Inspection and Maintenance 

Since Models HTY78X3, HY78X3, and TY78X3 series are factor-inspected and -calibrated for high accuracy, no field calibration 
is necessary when these products are installed.  For inspection and maintenance, follow the maintenance instructions below: 

 

Periodic inspection 

Periodically inspect these products for its sensing accuracy.  Set the period between inspections based on how much 
atmospheric dust and other contaminants are contained in the installation environment. 
Check that if the filter is clogged with dust and other contaminants, and clean the filter. 

 

Troubleshoot 

If any problem occurs during operation, refer to the following table for appropriate solutions. 

Troubleshooting 

Problems Check 

points 

Solutions 

Loose wiring 

Tighten the terminals. 

Disconnected  wiring 

Re-perform wiring. 

Power supply voltage  

 

 No output 

 Unstable output 

Duct sensor main unit damages 

Replace the duct sensor. 

Slow response to output 

Moisture/condensation on the duct sensor 

1. Detach the duct sensor from the bracket. 
2. Remove the filter cap and the filter. 
3. Air-dry the duct sensor in a clean air. 

Inappropriate installation location 

Refer to 

Installation

 section and check if the installation 

location meets the requirements. 
Clean the filter. 
Replace the filter. 
Perform single-point calibration. 

Error in output 

Dust and contamination on the duct sensor 
main unit 

Replace the duct sensor. 

 

Filter replacement 

 WARNING  

 

Before wiring and maintenance, be sure to turn off the power to the product. 
Failure to do so might cause electric shock. 

 

IMPORTANT: 
 

Do not to touch the print board and other parts when these are not covered by the filter cap or the filter. 
Doing so might damage these parts. 

 

Содержание HTY78

Страница 1: ...ioning ducts and AHU and meteorological observation as well as industrial applications Model TY78X3 series temperature sensor and Model HY78X3 series humidity sensor are also available AHU Air handlin...

Страница 2: ...the left indicates general instructions WARNING Before wiring and maintenance be sure to turn off the power to the product Failure to do so might cause electric shock After wiring be sure to reattach...

Страница 3: ...t Doing so might cause device failure Dispose of this product as industrial waste in accordance with your local regulations Do not reuse all or a part of this product IMPORTANT Measuring accuracy of t...

Страница 4: ...0 Short probe No power N A RTD Pt100 TY7803Z0K00 Long probe TY7813Z0K00 Short probe No power N A RTD Pt1000 HTY7803D4400 Long probe HTY7813D4400 Short probe 24 V DC two wire 4 20 mA DC 4 20 mA DC HY78...

Страница 5: ...TY78X3D series Time constant at 2 m s air velocity Humidity 1 min or less at constant temperature 24 V AC 10 15 50 Hz 60 Hz 24 V DC 10 for Models HTY78X3T series HY78X3T series Power supply 24 V DC 1...

Страница 6: ...hort probe type Installation onto an duct or AHU in an instrument shelter with the dedicated bracket Wiring length Max 100 m Connection Terminal block connection AHU Air handling unit IEC Internationa...

Страница 7: ...3 HY7803 mm Models HTY7813 TY7813 HY7813 series Figure 2 Dimensions Models HTY7813 TY7813 HY7813 mm Mounting bracket Part No 83157235 001 optional Figure 3 Dimensions Part No 83157235 001 mm 30 25 50...

Страница 8: ...ceed the probe limit operating condition AHU Air handling unit Do not allow condensation especially when installing the probe pointing upward Condensation water that remains in the filter cap slits mi...

Страница 9: ...ing bracket onto the duct so that the shorter cylindrical part overhangs from the mounting surface Fasten the mounting bracket with accessory M4 screws Figure 10 Mounting bracket on the panel 3 Releas...

Страница 10: ...wiring and temperature humidity output wiring 1 25 mm or 2 mm shielded multi core cables JCS CVV S cables are recommended Be sure to ground the shielding on the controller side For Model HTY78X3D HY78...

Страница 11: ...r insufficient removal ratio provide an isolator on the controller input wiring Note No problem will occur for connecting the duct humidity sensor or duct temperature humidity sensor to our controller...

Страница 12: ...er of the conductors Temporarily screw the conduit connector and the attachment and select an O ring appropriate for the cable Figure 18 Conduit connection 1 2 Lead the cable into the duct sensor thro...

Страница 13: ...power Models HTY7803T1P00 HTY7803T4P00 HTY7813T1P00 HTY7813T4P00 7 conductors Figure 23 Terminal wiring Duct humidity sensor with 1 5 V 4 20mA humidity output 24 V AC DC power Models HY7803T1000 HY780...

Страница 14: ...oose wiring Tighten the terminals Disconnected wiring Re perform wiring Power supply voltage No output Unstable output Duct sensor main unit damages Replace the duct sensor Slow response to output Moi...

Страница 15: ...y use a slotted screwdriver or other tools while replacing the filter Failure to do so might damage the electronic components and rubber packing 3 Attach the new filter and then the new filter cap to...

Страница 16: ...liable calibration instrument for the single point calibration Carefully handle the duct sensor and check the appropriate environment for the calibration Calibrated digital multimeter is recommended t...

Отзывы: