Sensorandpowersupplyinonecaseforonwall-,ceiling-

andflushmounting

Power supply:

230 V~+6 %/-10 %

Power consumption:

<1 W

Ambient temperature:

-25°C–+40°C

Degree of protection/class:

 

SMIP20,withaccessoryIP54,FCandFMIP20with

accessoryIP23/II

Settings:  

locallyandbyremotecontrol

Light values - IR-PDim:

50-1500Lux

Parallel operation:

Master/Slave

Area of coverage:

circular360°

Range of coverage Ø H 2.5 m / T=18°C:

seated5 m/tangential10 m/radial6 m

Recommended height for mounting:

2-3 m

Light measurement:

Mixedlight,dartificiallight

Lux values - Potentiometer:

10-2000Lux

• Relay/Channel 1 for light-connection

Type of contact

:NOC/withpretraveltungstencontact

Contact load:

2300 W,230 V~,10 Acos (

ϕ)

=1/

1150 VAcos (

ϕ)

= 0.5

Max. no. of series-connected electronic ballasts:

dependingontypeandmake,totalconnectable140 µF.

DIM-Output:

1x(1-10 V)

Max. no. of series-connected electronic ballasts: 

max.50electronicballastsbyonesinglesupplywith

max.100 mcablerunandaconducturcross-sectionof

0.75 mm²

Time-settings:

1-30min./test

Dimensions HxØ [mm]

SM

FC

FM

PD2-M-DIM

50 x 98

66 x 79 70 x 98

Visible portion when built into ceiling:

34 x 79 mm

Technical data PD2-Slave

Electricaldatasameasabove,butjustonechannelfor

signalingmotiondetection.

Declaration of Conformity: 

Theproductcomplieswith

thelowvoltagerecommendation2006/95/ECandthe

EMVrecommendation2004/108/EC.

13. Technical data PD2-M-DIM

10. Wiring diagrams

11. PD2-DIM - Connections

Type

SM

FC

FM

PD2-DIM (Master)

92153

92167

92157

PD2-S (Slave)

92152

92166

92156

LUXOMAT

®

 Remote control:

IR-PDim(incl.wallbracket)

92200

Accessory:

BSKBallbasketguard 

92199

Wallbracketforremotecontrolasreplacement 92100

Occupancydetectors-CoveringIP23

92206

SocketIP54

92161

12. Article / Part-Nr. / Accessory

MAN

5

56

2

01_0

9/200

8

IncasethesensingareaoftheLUXOMAT

®

PD2-DIM

istoolargeorareasarebeingcoveredthatshould

notbemonitored,therangecanbereducedorlimi-

tedthroughuseoftheenclosedmaskingclips(e).

9. Exclude sources of interference

8. Range of Coverage

6.  Manual Dimming - Preset / User 

(for IR-PDim functions see page 1)

Youcandimmanuallybypressingthepushbutton

foralongtime(>2sec).Whenthebuttonisreleased,

thecurrentdimmingvalueisretained.Uponrenewed

dimming,thedimmingdirectionisreversed.

PRESET

theluminancesetpointissetduringstart-up

operationbytheinstallerandremainsunchanged.

The luminance set- point configured through manual 

dimmingisonlyappliedforthetimebeing.

Caution:

Theconstantlightregulationisnowdeactivated!

The currently set artificial light is retained independent 

oftheambient/daylightbrightness!

Afterswitchingoffandthenbackon,theoriginallyset

luminanceset-pointisreset=constantlightregulation

isactivated.

USER

- can only be activated via the remote control!

Theluminanceset-pointischangeduponeachmanual

dimmingandre-adjustedbytheuser(Conformation

throughrelayclicking!)

Theconstantlightregulationremainsactivated!

5.Fully / Semiautomaticmode

(for IR-PDim functions see page 1)

Fully automatic operation

Inthisoperatingmode,thelightingswitchesautomati-

callyonandoffforincreasedcomfort,dependingon

presenceandbrightness.

Semiautomatic operation

(Semiautomatic can only be activated via the remote 

control!)

Inthisoperatingcondition,inordertogainincreased

savings,thelightingisenergizedonlyafterbeingmanu-

allyswitchedon.Switch-offtakesplaceautomatically.

Thesemiautomaticmodebasicallybehaveslikethefully

automaticone.However,thedifferenceisthatswitching-

onmustalwaysbecarriedoutmanually!

Asmany(closer-contact)buttonsasdesiredcanbewired

inparallelonthe“S”buttoninput(ON/OFFDimm).

7. Manual Switching 

Youcanswitchthelightingonandoffmanuallyby

pressingthepushbuttonforashorttime.Itwillstayonor

off as long as people are detected plus the configured 

followuptime.

Push button operation

 For manual switching 

push the button only a short time (0.2 - 0.5 sec.)! 

To dim push the button until the wished light level is 

arrived.

Master-/ slave-operation. The master is the only one 

to read the light level and to switch the connected 

loads. Independant of the light level the slave units 

react to movements only by sending impulsions via 

the dry contact.

 

No load can be connected to the dry 

contact. The master-dim-occupancy detec-

tors can not be switched into parallel. For 

that application please prefer the master- / 

slave-installation. It is recommended to put 

the master the furthest possible postion 

away from the natural light source.

14. LED-functional indicators, fault-finding

ThefunctionalindicatorsinthecaseoftheLUXOMAT

®

PD2-DIM-MASTER(redandgreenLED‘s)

Red LED indicating self-checking mode (over a period 

of 60 seconds following mains‘-supply lock-on)

Flashing at intervals of 1 second

EEPROM/memoryempty

Flashing rapidly

EEPROM/memorycontainsinformation

Red LED as an indicator of status

Flashing irregularly

Movementsaredetectedwithintheareaofcoverage

Flashing regularly

Detectoridentifiesbright,lightoff

(dependentuponoperatingmode)

Not illuminated

Detectoridentifiesdark,lighton

(dependentuponoperatingmode)

Flashing extremely rapidly

Toobright/Toodark/Undefined

Red LED as an acknowledgement of receipt for  

commands from the remote control 

Illuminated for 2 seconds

Signalvalidlyreceived

Illuminated for 0.5 seconds

Not-acceptedcommand,detectorblocked

Flashing extremely rapidly

Not-acceptedcommand,occurs,forexample,when

anattemptismadetoinputtwilight-valuearetoo

brightortoodark

Green LED as an acknowledgement of receipt for  

commands from the remote control

Lights up for 3 seconds

Semiautomaticorusersignalcorrectlyreceived

Green LED as an indicator of status (only for status 

“Permanent protection against sabotage”

)

Flashing irregularly

Movementaredetectedwithintheareaofcoverage

Flashing regularly

Detectoridentifiesbright,lightoff

(dependentuponoperatingmode)

Not illuminated

Detectoridentifiesdark,lighton

(dependentuponoperatingmode)

lluminated for 2 seconds 

Signalvalidlyreceived

(dependentuponoperatingmode)

W

ARRANTY

YEARS

3

  

             

1-10

VDC

Terminal connection for push button operation

MASTER

  

+

             

R  L'  N  L  S

  

  

             

1-10 VDC

Terminal connection for master-/ slave-operation

MASTER

SLAVE

  

             

R  R  N  N  L  L

L'  N  L  S  +  -

1

2

quer zum Melder gehen 
frontal zum Melder gehen
Unterkriechschutz

walking across
walking towards
seated

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

Connections PD2-DIM-SM

10 m

6 m

5 m

10 m

360°

Mounting height

2.5 m

1

+

N

R

+

L

S

SLAVE

L'

1-10 V

Connections PD2-DIM-FC/FM

+

N

R

+

L S

SLAVE

L'

1-10 V