Installation and Operating Instruction for 

B.E.G.

 – Occupancy detector PD4-M-2C-DS-FC

LUXOMAT

®

PD4-M-2C-DS

 2. Safety note

 

Work on the 230 V mains supply may only 

be carried out by qualified professionals or 

by instructed persons under the direction 

and supervision of qualified skilled electrical 

personnel in accordance with electrotechnical 

regulations.

Disconnect supply before installing! 

The device is not suited for safe disconnection 

of the mains supply. 

 

Attention:

Both the switch push buttons and the (-) - and 

(+) - clamps must not be connected to the 

supply voltage!

 

The pushbutton is supplied 

directly from the device.

GB

3. Installation of the PD4-M-2C-DS

5.  Hardware configuration  

Position Potentiometer and DIP-switch

The DIP switch settings are overriden using the remote 

control. 
 

6. DIP switch functions

DIP-

switch

ON

OFF

1

Semi automatic mode

Fully automatic mode

2

Slave

Master

3

Corridor mode

 Standard mode

DIP

OFF

ON

1

2

3

Corridor function:

 After deactivation by an external push button, the 

detector switches off and returns to automatic mode after 5 sec.

 

The DIP settings are enabled again by:
• Adjusting the DIP switches when closed
• Reset with test sun setting at the potentiometers
• Reset when open

Semi automatic mode/Fully automatic mode:

 see pt. 16

A circular opening of diameter 

100 mm must first of all be 

produced in the ceiling. 
 

Having connected up the ca-

bles in accordance with regula-

tions, the detector is inserted 

into the opening as shown in 

the drawing opposite and fixed 

into position with the assistance 

of the spring clip.
When in Master/Slave mode 

of operation, the Master-appli-

ance must always be installed 

at the location where there is 

least daylight.

80 - 90 mm

100 mm

DIP

321

1

2

Potentiometer 1 Lux

Potentiometer 2 Time

1  LED red 

2  LED green 

3  LED white

4.  

Hardware configuration

 

Position LED’s

3
2
1

DIP1 VA/HA

DIP2 Master/Slave

DIP3 Corridor mode/standard mode

ON

OFF

DIP

S     L     L         

R

Rel2

N

Rel1

230 VAC ±10%

50-60 Hz

3 2

1

Slave function

When using the detector as slave device it sends a data 

telegram to the master device upon each detection of mo-

tion, disregarding ambient luminosity.

7. Putting into operation / Settings

 

Self test cycle 

After an initial 60-second self-test cycle, the 

LUXOMAT

®

 

PD4-M-2C-DS is ready for operation.  

 Potentiometer 1 - Adjustment follow-up time 

“Light“  

Symbol 

TEST

: Test mode, reacts on motion 

only. Every movement switches on the light 

for a period of 2 seconds, switching it off for 

a period of 2 seconds. The time can be set 

infinitely variably at between 15 sec. and 60 

minutes.

Potentiometer 2 - Adjustment twilight-switch

The switch-on value for the light can be set 

at between 10 and 2000 Lux. Using the 

potentiometer, the luminance set points can be 

set as desired.
Symbol

 

Night operation

Symbol  :  

Day/Night operation

Determining the current brightness

 

Set potentiometer 1 to the “Test“ setting. The 

green LED lights up permanently as soon as the 

value set at the potentiometer 2 exceeds the 

current measured brightness. 

The potentiometer settings are valid for both switching chan-

nels. They are overriden using the remote control.

9.  Putting into operation of the remote 

control IR-PD-1C (optional)

Check Battery:

 

Open battery compartment by pressing the 

plastic springs together and removing the 

battery-holder.

 

Caution:

 Settings with remote control supersede the 

settings by potentiometers.   

1

2

8. Reset and default settings

1. Default settings 

If the potentiometers are in the 

“Test“ and “Sun“ position and 

the detector is unprogrammed, 

the factory program is acti-

vated: 500 lux and 10 min.

2. Reset 

 

If both potentiometers are returned to the “Test“ and “Sun“ 

setting from any other position, a reset is executed. All values 

programmed with the remote control are deleted.

Option: Remote control IR-PD-1C  

Wall bracket for remote control IR-PD-1C 

LUXOMAT

®  

 

PD3

B.E.G.

500

200

400

100

20

IR-PD-1C

PIR

CdS

ON/OFF

HA

B.E.G.

LUXOMAT

®

B.E.G.

LUXOMAT

®

By means of this remote control all settings of 

the presence detector can be made comfort-

ably from the ground. A useful wall bracket is 

included in delivery.

 1. Product information 

 

For an increased reliability of the 

illumination system the PD4-M-

2C-DS can be connected to two 

seperate ciruits of the alternating 

current network.

Thus, the illumination system can 

be divided into two electrically 

isolated groups, thereby reducing 

the risk of total failure of the il-

lumination system importantly.

The convenience of a shared 

pushbutton for both groups is 

preserved based on the fact that 

the pushbutton is also electrically 

isolated. 

!

!

!

!

LUX        

LUX        

             R1          

15s

30s

15

20

TE

             R1          

15s

30s

15

20

TE