![BAC VX Series Скачать руководство пользователя страница 14](http://html2.mh-extra.com/html/bac/vx-series/vx-series_operation-and-maintenance-manual_3053082014.webp)
8
W W W . B A L T I M O R E A I R C O I L . C O M . A U
M A R 1 1 3 - 0
Model Number
Operating Level (mm)
measured from the pan (bottom)
VXT-10 TO 135
327mm
VXI-S9, 18, 27, 36
343MM
VXC-S14 to S135
343mm
VXT-150 to 185
394mm
VXI-S50
419mm
VXC-S150 to S205
419mm
VXT-N215 to N535
432mm
VXI-S70, 95, 145, 190, 290
432mm
VXC-S221 to 265 & VXC-S288 to 1010
432mm
VXT-315 to 4800
457mm
VXI-S180, 360
457mm
VXC-S357 to 1360
457mm
VXC-S495 to 1608
356mm
VXI-S144, 215, 288, 430
356mm
Table 2 - Operating Water Level
The water level in the cold water sump will vary as a function of the
system load (evaporation rate), bleed rate, supply water pressure, and
the quantity of water suspended in the tower during pump operation
plus that contained in the water distribution system, external piping,
and any heat exchangers which could drain to the tower sump when
the circulating pump is shut down. Because the typical winter load is
less than the summer load, the winter evaporation rate is frequently
less than the summer evaporation rate. With this reduced evaporation
rate in the winter, the water level in the cold water sump will
increase unless the float is
readjusted.
Due to these variables the
operating water level should
be checked monthly and the
float adjusted as necessary
to maintain the desired
operating level. The valve
itself should be inspected
annually for leakage and
the valve seat replaced if
necessary.
Figure 1a - Operating Water Level