Sensor and power supply in one case for onwall-, ceiling- and

flushmounting

Power supply:

  

230 V~ 

±

10 %

Power consumption:

  

< 1W

Ambient temperature:

  

-25°C to +50°C

Degree of protection/class:

   FC IP20 / II

Settings:  

 

locally and by remote control

Light values remote control:

   50 - 1500 Lux

Extension of the detection area:

 with Slaves

Area of coverage:

  

circular 360°

Range of coverage Ø H 2,50 m / T = 18°C:

  

 

 

seated 6,40m / tangential 24 m /   

 

radial 8 m

Recommended height for mounting:

 2 - 3 m

Light measurement:

  

 Mixed light, da artificial light 

Lux values potentiometers:

   10 - 2000 Lux

• Channel 1 for light-connection

Type of contact:

  

NOC/with pretravel tungsten  

 

 contact

Contact load:

  

 2300 W cos

ϕ

=1 /  

1150 VA cos

ϕ

= 0,5, µ-Contact 

DIM-Outputs:

  

1 x (1-10 V) 

Max. no. of series-connected electronic ballasts: 

max. 50 electronic 

ballasts by one single supply with max. 100 m cable run and a 

conductor cross-section of 0.75 mm²

Time-settings:

  

1 - 30 Min. / Test

•  

Channel 2 for control devices (only reacts on motion)

Contact load:

  

 230 V~, 3 A cos

ϕ

=1, µ-Contact

Time-settings:

  

 5 min. - 120 min. with time delay of 

5 min. for follow-up time > 15 min./ 

Alarm impulse

Dimensions H x Ø [mm]

  103 x 98

Visible portion when built into ceiling:

 38 x 98 mm

Technical data PD4-Slave

Power supply:

  

230 V~ 

±

10 %

Impulse output:

  

Optocoupler max. 2 W

Impulse duration:

  

2 s or 9 s

Dimensions:

 

see above

 

Declaration of Conformity: 

The product complies with the low 

voltage recommendation 2006/95/EC and the EMV recommenda-

tion 2004/108/EC.

19. Technical data PD4-M-DIM-HVAC

14. Wiring diagrams

15. Connections

Type

SM

FC

FM

PD4-M-DIM-HVAC (Master)

92507

PD4-S (Slave)

92142

92254

92163

LUXOMAT

®

 Remote control

IR-PD-DIM-HKL(incl. wall bracket) 

92114

Accessory:

 

BSK Ball basket guard 92199

Occupancy detectors – Covering IP23 

92206

17. Article / Part nr. / Accessory

MAN 7181 

– 

31

07

13

–4

In case the sensing area of the 

LUXOMAT

®

 PD4-M-DIM-HVAC 

is too large or areas are being covered that should not

be monitorerd, the range can be reduced or limited

through use of the enclosed masking clips

18. Exclude sources of interference

13. Range

11.  Manual Dimming – Preset /User 

(for IR-PD-DIM-HKLfunctions see page 1)

 

You can dim manually by pressing the push button for

a long time (> 2 sec). When the button is released,

the current dimming value is retained. Upon renewed

dimming, the dimming direction is reversed.

PRESET – 

the luminance set point is set during start-up

operation by the installer and remains unchanged.

The luminance set- point configured through manual

dimming is only applied for the time being. 

Caution: 

The constant light regulation is now deactivated!

The currently set artificial light is retained independent

of the ambient/daylight brightness!

After switching off and then back on, the originally set

luminance set-point is reset = constant light regulation

is activated.

USER – can only be activated via the remote control!

The luminance set-point is changed upon each manual

dimming and re-adjusted by the user (Conformation

through relay clicking!)

The constant light regulation remains activated!

10.  Fully / Semi automatic mode 

(for IR-PD-DIM-HKLfunctions see page 1)

 

The system switches over when the “Light” push-button is

open (see remote control functions, page 1).

Each time a push-button is pressed, the current operating

mode is indicated by the red LED:

Lit for 3 sec. = Fully automatic mode

Flashes for 3 sec. = Semi-automatic mode 

Fully automatic operation

In this operating mode, the lighting switches automatically on 

and off for increased comfort, depending on presence and 

brightness.

Semiautomatic operation

(Semiautomatic can only be activated via the remote control!)

In this operating condition, in order to gain increasedsav-

ings, the lighting is energized only after being manually 

switched on. Switch-off takes place automatically.The  

semiautomatic mode basically behaves like the fully 

automatic. However, the difference is that switching-on must 

always be carried out manually!
As many (closer-contact) buttons as desired can be wired in 

parallel on the “S” button input (ON/OFF Dimm).

12. Manual Switching

 

The light will remain switched on or off, as movements are 

detected in the area. After the last detected movement the 

light will be off for the duration of the set-up time. The device 

will then return independently to the Operation mode (Full or 

Semi-automatic).

20. LED-functional indicators, fault-finding

The functional indicators in the case of the 

LUXOMAT

®

  

PD4-M-DIM-HVAC (red and green LED‘s) 

Red LED indicating self-checking mode (over a period of 60 

seconds following mains‘-supply lock-on)

 

Flashing at intervals of 1 second

EEPROM

/memory empty

Flashing rapidly

EEPROM

/memory contains information

Red LED as an indicator of status

 

Flashing irregularly

Movements are detected within the area of coverage

Flashing regularly

Detector identifies bright, light off
(dependent upon operating mode)

Not illuminated

Detector identifies dark, light on
(dependent upon operating mode)

Flashing extremely rapidly

Too bright / Too dark / Undefined

Red LED as an acknowledgement of receipt for commands from 

the remote control

 

Illuminated for 2 seconds

Signal validly received

Illuminated for 0.5 seconds

Not-accepted command, detector blocked

Flashing extremely rapidly

Not-accepted command, occurs, for example, when an attempt
is made to input twilight-value are too bright or too dark

Green LED as an acknowledgement of receipt for commands from 

the remote control 

Lights up for 3 seconds

Semi automatic or user signal correctly received

Green LED as an indicator of status (only for status

“Permanent protection against sabotage”) 

Flashing irregularly

Movement are detected within the area of coverage

Flashing regularly

Detector identifies bright, light off
(dependent upon operating mode)

Not illuminated

Detector identifies dark, light on
(dependent upon operating mode)

lluminated for 2 seconds

Signal validly received
(dependent upon operating mode)

White LED

 

Lights permanently

 

Semi-automatic active (shines)

Illuminates 4 seconds, then 1 sec off

 

Semi-automatic and active corridor 

Illuminates 1 seconds, then 4 sec off

 

Only active corridor

e

1

2
3

Walking across
Walking towards
Seated

24 m

8 m

6,40 m

24 m

360°

2,50 m

2

3

1

WE RECOMMEND THAT BEFORE DIMMING OF THE CONNECTED 

LIGHTS A 100H BURN IN (T5 TUBES OR 80 HOURS FOR T8 TUBES )

FUNCTION TA kES PLACE .
THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN 

DOES NOT TA kE PLACE .

Standard mode with master-DIM-HVAC-occupancy detectors

Master

Slave

L

N

       

E1     1

-

10 V EB

 

N

 

+

 

-

 

R

 

S

 

L´1

 

-

 

+

 

N

 

R

 

T1

 

C1

 

C1

 

M1

 

NO

 

HVAC

 

NO

 

HVAC

 

T2

 

M1 = HVAC-Function

optional

T1 = NO Taster for Light-Channel
T2 = NO Taster for HVAC-Channel
Slave to the extension of coverage

PD4-M-DIM-HVAC-FC

L

N

R

Slave

L'

NO

NO

L

S N

+ R

T1

T2

N

L

+

E1  

1-10 V  

EVG

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

M1

16. Manual switching HVAC-Channel

230VAC for 0.1 - 1 second on the slave port R

Lay on the slave port R for 0.1 - 1 second to 230VAC,is this 

like a key signal for the HVAC channel interpreted.

quer zum Melder gehen 
frontal zum Melder gehen
Unterkriechschutz

max

50

Lux

1500

Lux

ON

OFF