

 

G. Use the up^ and down v keys to change the value 

 

 

 

 

 

 

H.  Push the appropriate set key again, and wait 10 

 

 

     seconds 

 

 

I.   Depress the up^ and down v keys to lock the keyboard. 

 
 

  9. There is no reason to change any besides temperature or humidity 

 

      set point depending upon the end users preference. 

 
 

10. 

IMPORTANT:

  In some instances, very tightly insulated rooms, or rooms with outside 

 

      humidity infiltration can have a call for dehumidification.  In that mode, refrigeration 

 

      turns on until humidity is decreased to set point.  If this occurs, reset humidity set point 

 

      up 5% higher than original set point.  A high of 70% RH is allowable. 

 
 

 

         

VH620 Keyboard 

 

 

                

 

Содержание BCS1000

Страница 1: ...dependent upon your condensing unit for outdoor condensing unit Check local codes 5 18 2 stat wire to be used to extend temperature sensor humidity sensor cable keyboard 6 Condensing unit pad Condensing Unit Set Up 1 Place a suggested model on a firm level location pad for outdoor applications or add 4 anti vibration pads to each corner of the condensing unit for indoor use Place in an area with a...

Страница 2: ...out to a suitable location Heat tape any portion susceptible to freezing 3 Attach template to the ceiling Remove the stainless steel outer enclosure from the base of the unit Attempt to locate any mounting holes below ceiling joists for secure attachment with 8 wood screws Use moly bolts for all other mounting locations Attach base securely to the ceiling diagram 1 Minimum 7 mounts 4 Bring in powe...

Страница 3: ...r supply Shut off water supply to the line and braze in the CPS water supply compression adapter Connect the water filter to the fitting and run copper from the filter thru the evaporator ceiling opening and cap and attach to the water solenoid inlet in each evaporator 8 Attach the 1 4 vinyl hose drain tube to the outlet of the green condensate pump 9 For indoor applications run 1 4 vinyl condensa...

Страница 4: ...xpose to water or moisture use the controller only Within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation 6 Warning disconnect all electrical connections before any kind of maintenance 7 Ensure that the wires for probes leads and the power supply are separated and are not intertwined or crossed XH10P Humidity Sensor 8 The...

Страница 5: ... temperature alarm outputs unchanged HHA High humidity alarm outputs unchanged HLA Low humidity alarm outputs unchanged In the instance of any of these alarms call Bacchus Tech Services or your installation contractor Power to the Evaporator 1 Bring in 14 2 conductor wire with ground to the evaporator and connect to the 14 2 with ground wire harness exiting the evaporator Make sure the line has ad...

Страница 6: ...nd replace the cover Power up the evaporator and let the system pull down At temp set point the refrigerant solenoid will close and the system will pump down and shut off the condensing unit 5 Check level of safety float Breakers We recommend a 30a fused disconnect Maintenance and Troubleshooting Have your system checked each year by a certified refrigeration technician He should 1 Clean the indoo...

Страница 7: ...nchanged In the instance of any of these alarms call Bacchus Tech Services or your local service contractor Dimensional Electrical BCS1000 BCS1000 BCS1500 BCS1500 BCS2000 BCS3000 Cond Unit Evap Con Unit Evaporator Con Unit Con Unit Dims 17 D x 13 3 W 18 D x 29 25 W 19 D x 16 2 W 18 D x 29 25 W 19 D x 21 W 25 D x 20 W x 11 8 H x 6 5 H x 14 H x 6 5 H x 16 5 H x 16 H Weight 51 lbs 49 lbs 62 lbs 51 lb...

Страница 8: ...8 Phone 937 665 0424 Fax 937 890 6664 ...

Отзывы: