64
5-2-5. Installation resistance test
CAUTION
Do not perform the insulation resistance test. By performing this test, the built-in varistor
for surge current absorbance will be damaged. If it required to perform this test, please
carefully follow the following procedures.
Procedure
Remove the external wiring.
Short-circuit both plus and minus input signal terminals.
Perform the test between these short-circuited sections and the grounding terminal.
Applied voltage and criterion are listed below. To prevent damaging the instrument, do not
apply a voltage of more than the value given below.
Criterion
The criterion of the test is as follows.
Test
Criterion
Insulation resistance test
2×10
7
Ω or above when test voltage is 25 V DC (25°C, 60% RH
or less)