Installation and Operating Instruction for B.E.G. - Occupancy detector PD2-M-DALI/DSI-SM/FC

LUXOMAT

®

PD2-M-DALI/DSI

DE

2. Operation

The presence detector controls the light automatically according 

to people present (movements) and the ambient brightness.
The integrated light sensor constantly measures the ambient 

light  and compares it with the set value brightness on the 

detector. 

If the ambient light is sufficient, lighting will not be switched.  

If the ambient light level is below the set value brightness, a 

movement activates the lighting in the room.
The detector switches the light off despite of a person being 

present if there is enough natural light for 5 min or if no move-

ment is detected for one follow-up time. 

 3. Safety information

A circular opening of diameter

68 mm must be produced in the

ceiling. Having connected up the

cables in accordance with regula-

tions, the detector is inserted into

the opening and fixed into position 

with the assistance of the spring 

clips (see figure 2).

4b. Mounting FC

68 mm

68 mm

5a.   Position DIP switches, LEDs and 

Potentiometers SM

5b.  Position DIP switches, LEDs and Poten-

tiometer FC

  1. Product information

 

·

       Occupancy  detector  for  daylight-dependent  lighting  control

 

·

DALI / DSI interface for controlling digitally dimmable 

electronic ballasts as a group

 

·

Switching between DSI and DALI program by remote 

control or DIP switch

 

·

Extension of the detection area by slave devices is possible

 

·

Other functions adjustable by remote control (optional)

 

·

Manual switching and dimming via pushbutton possible

 

·

Orientation light function

Work on the 110-240 V mains supply may only 

be carried out by qualified professionals or by 

instructed persons under the direction and super-

vision of qualified skilled electrical personnel in 

accordance with electrotechnical regulations.
Disconnect supply before installing!
This device is not suitable for disconnection.
Mounting the cover ring after introduction of the 

power cable (FC version).

!

!

!

The product enters an initial 60-second self-test cycle, when the  

supply is first connected. During this time the device does not 

respond to movement and stays on.

6. Self test cycle/Startup behavior

7. Putting into operation/Settings

Brightness set value for constant light control 

(Potentiometer A)

The brightness set value can be defined between 

10 and 2000 Lux. The potentiometer enables a free 

selection of the brightness value.
Symbol

 

:   Night-time operation

Symbol

 

:     Daytime operation 

(light evaluation inactive)

Follow-up time “Light” (Potentiometer B)

The follow-up time can be set to 1 to 30 minutes.
Symbol 

TE

: test mode  

Irrespective of the brightness, every movement 

switches the light on for 1sec., then off again for 

2 sec.

Follow-up time orientation light (Potentiometer C)

Manually switching the orientation light on/off. 

“ON” for permanent orientation light OFF” for 

switching off the orientation light

TIME

TE

1

3

6

22

18 16

10

30

25

LUX

40

2000

600

1200

200

20%

60

5

10

50 30

O

FF

O

N

9s

2s

LED ON

LED OFF

TIME

TE

1

3

6

22

18 16

10

30

25

LUX

40

2000

600

1200

200

20%

60

5

10

50 30

O

FF

O

N

9s

2s

LED ON

LED OFF

TIME

TE

1

3

6

22

18 16

10

30

25

LUX

40

2000

600

1200

200

20%

60

5

10

50 30

O

FF

O

N

9s

2s

LED ON

LED OFF

8. Wiring diagram

9. Manual switching and dimming (see section 23)

By pressing the push button, the phase can be given to the S

terminal.
To turn on or off the light, press the push button briefly. The light 

will remain on or off, as long as people are detected plus the 

follow-up time.
With a long press of the push button the light will be dimmed 

manually. When releasing the button, the current brightness 

value is retained.

With renewed long press of the push button, the dimming 

direction is reversed.

Standard mode with Master/Slave device(s)

Connected Slave devices must have the same phase as the 

Master device.

!

Figure 2

!

!

The light sensor must be positioned facing away from 

the window.

In master/slave mode, the master device must al-

ways be installed at the location with least daylight.

EN

L

N

E1 

DALI /DSI

L

N

DA
DA

L

N

R

S

+

-

DA1

N

L

R

T1

Master

 device

  

        

Slav

e

 device

!

4. Mounting

4a.   Mounting SM

The detector has to be mounted on 

a plane and solid surface. Before 

mounting, cover ring has to be 

removed. To do so, twist the cover 

ring anticlockwise through approx. 5° 

and lift off. 

Having connected up the cables in 

accordance with regulations, put 

on the cover ring by turning in a 

clockwise direction (see fig. 1). Apply 

mains voltage.

Figure 1

close

open

Schematic diagram - when connecting the detector, please res-

pect the labelling of the terminal connections at the detector!

DIP switch functions
DIP 1

Full automatic mode

(VA)

Semi-automatic mode 

(HA) 

DIP 2

LED ON

LED OFF

DIP 3

Operation mode DALI

Operation mode DSI

LED I

   green

LED II  

red 

LED III   

white 

Potentiometer  A

 Brightness set value (constant light control)

Potentiometer  B

 Follow-up time light

Potentiometer  C

 Follow-up time (orientation light)

C

B

A

PD2 Surface 

mounting

Light  

measurement

DIP

LED

OFF

DSI

DALI

VA

HA

LED

ON

1

I

II

III

2

3

I

II III

PD2  

False ceiling 

mounting

C

B

A

Light  

measurement

DALI_D

SI

LED ON_ LED OFF

 

VA_HA

1

2

3

DIP

10. Range

11. Exclude sources of interference

SM

FC

If the detection zone is too large, or areas are covered that should not 

be monitored, use the blinds to reduce or limit those areas.

 

·

Walking across

 

·

Walking towards

 

·

Smaller movements / Seated

2

1

1 79m

2 28m

3 13m

3

10m

6m

4m

2,50m