MAN

 86

75

_P

D2

-M

-D

AL

I/

DS

I_

EN

_0

80

11

8_

5

Wall bracket for  

remote control IR-PD-DALI-E 

IR-PD-DALI-E

15.  Settings with remote control (optional) 

(see also section 24)

Infrared remote control LUXOMAT

®

 IR-PD-DALI-E

1. Check Battery:

 

Open battery compartment by pressing 

the plastic springs together and remo-

ving the battery-holder.

2. Note

Using the remote control, the occupancy detector can only be 

operated brightness-depending. The setting “SUN” can only be 

chosen with potentiometer A.
When using the remote control IR-PD-DALI-E, we recommand to 

set potentiometer A to “SUN”. Pressing the RESET button on the 

remote control then resets the detector to brightness-independ-

ant mode (SUN).

16. Settings by remote control when open

Unlock device – 

Activation of the 

programming mode

Resetting 

when open: 

Deletes all 

values set with 

the remote 

control, light 

OFF.

Follow-up time 

light

Orientation light  

on/off

Automatic reading 

in the current light 

value as new lumi-

nance set value

or

Dimming of the 

lighting to the 

desired bright-

ness value

Stepwise adjusting the 

set value brightness 

from 50 to 1500 Lux:
+/–   step 

5 Lux

+/–  

step 

10 Lux

+

/

 step 

20 Lux

1

min

to

30

min

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

DSI/

DALI

Switching between 

DSI and DALI 

program. 

The Factory setting 

is DALI.

or

+

Full automatic-/semi- 

automatic mode (see 18) 

max

50

Lux

1500

Lux

ON

OFF

Follow-up time 

orientation light

to

min

60 

min

op

tional

op

tional

op

tional

op

tional

The DIP settings are reactivated by 

•  setting the potentiometers to “TEST” and “SUN” 

(see section 24), or

•  pressing the RESET button on the remote control in open state

!

Settings with remote control override the potentiome-

ter and DIP settings.

Exit programming 

mode

If there is no entry

for about 3 min.

the programming

mode is ended

automatically.

17. Light regulation

The detector has two different integrated light control 

algorithms. The set value for the first algorithm is adjusted by 

potentiometer (LUX) on the device. Very small light amounts, 

which shine directly to the detector, have as result that the set 

value brightness is exceeded.
The second algorithm has an integrated daylight compensation. 

Therefore, it is necessary that the detector analyses the swit-

ched light quantity. This algorithm can only be used by remote 

control. The programming of the set value and the measurement 

of the light quantity is carried out in two steps: 

In the open state

•  The set value is adjusted without daylight (please darken 

the room) by using the remote control.

•  Measuring the light quantity will be initiated by a long press 

(> 3 sec.) of the test button. The detector turns the light on 

for 5 min. at 100 %. Then the light will turn on and off for a 

short time and stays on after that. This measuring process 

is shown by a flashing green LED (10 sec. off/ 1sec. on). This 

measuring process is required for each change of the set 

value. If the setting “permant orientation light” is chosen, 

the function only will be active after the measuring process 

is done.

If the measuring process is not performed, the detector 

performs it automatically when the ambient light is less than 

50 Lux for 1h.

18.  Full / Semi-automatic mode  

max

50

Lux

1500

Lux

ON

OFF

 

Full automatic operation 

In this operating mode, the lighting switches automatically on and 

off for increased comfort, depending on presence and brightness.

Semi-automatic operation 

In this operating mode, the light turns on only after a manual 

switching, for an increased savings success (see section 22). 

Switching off is automatically or manually (see section 22). 

The semi-automatic mode basically behaves like the full automatic 

mode. The only difference is that the switching on has to be done 

by hand. 

In case motion is detected within the 10 sec. after elapse of the 

follow-up time, the detector switches the light on again and the 

follow-up time starts again. If there is no motion detected within 

the 10 sec. after elapse of the follow-up time, the light has to be 

turned on manually. 

Double lock

Red LED flashes

op

tional

max

50

Lux

1500

Lux

ON

OFF

t < 5 s

INI-OFF/ON mode:   

Turn off or turn on the light during the self-test cycle of 

60 sec. The last state is active. Factory setting is that the 

light is on during initialisation.
When INI OFF is chosen, the detector does not switch on 

the light after voltage supply. Even upon detected mo-

vement the light is switched on only after 60 sec.

Startup behavior

:    

The set value can be reached in two ways after switching 

on. The detector switches the lights on at 10 % and then 

adjusts upwards (min button) or it switches the light on at 

100 % and regulates down (max button). This is confirmed 

by a short flashing of the red and white LED as well as the 

lighting. Factory setting is that the detector switches the 

light on at 100 %.

Reset of electronic ballasts (manually or automatically)

 

If required the connected EB can be reset and preset 

parameter can be deleted. Press the button “Reset” 

briefly in self-test cycle.

The use of some electronic ballasts may require to send 

a reset command automatically after each start of the 

detector (auto reset). In order to activate (red LED) oder 

deactivate (green LED) the function press the „reset“ 

button in open state for 3 seconds.

!

19.  Settings during the Self-test cycle

In the first 60 seconds after connecting the AC voltage, the 

following functions can be set:

20. Test mode/Reset

 

Test mode 

Use “Test” button for activating the test mode and the 

“Reset” button to deactivate it.

Reset in closed state 

The lighting is switched off, and the follow-up times are 

reset.

Reset in open state

Pressing the button for >3 sec. deletes all settings 

(except of INI ON/OFF) and the detector is reset to 

factory state. 

21. 100 h function 

(

long press

 (> 3 sec.) 

when closed

max

50

Lux

1500

Lux

ON

OFF

Before the lamp can be dimmed, the dimming function has 

to be suppressed for a certain time in order to burn in the 

lamps.

T5 fluorescent lamps: 8

0 h

T8 fluorescent lamps: 10

0 h

For activating the function, press button “Light ON/OFF” in closed 

state. During this time, the detector only switches the light ON or 

OFF. A dimming to the set value does not take place. After having 

activated the function, the red and green LED flash alternately. By 

pressing the button “Light ON/OFF” again, it is possible to deacti-

vate the function before the time has elapsed.
Failure to comply to the burn-in would lead to reducing the life 

of the lamp. A further disadvantage could be unwanted random 

variations in light intensity.

24.  Reset the detector

If the double lock is activated, the detector can be opened again as 

follows:
• 

Disconnect operating voltage

• 

Connect operating voltage for 31sec. to 59 sec.  

• 

Disconnect operating voltage again

• 

Connect operating voltage again and wait for the self testing

• 

Open detector

With this procedure, the remote control programmed values are not 

deleted (before activation of the double lock).

If the setting is not changed by remote control after deactivation 

of the double lock, the detector changes in the double locked mode 

again after a period of 30 minutes. This way the detector cannot be 

unlocked during an accidental power failure.
Alternatively, the detector can be reset in this way: 

Set potentiometer A to “Sun” and potentiometer B to “Test”. The de-

tector now is in test mode and the potentiometer settings are active. 

All operating LEDs are flashing for three seconds.
Except of the INI ON/OFF setting, the detector is reset to factory 

setting or the setting of the potentionmeter.
Pushing the “RESET” button on the remote control, in opened mode, 

will delete all of the values which were set by the remote control 

(beside of INI ON/OFF) and set the detector back to  

its factory settings.

Factory settings

 

The detector is delivered with the following factory  

settings: Brightness set value: 500 Lux, follow-up time:  

10 minutes. Auto reset: off. Starting the detector in the factory 

program the self-test cycle starts with a constant flashing of the 

three operating LEDs.

23.  Manual Dimming - Preset / User  

 

(long press when closed)

You can dim manually by pressing the external push button or 

the remote control buttons "min/max" – for a long time  

(> 2 sec.). When the button is released, the current dimming 

value is retained. Upon renewed dimming, the dimming direction 

is reversed.

max

50

Lux

1500

Lux

ON

OFF

     Two different operating modes are selected  

in the opened state.

Changing the mode is done by pressing the "double lock" button. 

Each time the button is pressed, the current operating mode is 

indicated:

Red shines for 3 sec.  = Preset

Green shines for 3 sec.  = User

PRESET – 

the set value brightness is set during start-up operation 

by the installer and remains unchanged. The set value brightness 

configured through manual dimming is only applied for the time 

being. 
The constant light regulation is now deactivated! The current set 

artificial light is retained independent of the ambient/daylight 

brightness! After switching off and then back on, the original 

set set value brightness is reset = constant light regulation is 

activated.

USER can only be activated via the remote control

The set value brightness is changed upon each manual dimming 

and re-adjusted by the user. The constant light regulation 

remains activated!

22. Manual Switching 

(

short press when closed

)

 

max

50

Lux

1500

Lux

ON

OFF

You can switch the lighting on and off manually by pressing the 

pushbutton or the remote control button “Light ON/OFF” for a 

short time. It will stay on or off as long as people are detected 

plus the configured follow up time.

!

Preset/User-mode 

(see section 23) 

Start light measurement 

by long press of the 

button (see section 17) 