Access Door
The large access door is easily removed to provide complete access to
drift eliminators, spray system and fill.
To remove the door, take out the louvres from door side. Loosen and
remove the knobs that hold the door in place. Larger units are provided
with convenient anchor points to assist in removing the door and
securing the door to the unit when removed.
Figure 8.
Access Door Anchor Points
WARNING:
The access door
should not be removed without
first ensuring the fan and pump
motors have been isolated, tagged
and locked in the off position.
Louvres and Eliminators
Inspect regularly and remove foreign objects that might impair air
passage. Replace damaged and/or missing sections as necessary.
WARNING:
Damaged or missing
drift eliminators will result in
excessive drift from the tower.
This may constitute a hazard
due to biological or chemical
contaminants, including
Legionella, being discharged from
the tower. When such damaged
or missing drift eliminators
are noticed the tower MUST be
stopped and not re-started until
the sections are replaced.