E4
BATTERY REPLACEMENT
IMPORTANT
If this module is used as a UL-certified product, the battery
should be replaced by a person who not only uses but also
maintains equipment that incorporates a UL-certified product.
Battery replacement
The backup battery can be replaced whether the power is turned
on or off.
Handling Precautions
•
To replace the battery with the power off, make sure that the
power was on for 60 minutes or more before turning it off,
and complete the replacement within 10 minutes. Failure to
do so might cause the backup data to be lost.
•
If the battery is replaced when the power is on, the battery
indicator may stay lit for about 3 minute after replacement.
This is normal, but check that the indicator turns off 3 minute
or so after replacement.
•
When putting the battery holder back into the unit, push the
release lever firmly until it clicks.
z
Replacement method with the power off
(1) Back up the module’s data to a PC using the SLP-NX
Smart Loader Package.
(2) After making sure that the power was on for 60 minutes or
more, turn the power off.
(3) Remove the unit from the base, and then remove the
battery holder from the bottom of the unit and unplug the
connector.
(4) Remove the battery from the battery holder.
(5) Set the new battery in the holder, connect the connectors,
and hang the battery cable on the hook of the holder.
(6) Put the battery holder back into the unit and connect the
unit to the base.
(7) Using the SLP-NX, check if the module’s date and time
are correct. If they are not correct, correct them and then
write the backup data that was stored in the PC in step (1)
to the unit.
Unit: mm
Clearance required
for removal of unit
Clearance required for
removal of battery holder
Battery holder
Cable hook
20
45
Release lever
z
Replacement method with the power on
(1) Remove the battery holder from the bottom of the unit,
and unplug the connector.
(2) Remove the battery from the battery holder.
(3) Set the new battery in the holder, connect the connectors,
and hang the battery cable on the hook of the holder.
(4) Put the battery holder back into the unit.
Battery disposal
When discarding the battery, dispose of it appropri-
ately, following local regulations.
DISPOSAL
When discarding the NX-S01, first remove the battery and then
dispose of it appropriately as industrial waste, following local
regulations.
SPECIFICATIONS
Specifications
z
Fault digital output contact (optional function:
NX-S_ _ _ _ _ _ 1 _)
Outputs:
1
Contact rated voltage: 24 V DC
Allowable voltage:
20.4 to 27.6 V DC
Allowable output current:
100 mA DC max.
Output type:
PhotoMOS relay output (no voltage
from A contact)
Polarity:
None
OFF-state leakage current:
100 μA max.
Maximum ON-state voltage drop:
2 V max. (at 24 V DC, 0.1 A)
Output update cycle: The same as the cycle time
z
Standard conditions
Ambient temperature: 23 ±2 °C
Ambient humidity:
60 ±5 %RH (without condensation)
Rated voltage:
24 V DC
Vibration:
0 m/s
2
Shock:
0 m/s
2
Mounting angle:
Reference plane ±3°
z
Operating conditions
Ambient temperature: 0 to 50 °C (below the installed module)
Ambient humidity:
10 to 90 %RH (without condensation)
Allowable operating voltage:
21.6 to 26.4 V DC
Vibration:
0 to 3.2 m/s
2
(10 to 150 Hz for 2h each
in X, Y, and Z directions)
Shock:
0 to 9.8 m/s
2
Mounting angle:
Reference plane ±3°
Dust:
0.3 mg/m
3
max.
Corrosive gas:
None
Altitude:
2000 m max.
Pollution degree:
2 (equivalent to normal office
environments)
z
Transport and storage conditions
Ambient temperature: −20 to +70 °C
Ambient humidity:
5 to 95 %RH (without condensation)
Vibration:
0 to 9.8 m/s
2
(10 to 150 Hz for 2h each
in X, Y, and Z directions)
Shock:
0 to 300 m/s
2
(when installed to the
DIN rail, 3 times in the up-down
direction)
Package drop test:
Drop height 60 cm (free fall on 1 cor-
ner, 3 edges, 6 sides)
EU