Installation and Operating Instruction for
B.E.G.
– Occupancy detector PD4-M-2C-DS-FC
LUXOMAT
®
PD4-M-2C-DS
2. Safety note
Work on the 230 V mains supply may only
be carried out by qualified professionals or
by instructed persons under the direction
and supervision of qualified skilled electrical
personnel in accordance with electrotechnical
regulations.
Disconnect supply before installing!
The device is not suited for safe disconnection
of the mains supply.
Attention:
Both the switch push buttons and the (-) - and
(+) - clamps must not be connected to the
supply voltage!
The pushbutton is supplied
directly from the device.
GB
3. Installation of the PD4-M-2C-DS
5. Hardware configuration
Position Potentiometer and DIP-switch
The DIP switch settings are overriden using the remote
control.
6. DIP switch functions
DIP-
switch
ON
OFF
1
Semi automatic mode
Fully automatic mode
2
Slave
Master
3
Corridor mode
Standard mode
DIP
OFF
ON
1
2
3
Corridor function:
After deactivation by an external push button, the
detector switches off and returns to automatic mode after 5 sec.
The DIP settings are enabled again by:
• Adjusting the DIP switches when closed
• Reset with test sun setting at the potentiometers
• Reset when open
Semi automatic mode/Fully automatic mode:
see pt. 16
A circular opening of diameter
100 mm must first of all be
produced in the ceiling.
Having connected up the ca-
bles in accordance with regula-
tions, the detector is inserted
into the opening as shown in
the drawing opposite and fixed
into position with the assistance
of the spring clip.
When in Master/Slave mode
of operation, the Master-appli-
ance must always be installed
at the location where there is
least daylight.
80 - 90 mm
100 mm
DIP
321
1
2
Potentiometer 1 Lux
Potentiometer 2 Time
1 LED red
2 LED green
3 LED white
4.
Hardware configuration
Position LED’s
3
2
1
DIP1 VA/HA
DIP2 Master/Slave
DIP3 Corridor mode/standard mode
ON
OFF
DIP
S L L
R
Rel2
N
Rel1
230 VAC ±10%
50-60 Hz
3 2
1
Slave function
When using the detector as slave device it sends a data
telegram to the master device upon each detection of mo-
tion, disregarding ambient luminosity.
7. Putting into operation / Settings
Self test cycle
After an initial 60-second self-test cycle, the
LUXOMAT
®
PD4-M-2C-DS is ready for operation.
Potentiometer 1 - Adjustment follow-up time
“Light“
Symbol
TEST
: Test mode, reacts on motion
only. Every movement switches on the light
for a period of 2 seconds, switching it off for
a period of 2 seconds. The time can be set
infinitely variably at between 15 sec. and 60
minutes.
Potentiometer 2 - Adjustment twilight-switch
The switch-on value for the light can be set
at between 10 and 2000 Lux. Using the
potentiometer, the luminance set points can be
set as desired.
Symbol
:
Night operation
Symbol :
Day/Night operation
Determining the current brightness
Set potentiometer 1 to the “Test“ setting. The
green LED lights up permanently as soon as the
value set at the potentiometer 2 exceeds the
current measured brightness.
The potentiometer settings are valid for both switching chan-
nels. They are overriden using the remote control.
9. Putting into operation of the remote
control IR-PD-1C (optional)
Check Battery:
Open battery compartment by pressing the
plastic springs together and removing the
battery-holder.
Caution:
Settings with remote control supersede the
settings by potentiometers.
1
2
8. Reset and default settings
1. Default settings
If the potentiometers are in the
“Test“ and “Sun“ position and
the detector is unprogrammed,
the factory program is acti-
vated: 500 lux and 10 min.
2. Reset
If both potentiometers are returned to the “Test“ and “Sun“
setting from any other position, a reset is executed. All values
programmed with the remote control are deleted.
Option: Remote control IR-PD-1C
Wall bracket for remote control IR-PD-1C
LUXOMAT
®
PD3
B.E.G.
500
200
400
100
20
IR-PD-1C
PIR
CdS
ON/OFF
HA
B.E.G.
LUXOMAT
®
B.E.G.
LUXOMAT
®
By means of this remote control all settings of
the presence detector can be made comfort-
ably from the ground. A useful wall bracket is
included in delivery.
1. Product information
For an increased reliability of the
illumination system the PD4-M-
2C-DS can be connected to two
seperate ciruits of the alternating
current network.
Thus, the illumination system can
be divided into two electrically
isolated groups, thereby reducing
the risk of total failure of the il-
lumination system importantly.
The convenience of a shared
pushbutton for both groups is
preserved based on the fact that
the pushbutton is also electrically
isolated.
!
!
!
!
LUX
LUX
R1
15s
30s
15
20
TE
R1
15s
30s
15
20
TE