7. Consultation menu
1) Check that the mounting position of the thermal energy meter and all electrical wiring are carried
out correctly
2) Check if the device is configured, otherwise set the installation version and the unit of measurement
3) Check at level 3 that all configured parameters are correct (heating and cooling data)
4) Check that the thermal energy meter, pulse devices, probes etc. are installed correctly (refer to the
specific installation manuals for each product)
5) Start the heating/cooling system:
→ Check the consistency of the reported values (energy and volume)
→ Check in level 2 the instant data
6) Check for errors
7) Apply installation seals. It’s recommended to lock the device with a password set through the
BMETERING NFC Config android app (downloadable from the Google Play Store).
PROCEDURE FOR COMMISSIONING
The consultation menu is divided into 9 levels by a numerical index always visible at the top left of the
display. By pressing the T1 button you can choose the desired level, while pressing the T2 button you
can view the sublevels of the preset level. After 60 seconds without iteration the display turns off. If no
button is pressed within 20 seconds (with the display off) the display cycle will start again from level 1.
If a button is pressed within 20 seconds (with the display off) the last level consulted will be displayed.
In any level or sublevel, holding down the T1 button for 3 seconds will direct the index to level 1. To
access to a sublevels, where present (indicate by the symbol ‘–‘), it is necessary to hold down the T2
button for 3 seconds. To return to a main level from a sublevel it’s necessary to hold down the T2 button
again for 3 seconds. Each level consists of a brief indication in letters of the data that will be shown after
a few seconds in a second screen.
1
INDEX
INF
UM
1.01
HEAT
J,MJ,GJ,kWh,MWh
1.02
COOL
J,MJ,GJ,kWh,MWh
1.03
HEAT
m³
1.04
COOL
m³
1.05
ABSOLUTE
m³
1.06
FORWARD
m³
1.07
REVERSE
m³
1.08
IN 1
m³
1.09
IN 2
m³
1.10
LOST
m³
2
INDEX
INF
UM
2.01
POWER H
kW
2.02
POWER S
W
2.03
HEAT
J, Wh
2.04
FLOW
m³/h
2.05
TEMP. SUPPLY
°C
2.06
TEMP. RETURN
°C
2.07
TEMP.DIFFERENCE
°C
2.08
TEMP. AMBIENT.
°C