SPECIAL CALIBRATION NOTES: 

For some products, the LS6000 can be calibrated with product touching the probe.  To do this, turn the 
sensitivity adjust pot CW until the red LED just comes on and continue CW for 1/8 to ¼ of a turn.  Always 
check to see if the unit resets in the absence of product. 
 

INTERFACE CALIBRATION 

For applications such as an oily water interface, the unit should be calibrated in the less electrically 
conductive fluid (oil) and the unit will then “ignore” the oil, but sense the water. 
 

5. MAINTENANCE AND TROUBLESHOOTING 

No routine maintenance is required other than keeping the interior of the unit clean and free of dirt, dust and other 
contaminants. 
The LS6000 consists of three main sub-assemblies.  These are the enclosure, the antenna probe and the electronics.  
The following troubleshooting guide will assist in determining how to correct most of the problems which may 
occur in sections 3 and 4. 

 

PROBLEM POSSIBLE 

CAUSE 

SOLUTION 

RED LED cannot be adjusted to 
turn on. 

Antenna lead not connected 
No power to unit. 
Bad electronic card. 

Plug antenna lead into probe. 
Check for correct power to unit. 
Repair or replace card. 

RED LED remains on at all times 

Antenna probe is shorted to case 
or ground. 
 
 
 
 
 
 
 
Bad sensing card. 

Unplug banana plug and position 
it so that the bare end is not 
touching anything.  Turn 
calibration pot 20 turns CCW.  
LED should go out.  If it does, 
repair, replace or clean antenna 
probe.  If LED does not go out, 
replace electronics. 
 
Repair or replace card. 

Unit triggers when material 
touches probe, but will not reset 
when material recedes from probe 
or unit and gives false alarm. 

Improper mount of probe. 
Improper calibration procedure. 
Excessive material build-up on 
probe. 
 
Probe is mounted in flow of 
material. 

Contact factory or dist. 
See section 4B. 
Perform “dirty probe calibration”: 
Recalibrate with built up material 
on probe.  See section 4B. 
Revise mounting. 

Unit will not detect material. 

Improper calibration. 
 
Antenna lead not plugged into 
probe. 
Unit was calibrated with material 
touching probe. 

See calibration instructions, 
section 4. 
Plug antenna lead into probe. 
 
Be sure material is not touching 
probe and recalibrate. 

Unit will not stay in calibration. 

Poor grounding of unit to vessel. 

Provide secure ground connection. 

Relay operates properly, but no 
signal at terminals. 

Burned or broken lands on the 
printed circuit board. 
 
 
 
Bad relay contacts. 

Turn off power.  Remove module 
from housing and inspect lands on 
printed circuit  for damage.  
Replace if necessary. 
 
Replace relay or return  for repair. 

PLEASE CONTACT THE FACTORY OR YOUR DISTRIBUTOR IF YOU HAVE ANY 
QUESTIONS OR NEED ASSISTANCE

 

 
 

Содержание LS6000

Страница 1: ...H O OW WN NE ER RS S M MA AN NU UA AL L I IN NS ST TA AL LL LA AT TI IO ON N C CA AL LI IB BR RA AT TI IO ON N T TR RO OU UB BL LE ES SH HO OO OT TI IN NG G W WA AR RR RA AN NT TY Y BABBITT INTERNATIO...

Страница 2: ...tion 2 3 Installation 2 A Inspection and Operation Check 2 B Physical Installation 2 C Removing Electronics 3 D Typical Applications and Wiring Diagrams 3 1 LS6000 Terminal Layout 3 2 Ladder Diagrams...

Страница 3: ...able high or low level RF Frequency Approximately 1 3 MHz Environmental Hazardous Area Class I Group D Class II Group E F G Temperature Probe 30 F to 250 F Electronics 40 F to 185 F Pressure Probe 150...

Страница 4: ...ting or welding in the coupling for the LS6000 a Tag and lock out the electrical power to the equipment that services the vessels b Check liquid or dry powders that create a gas in the vessel for oxyg...

Страница 5: ...nics 1 Disconnect supply power at main power source 2 Disconnect wires from terminal strip 3 Unplug blue antenna lead 4 Remove green grounding screw D Typical Applications and Wiring Diagrams As follo...

Страница 6: ...4...

Страница 7: ...FAIL SAFE INSTRUCTIONS SEC 4A FIGURE 6 4 5 TYPICAL WIRING APPLICATION L1 115 VAC L2 AUTOMATIC FILLING OF TANK WHEN LEVEL FALLS TO POINT A A PUMP COMES ON TO FILL TO A POINT B THEN TURNS OFF L1 LS6000...

Страница 8: ...cumstances Please call your distributor or the factory if you need assistance B Sensitivity Calibration The LS6000 should be calibrated when no material is touching the probe and when the unit is inst...

Страница 9: ...und Bad sensing card Unplug banana plug and position it so that the bare end is not touching anything Turn calibration pot 20 turns CCW LED should go out If it does repair replace or clean antenna pro...

Страница 10: ...ditions or components which have been misused abused damaged by neglect or accident This warranty shall not apply to any components which have been altered or repaired without the prior written consen...

Отзывы: