B.E.G. LUXOMAT LC-Click-N 140 Скачать руководство пользователя страница 2

Article

Colour

Part.-nr.

LC-Click-N 140

white

91001

LC-Click-N 140

black

91021

LC-Click-N 140

brown

91011

LC-Click-N 200

white

91002

LC-Click-N 200

black

91022

LC-Click-N 200

brown

91012

Accessory

:

RC-Suppressor 10880

13. Article / Part nr. / Accessory

12. 

Technical data

Power supply:

        

230 V~ 

±

10 %

Detection area: LC-Click-N  140

 

140°

 

LC-Click-N 200

 200° 

and 360° anti-creep protection

Range of coverage in m:

  

max. 12 m when walking across (tangential

)

Degree of protection/class:

   

IP 44 / Class II / 

Dimension: 

L 103 x B 78 x H 80 mm

Ambiente temperature:

  -25°C to +50°C

Package:  

Housing UV- and 

shock-resistant Polycar-

bonate

Chanel 1 for light control
Contact load: 

1000 W, cos

φ

= 1 ,  

 µ-Contact

Time-settings: 

4 s - 10 min.

Brightness value: 

2 - 2000 Lux

 

Declaration of Conformity: 

The product complies with the low voltage 

recommendation 2006/95/EC/ and the EMV 

recommendation 2004/108/EC.

10. Dimensions (mm)

M

A

N 7

02

– 111

01

2-

6

9. Wiring diagrams

N

L

N

L

L‘

C 1

E 1

L

N

E 1

S 1

RC

N

L

L‘

C 1

N

N

L

L

L‘

C 1

E 1

T 7

L

L

L

C 1

C 1

L‘

L‘

N

N

N

E 1

L

L

L

L‘

N

N

N

E 1

T 1

T 2

30 s - 

10 min.

4

3

Standard mode with 1-channel motion detector

Standard mode with 1-channel motion detector with  

permanent light function

Standard mode with 1-channel motion 

detector with NC pushbutton

Parallel connection with 1-channel motion detectors 

max. 2 parallel

Standard mode with 1-channel motion detector 

(e.g. stairs)

optional:

S1 = switch for permanent light
RC = RC-suppression kit if required

T 1 = NC button

 

Manual switching additionally possible (press opener 

approx. 2 sec.).

11. Trouble Shooting-Practical hints 

1. Lamp does not light up
Cause 

- Action

Lamp is defective

- Replace light bulb

.

No mains connection

- Check mains fuse

.

Switching threshold of the twilight switch is not 
correct 

-  Accordingly adjust sensitivity of twilight switch 

via the setting dial.

Detection area not set correctly
Set detection area correctly.
Unit mounted too high

-  Mount at recommended height (2.50 m) 

PIR detector lens obstructed by dirt or other 
objects

- Clean lens or remove objects

2. Delayed lamp activation

Mounted too high

- Mount at height stated in specification (2.

5 m)

Only direct in-line approach of detector is 

possible 

-  Mount detector in such a way that a sideways 

approach is also detected.

3. Lamp stays on continuously

Continuous thermal movement within detec-

tion area 

-  Remove the heat source out of the detec-

tion area.

Check the correct functioning of the detector in 

fully covering the lens (lights should go out after 

a certain time-delay).

Motion detector is switched parallel to a switch 

that enables direct manual switching on 

- Mind the correct connection of the switch.

4.  Light source remains on for long periods when 

no persons are present

Permanent  influence  from  heat  sources  within 

detection area (trees, shrubs when blown by the 

wind, presence of animals like cats and dogs in 

the detection area)

-  Reduce detection area of the detector in 

turning the detector head downward or cover 

parts using the enclosed covers.

Direct sunlight radiation into detector lens

- Shelter lens from direct sunlight.

Detector mounted above extractor fan

- Change mounting place of the detector.

5.  Limitation of range (not up to the minimum 

specification)

Mounting height is not optimal

-  Accordingly change mounting height 

(2.50 m).

Persons only move directly towards 

the detector

-  Mount detector in such a way that a sideways 

approach is also detected.

Steep terrains

- Adjust spherical head accordingly.

6. No reaction to vehicles

Vehicle not warmed up

Vehicle is well insulated (by silencing equipment)

78

78

60

36

67

80

Отзывы: