NETWORK DESIGN AND TROUBLESHOOTING 

 

NETWORK PHYSICAL LAYOUT 

The Wzzard Mesh network is extremely robust and reliable when you follow a few simple rules. 

 

 

1.  Each node should have a line of site path to 3 other nodes or to the gateway. 2 of these should be in 

the direction closer to the gateway if possible. In the small example network above, only nodes 5 and 

6 violate this rule. The outermost nodes may not have a third node to connect to, but they do have 2 

good “Parents” in their path back to the gateway. 

2.  You should be able to picture at least two paths from any one node to the gateway. 

3.  Each path should be as short as possible. Less than 100m indoors with lots of metal or walls. Less 

than 300m outdoors with no obstructions. 

4.  No node’s data should have to go through more than 7 other nodes before reaching the gateway. 8 

hops is the maximum allowed by the network. 

5.  It’s best to build the network from the gateway out where possible. The more nodes that attach 

directly to the gateway, the less traffic that has to flow through a single node. The small example 

network above has two nodes that connect directly to the gateway. For larger networks, this number 

should be higher. 

 

No RF site survey is necessary. The SmartMesh IP network will automatically adjust frequencies between 

channels when RF conditions change. 

 

As nodes are added to the network, they will automatically join the network and the paths will be re-

optimized for reliable communication  

 

SmartWorx Hub provides several features for troubleshooting your Wzzard Mesh network, individual 

nodes, and individual I/O points. 

Содержание Wzzard WSD2C21150

Страница 1: ...Wzzard Mesh Wireless Sensors Intelligent Edge Nodes Wireless Sensing Platform USER MANUAL ...

Страница 2: ...awa IL 61350 USA Phone 815 433 5100 Fax 815 433 5105 Advantech B B SmartWorx European Headquarters Westlink Commercial Park Oranmore Co Galway Ireland Phone 353 91 792444 Fax 353 91 792445 www advantech bb com support advantech bb com Documentation Number Wzzard Ind Comm_r5_0518m ...

Страница 3: ...1 Restoring Node to Factory Default 11 Battery Replacement 11 Connecting Your Sensor to Wzzard Commercial Node Model 13 MOunting Options Commercial Node 13 Adhesive Strip Mounting 13 Mounting Bracket Plate 14 Zip Tie Mounting 14 Putting Node in Deep Sleep 14 Restoring Node to Factory Default 14 CONFIGURING AND MANAGING WZZARD MESH WIRELESS SENSORS 15 CREATE AND LOCK THE NETWORK 16 CONFIGURE THE GA...

Страница 4: ...GENERAL SPECIFICATIONS ALL MODELS INDUSTRIAL COMMERCIAL 36 RADIO SPECIFICATIONS ALL MODELS INDUSTRIAL COMMERCIAL 37 MECHANICAL DRAWINGS 38 Wzzard Industrial Node Models 38 Wzzard Commercial Node Models 38 MODEL NUMBERS 39 Wzzard Mesh Wireless Sensors Industrial Nodes 39 Wzzard Mesh Wireless Sensors Commercial Nodes 39 DECLARATION OF COMPLIANCE 40 DECLARATION OF CONFORMITY CE 42 ADVANTECH B B SMART...

Страница 5: ...aid End user agrees to accept all liability for loss of or damages to the returned product during shipment Advantech B B SmartWorx shall repair or replace the returned product at its option and return the repaired or new product to the end user freight prepaid via method to be determined by Advantech B B SmartWorx Advantech B B SmartWorx shall not be liable for any costs of procurement of substitu...

Страница 6: ... network management and comprehensive security features The platform uses full SmartMesh IP networking and time synchronized channel hopping to provide up to 99 999 connectivity even in the most demanding RF environments The Wzzard Mesh wireless sensor platform enables rapid network deployment and expansion New nodes may be added at any time and the SmartMesh network dynamically self configures as...

Страница 7: ...it connection model only 2 AA 3 6V Thionyl Chloride Lithium batteries External antenna Quick Start Guide Anti Skid disk WZZARD COMMERCIAL NODE MODEL PACKAGE INCLUDES Wzzard Mesh Wireless Sensor Node for commercial applications 1 2 3 AA 3 6V Thionyl Chloride Lithium battery Quick Start Guide Mounting Bracket Plate included factory installed Dual adhesive strip included factory installed ...

Страница 8: ...e Note UL C1 D2 rating is voided when using non UL specified batteries Remove the four 4 black screws that hold the top of the Wzzard node in place Connect your sensor CONDUIT NODE MODELS Thread the included wire harness through the conduit and into the node Plug the wire harness into the circuit board inside the node 1 Brown 2 Red 3 Pink 4 Yellow 5 Green 6 Blue 7 White 8 Gray ...

Страница 9: ...0 VDC AIN1 AIN2 DO1 DIN1 GND GND GND Wiring Chart Abbreviations 10 30VDC 10 30V DC Power Input AIN1 Analog Input 1 AIN2 Analog Input 2 AIN3 Analog Input 3 DIN1 Digital Input 1 D01 Digital Output 1 GND Ground Input INDUSTRIAL NODE WITH M12 CONNECTOR M12 ACCESSORY CABLE Note UL Class1 Division2 rating is voided when using M12 model M12 WIRING TIP You can use your own M12 cable or order B B SmartWorx...

Страница 10: ...tal Input 1 GND Ground Input TERMINAL BLOCK CONNECTIONS THERMOCOUPLE THERMISTOR Thread the thermocouple and thermistor wires through the conduit and attach them to the terminal block MOUNTING THE NODE Wzzard industrial nodes may be mounted either with screws or temporarily with built in magnets The included anti skid disk may be attached to bottom of unit to prevent slipping on metal surfaces Flan...

Страница 11: ...figuration button for 5 seconds until the Status LED turns off The node will retain all settings including the associated network if the node has been claimed It will not reset the device back to factory settings RESTORING NODE TO FACTORY DEFAULT To reset the node to factory defaults press and hold the Status Sleep Reset configuration button for 10 seconds until the Status LED flashes quickly This...

Страница 12: ...lip is to insert a small flathead screwdriver between the batteries and the clip parallel to the batteries and give the screwdriver a gentle twist This will remove the clip without damage Note As with all batteries these are a fire explosion and severe burn hazard Do not burn or expose them to high temperatures Do not recharge crush disassemble or expose the contents to water Properly dispose of u...

Страница 13: ... Pin 6 Do Not Use DIN1 Thermistor Input AIN1 AIN2 Common GND Pin Abbreviations DIN1 Digital Input AIN1 Analog Input AIN2 Analog Input GND Ground THERMISTOR BREAKOUT CABLE PIN OUT PIN AIN1 AIN2 Door Switch Red Black Yellow Black Blue Black AIN1 GND AIN2 GND DIN1 GND Pin Abbreviations AIN1 Analog Input AIN2 Analog Input DIN1 Digital Input GND Ground MOUNTING OPTIONS COMMERCIAL NODE ADHESIVE STRIP MO...

Страница 14: ...ut into deep sleep Press the Status Sleep Reset configuration button for 5 seconds until the Status LED turns off The node will retain all settings including the associated network if the node has been claimed It will not reset the device back to factory settings RESTORING NODE TO FACTORY DEFAULT To reset the node to factory defaults press and hold the Status Sleep Reset button for 10 seconds unti...

Страница 15: ... to log in and claim your gateway The configuration of the Wzzard Mesh sensor network is done at 3 levels 1 Gateway Network Level When the gateway is selected in the tree you can turn node discovery on and off claim and release nodes and review the health status of the network 2 Node Level When a single node is selected in the tree you can configure the measurement interval set up any triggers ret...

Страница 16: ...ween Centigrade and Fahrenheit etc CREATE AND LOCK THE NETWORK 1 Wake Up The Node Press and hold Status Sleep Reset configuration button for 5 seconds until the Status LED comes on and starts blinking 2 Check LEDs After you wake the node the Status LED will begin to blink This indicates that the node is attempting to establish a network connection The Status LED will come on solid when a network c...

Страница 17: ...lick the checkbox next to each node Click the Claim Nodes button to prevent the nodes from joining another open network All nodes will be set to a unique Network ID and Join Key for this network They will no longer search for another open network The gateway will automatically turn off node discovery for the network 24 hours after powering on In some cases it may be necessary to control this funct...

Страница 18: ...Node Discovery select the gateway from the tree and click the Node Discovery switch to move it in the opposite position CONFIGURE THE GATEWAY S MESH INTERFACE Select your SmartSwarm Gateway by clicking on the Device ID Now select the Wzzard Mesh App ...

Страница 19: ...me made up by you and is required for any MQTT connection Timeout Retry Interval and Keep Alive need to be filled in to work with any broker Defaults are shown below and should work in most instances The SmartSwarm 342 includes an internal broker for use with the embedded Node Red app The internal broker is at the main IP address of the gateway The default is 192 168 1 1 The port for the internal ...

Страница 20: ...arge as possible to save battery life and still get the measurement resolution required by the application The nodes are capable of a Measurement Interval of 10s to 84 600s 24 hours The default is set to one minute To set the Measurement Interval for a node Select the node from the tree Expand the Node Configuration section by clicking on the sign Enter the desired Measurement Interval in seconds ...

Страница 21: ...nly send its data out of the gateway at specific time periods or when limits of an input are exceeded This is especially helpful in conserving data costs on a cellular network On Time Turning on On Time publishes allows you to publish data values to MQTT over a longer time interval than what s being measured at the node On Value If On Time is turned on the On Value setting allows you to override t...

Страница 22: ...r you want to start receiving data when an input exceeds a certain value or falls below a certain value Select which input on the node to which you would like to apply the rule Enter the Threshold value to be exceeded in order for the trigger Rule to be true Values should be entered in Engineering Units Enter a value of hysteresis you would like to exceed before the trigger Rule is no longer true ...

Страница 23: ...Wzzard Sensor Edge Nodes 23 ...

Страница 24: ...al world Engineering units as it is published from the gateway Any consumers of the data could avoid having to make their own transformations In the Data Enrichment section enter the real world value being measured Gallons AC Amps etc Then enter two data points that correlate the measured Voltage or Current to the real world Engineering unit being measured Ex I have a linear level sensor that outp...

Страница 25: ...ons received on the Digital Input at the node s Measurement Interval Rate A Rate Measurement Type will publish 1 the number of 0 to 1 transitions received on the Digital Input during a one second sample at the node s Measurement interval Hz Multiplier Number above 0 000001 The Multiplier is the number a Counter or Rate will be multiplied by before being published over MQTT Engineering Unit ASCII T...

Страница 26: ...n wireless traffic and battery life Digital outputs are Enabled by default The Inverter Switch defines if 1 High output or 1 Low output Inverter Off 1 High and 0 Low Inverter On 1 Low and 0 High The Digital Output Mode switch allows you to manually set the Digital Output Off or On The output setting will be overridden by any MQTT command to set the output ...

Страница 27: ...HUMIDITY INPUT CONFIGURATION Humidity inputs can be Enabled Disabled It s recommended that you disable all unused inputs to save on wireless traffic and battery life Humidity inputs are Enabled by default COPYING NODE CONFIGURATIONS If more than one node is used to monitor the same type of asset it is simpler to copy configurations between nodes than to set up each node individually Once a node an...

Страница 28: ...rovide a list of all nodes on the network with the same model number Select the MAC address of the node s you wish to copy to and click the Replicate Settings button All settings for the node and the I O points will be copied to the selected node s ...

Страница 29: ... walls Less than 300m outdoors with no obstructions 4 No node s data should have to go through more than 7 other nodes before reaching the gateway 8 hops is the maximum allowed by the network 5 It s best to build the network from the gateway out where possible The more nodes that attach directly to the gateway the less traffic that has to flow through a single node The small example network above ...

Страница 30: ...ation review the nodes and their respective health color NODE LEVEL TROUBLESHOOTING There are two indications in SmartWorx Hub that a node is not behaving properly in the Mesh network 1 A node reports as lost Line through the node in the tree 2 Health color is yellow or red If a Node Health Color is not staying green 30 minutes after full network formation or if a node is periodically lost 1 With ...

Страница 31: ... nodes Nodes can also be added as repeaters Since all nodes act as repeaters just set one down and turn it on Is this node at the same height as others in the vicinity The farther from ground the node can be mounted the more the RF signal has a place to expand On industrial nodes is the antenna parallel to other nodes in the vicinity You may want to rotate the antenna if there is a vertical distan...

Страница 32: ...by clicking the triangle next to the node in the tree Data is shown in the Engineering Units set in the I O point configuration The date and time of the last data read is shown at the top of the I O point list This time is in Zulu time Usually GMT 2 To get a new data reading select the node and click the Update Data button After a few seconds the new sensor readings for that node will appear in th...

Страница 33: ... mounting ear flanges screws Certifications FCC FCC Part 15 Class A FCC Part 15 247 IC ICES 003 2016 ITE Emissions for Canada CE 2014 35 EU Low Voltage Directive 2014 53 EU Radio Equipment Directive 2011 65 EU Reduction of Hazardous Substances Directive RoHS 2012 19 EU Waste Electrical and Electronic Equipment Directive WEEE ETSI EN 300 328 v2 1 1 EMC Radio Spectrum Matters ERM Wideband Transmissi...

Страница 34: ...roups A B C D Safety IEC 60068 2 6 Sine Vibration 4G 10 500 Hz 0 06 in displacement IEC 60068 2 27 Mechanical Shock 50G 11ms 18 pulses Regulatory Approvals RoHS and WEEE Compliant THIONYL CHLORIDE LITHIUM BATTERY 2 supplied with industrial nodes Size AA Temperature Range 55 to 85 C Nominal Capacity 2 4 Ah Nominal Voltage 3 6 V Diameter 14 5 mm Height 50 1 mm Potential Hazard Do not recharge crush ...

Страница 35: ...Mounting Mounting Mounting bracket included VHB adhesive strip included or ZIP ties not included Weight 0 09kg 0 2 lb Certifications FCC FCC Part 15 Class A FCC Part 15 247 IC Industry Canada RSS210 Regulatory RoHS and WEEE Compliant CE EN 55022 CISPR Class B EN 61000 6 2 Generic Immunity Standard for Heavy Industrial Environments EN 61000 6 4 A1 Emission Standard for Heavy Industrial Environments...

Страница 36: ...lish interval Uses falling edge or rising edge based on Invert Enabled Setting Input Counter Channels Actively counts either falling edge Invert Enabled or rising edge Invert Disabled Can use a multiplier to convert to a unit type or count Shared with digital inputs Rolls over at 999999 9 Analog Inputs Input Range 0 10 VDC 0 20 mA software selectable Load Resistance 59 K Ohms Accuracy 25mV 0 05mA ...

Страница 37: ...lear Frequency 2405 5 k 11 MHz Modulation IEEE 802 15 4 Direct Sequence Spread Spectrum DSSS Raw Data Rate 250 kbps Range Indoor 100 m Outdoor 300 m Receiver Sensitivity Packet Data Error Rate PER 1 93 dBm PER 50 95 dBm Conducted Output Power PA On Delivered to a 50 Ω load 8 dBm Conducted Output Power PA Off Delivered to a 50 Ω load 0 dBm Radiated Output Power PA On Taoglas PA 11 BB antenna 7 dBm ...

Страница 38: ...CHANICAL DRAWINGS WZZARD INDUSTRIAL NODE MODELS Figure 1 Mechanical Drawing Wzzard Industrial Models Units millimeters inches WZZARD COMMERCIAL NODE MODELS Figure 2 Mechanical Drawing Wzzard Commercial Model Units millimeters inches ...

Страница 39: ...n BB WSD2C21150 Wzzard Mesh Wireless Sensor Industrial Cooler HVAC Node Conduit _Sensor Inputs 2 Analog Inputs 1 Digital Input 1 Digital Output 2 Thermocouples 2 Thermistors 1 Internal Temperature Indoor Outdoor w mounting ear installation WZZARD MESH WIRELESS SENSORS COMMERCIAL NODES Model Number Description UL C1 D2 Applications BB WCD1H2102H Wzzard Mesh Wireless 802 15 4e Sensor Commercial Cool...

Страница 40: ...Wzzard Sensor Edge Nodes 40 DECLARATION OF COMPLIANCE ...

Страница 41: ...Wzzard Sensor Edge Nodes 41 ...

Страница 42: ...Wzzard Sensor Edge Nodes 42 DECLARATION OF CONFORMITY CE ...

Страница 43: ...Wzzard Sensor Edge Nodes 43 ...

Страница 44: ...Wzzard Sensor Edge Nodes 44 ADVANTECH B B SMARTWORX TECHNICAL SUPPORT Phone 1 800 346 3119 Fax 1 815 433 5109 Email support advantech bb com Website www advantech bb com ...

Отзывы: