B.E.G. LUXOMAT PD4-M-2C-DS Скачать руководство пользователя страница 3

Activation of light for 12 h via mains interruption

1. Interrupt current of both supply lines 

2. Apply current for 2 to 5 sec.  

3. Interrupt current again 

4. Apply current 

5. Detector is now ON for 12 h

Exiting sabotage

1. Interrupt current of both supply lines 

2. Apply current for 30 to 60 sec.  

3. Interrupt current again 

4. Apply current 

5. Detector is in simple closed state

15.  Other functions

16.   Fully automatic and semi automatic mode 

(see functions IR-PD-1C)

 

Fully automatic operation

In this operating mode, the lighting switches automatically 

on and off for increased comfort, depending on presence 

and brightness.

- Channel 1 switches on in the event of motion if “dark“ is 

detected.

Semi automatic operation

In this operating condition, in order to gain increased  

savings, the lighting is energized only after being  

manually switched on.

Switch-off takes place automatically or manually.

The semi automatic mode basically behaves like the fully 

automatic one. However, the difference is that switching-on 

must always be carried out manually!

As many (closer-contact) buttons as desired can be wired 

in parallel on the “S” button input (ON/OFF).

Triggering in semi automatic mode: 

If the detector switches 

off in semi automatic mode (lag timer elapsed), the detec-

tor is switched on again within 10 sec. by motion (despite 

semi automatic mode).

HA

ON/OFF

In case the sensing area of the 

LUXOMAT

®

 PD4-M-2C-DS 

is too large or areas are being covered that should not be 

monitored, the range can be reduced or limited through use of 

the enclosed masking clips.

18. Exclude sources of interferences

Type

FC

PD4-M-2C-DS (Master and Slave)

92760

LUXOMAT

®

 

Remote control

:

IR-PD-1C (incl. wall bracket) 

 92520

Accessory:

BSK Ball basket guard 92199

Wall bracket for remote control as  

replacement  

92100

19. Article / Part nr. / Accessory

Sensor and power supply in one case

Power supply:

 230 V~ ±10 %

Buffering period of tension: 

200 ms

Power consumption:

 < 1W

Ambient temperature:

 -25°C to +50 °C

Degree of protection/class:

 IP20 / II 

BUS and pushbutton connections:

 screened cable: 0.28 mm

2

maximum cord length: 30 m

Settings:  

Potentiometer, DIP-switch and by remote control

Light values:

  20-1000 Lux by remote control 

10-2000 Lux by potentiometer

Extension of the detection area:

 with max. one device in slave-

configuration

Area of coverage:

 circular 360°

Range of coverage Ø H 2,50 m / T = 18°C:

 

 

seated 6,40 m / tangential 24 m / radial 8 m

Recommended height for mounting:

 2 - 3 m

Light measurement:

 da artificial light

• Power switch for light (both circuits)

Type of contact

: NOC/with pretravel tungsten contact

Contact load:

 2300 W cos

ϕ

=1 /  

                    1150 VA cos

ϕ

= 0.5, µ-Contact

Time-settings:

  

15 sec. - 60 min./ test with potentiometer 

5 min. - 30 min./ test with remote control

Dimension: 

PD4-M-2C-DS-DE       H 100 x Ø 117 mm 

Visible portion when built into ceiling FC:

  H 37 x Ø 117mm

 

Declaration of Conformity: 

The product complies with 

the low voltage recommendation 2006/95/EC and the EMV 

recommendation 2004/108/EC.

20. Technical data PD4-M-2C-DS

17. Range of Coverage

walking towards
walking across

 

seated

1
2
3

24 m

8 m

6,40 m

24 m

360°

2,50 m

2

3

1

21. Wiring diagram

Standard mode with master (2 alternating current circuits) and 

pushbutton as well as one device in slave-configuration

 

Optional 

PB1/2 = optional sensing device;

Slave = PD4-M-2C-DS in slave configuration

PD4-M-2C-DS

L1
N1

L2
N2

PE

N2 L2 L2‘

L1‘ L1 N1

+

PB PB

Master

N2 L2 L2‘

L1‘ L1 N1

+

PB PB

Slave

PE

!

!

!

!

PE

PB1

PB2

230 V~

230 V~

The PD4-M-2C-DS has a common optical system for both out-

puts. The device gets its operating voltage from both phases. 

If L2 fails, the device is operated with L1 and vice versa. L1‘ 

‚closes only if L1 is connected and L2´ ‚ closes only if L2 is 

connected.

22. Operation manual