Article
Colour
Part.-nr.
LC-Click-N 140
white
91001
LC-Click-N 140
black
91021
LC-Click-N 140
brown
91011
LC-Click-N 200
white
91002
LC-Click-N 200
black
91022
LC-Click-N 200
brown
91012
Accessory
:
RC-Suppressor 10880
13. Article / Part nr. / Accessory
12.
Technical data
Power supply:
230 V~
±
10 %
Detection area: LC-Click-N 140
140°
LC-Click-N 200
200°
and 360° anti-creep protection
Range of coverage in m:
max. 12 m when walking across (tangential
)
Degree of protection/class:
IP 44 / Class II /
Dimension:
L 103 x B 78 x H 80 mm
Ambiente temperature:
-25°C to +50°C
Package:
Housing UV- and
shock-resistant Polycar-
bonate
Chanel 1 for light control
Contact load:
1000 W, cos
φ
= 1 ,
µ-Contact
Time-settings:
4 s - 10 min.
Brightness value:
2 - 2000 Lux
Declaration of Conformity:
The product complies with the low voltage
recommendation 2006/95/EC/ and the EMV
recommendation 2004/108/EC.
10. Dimensions (mm)
M
A
N 7
02
3
– 111
01
2-
6
9. Wiring diagrams
N
L
N
L
L‘
C 1
E 1
L
N
E 1
S 1
RC
N
L
L‘
C 1
N
N
L
L
L‘
C 1
E 1
T 7
L
L
L
C 1
C 1
L‘
L‘
N
N
N
E 1
L
L
L
L‘
N
N
N
E 1
T 1
T 2
30 s -
10 min.
4
3
Standard mode with 1-channel motion detector
Standard mode with 1-channel motion detector with
permanent light function
Standard mode with 1-channel motion
detector with NC pushbutton
Parallel connection with 1-channel motion detectors
max. 2 parallel
Standard mode with 1-channel motion detector
(e.g. stairs)
optional:
S1 = switch for permanent light
RC = RC-suppression kit if required
T 1 = NC button
Manual switching additionally possible (press opener
approx. 2 sec.).
11. Trouble Shooting-Practical hints
1. Lamp does not light up
Cause
- Action
Lamp is defective
- Replace light bulb
.
No mains connection
- Check mains fuse
.
Switching threshold of the twilight switch is not
correct
- Accordingly adjust sensitivity of twilight switch
via the setting dial.
Detection area not set correctly
Set detection area correctly.
Unit mounted too high
- Mount at recommended height (2.50 m)
PIR detector lens obstructed by dirt or other
objects
- Clean lens or remove objects
2. Delayed lamp activation
Mounted too high
- Mount at height stated in specification (2.
5 m)
Only direct in-line approach of detector is
possible
- Mount detector in such a way that a sideways
approach is also detected.
3. Lamp stays on continuously
Continuous thermal movement within detec-
tion area
- Remove the heat source out of the detec-
tion area.
Check the correct functioning of the detector in
fully covering the lens (lights should go out after
a certain time-delay).
Motion detector is switched parallel to a switch
that enables direct manual switching on
- Mind the correct connection of the switch.
4. Light source remains on for long periods when
no persons are present
Permanent influence from heat sources within
detection area (trees, shrubs when blown by the
wind, presence of animals like cats and dogs in
the detection area)
- Reduce detection area of the detector in
turning the detector head downward or cover
parts using the enclosed covers.
Direct sunlight radiation into detector lens
- Shelter lens from direct sunlight.
Detector mounted above extractor fan
- Change mounting place of the detector.
5. Limitation of range (not up to the minimum
specification)
Mounting height is not optimal
- Accordingly change mounting height
(2.50 m).
Persons only move directly towards
the detector
- Mount detector in such a way that a sideways
approach is also detected.
Steep terrains
- Adjust spherical head accordingly.
6. No reaction to vehicles
Vehicle not warmed up
Vehicle is well insulated (by silencing equipment)
78
78
60
36
67
80