Inspection and Maintenance 

Neosensor (two-wire 4-20 mA output sensor) is factory-inspected, in order to suppress internal heat generation effects because 
of two-wire sensor characteristics.  However, internal heat generation depends on five parameters: Power voltage, load 
resistance, wind velocity, temperature, and humidity.  Set the controller as follows, according to the conditions in the installation 
location. 

  Subtract the offset value from the PV (actual temperature/humidity). 

  Add the offset value to the SP

 

(set temperature/humidity).  

etc. 

 

For inspection and maintenance, follow the instructions below. 

 

Periodic inspection 

Periodically inspect Neosensor for its sensing accuracy, and clean the cover.  Set the period between inspections based on 
atmospheric dust and other contaminants in the installation environment. 

If Neosensor is installed in an animal holding room or a hospital operating room, cover the Neosensor when the room is 
sterilized. 

 

Troubleshooting 

If any problem occurs during operation, refer to the table below for appropriate solutions. 

Troubleshooting 

Problems Check 

points 

Solutions 

 No output 

 Unstable output 

 Loose wiring 

  Disconnected  wiring  

  Inappropriate power supply voltage  

  Neosensor main unit damages 

 Re-perform wiring. 

 
 

  Replace the Neosensor. 

  Slow response to output 

  Moisture/condensation on Neosensor 

  Remove the cover. 

  Disconnect the power and air-dry the Neosensor in a clean 
 air. 

  Error in output 

  Inappropriate installation location 

  Inappropriate environmental conditions 

  Dust and contamination on the Neosensor

 Refer to 

Installation

 section. 

 

  Clean the cover. 

 Calibrate. 

  Replace the Neosensor. 

 

Calibration 

Neosensor is factory-calibrated and does not require field calibration right after installation.  However, field-calibrate the 
Neosensor having output shift due to offset, change in environmental conditions, and aged deterioration. 

For a humidity or temperature output error, calibrate the Neosensor with adjustment knobs on the board inside the main unit.  
Two adjustment knobs (VR51 for fine adjustment and VR52 for rough adjustment) are provided for humidity calibration, and one 
adjustment knob (VR2) is provided for temperature calibration. 
Turn clockwise to increase the output value and counterclockwise to decrease the output value. 

 

 

 

 

 

Notes: 

  Model HY7043D (humidity sensor model) does not have the temperature adjustment knob (VR2) or the temperature sensing element. 

  Model TY7043D (temperature sensor model) does not have the humidity adjustment knobs (VR51, VR52) or the humidity sensing element. 

 

Figure 16.  Locations of the adjustment knobs VR2, VR51, VR52 on the board: Models TY7043D, HY7043D, HTY7043D 

 

Temperature adjustment knob (VR2) 

 
Humidity fine adjustment knob (VR51) 
Temperature sensing element 

Humidity rough adjustment knob (VR52) 

 

Humidity sensing element 

Содержание HTY7043

Страница 1: ...ration for humidity sensing element enhance accuracy and reliability of Neosensor sensing Neosensor is thus suitable for various applications such as commercial building or other indoor uses Note that...

Страница 2: ...graphically indicates the actual action to be carried out For example the sign on the left indicates general instructions CAUTION Use the product under the operating conditions temperature humidity po...

Страница 3: ...20 mA humidity output 0 Humidity sensing only 4 4 mA to 20 mA temperature output 0 0 Lead wire connection With company logo 1 Without company logo Regarding the available model numbers refer to the ta...

Страница 4: ...crosswise mount 106mm H x 198mm W attached to outlet box Thermoplate Model DY2000A3022 For three Neosensor crosswise mount Model DY2000A1021 For one Neosensor square mount Model DY2000A2021 For two Ne...

Страница 5: ...or under conditions not specified above ask our salesperson Temperature 4 5 min or less Time constant at 0 15 m s wind velocity Humidity 40 sec or less For temperature sensing Rated operating conditio...

Страница 6: ...s as shown in the above figure Model HTY7043D temperature humidity sensor model has four lead wires Figure 1 Mounting dimensions mm Neosensor with Wall direct mounting kit Mounting plate Note 1 Use JI...

Страница 7: ...sensor model and TY7043D temperature sensor model has two wires as shown in the above figure Model HTY7043D temperature humidity sensor model has four lead wires Figure 3 Mounting dimensions mm Neosen...

Страница 8: ...not install Neosensor outdoors or in a duct Do not horizontally install Neosensor directly on a ceiling Precautions for installation Install Neosensor with a dedicated mounting kit sold separately su...

Страница 9: ...and check that the depth change levers on the bilateral sides of the Neosensor main unit are set at the upper position indicated with L shown in Fig 12 Then mount the main unit of Neosensor on the mai...

Страница 10: ...ition indicated with L shown in Fig 12 Then mount the main unit of Neosensor on the main unit of the Wall direct mounting kit with the 4 mounting screws M3 16 supplied with Neosensor 5 Attach the cove...

Страница 11: ...ral sides of the Neosensor main unit are set at the upper position indicated with L shown in Fig 12 Then mount the main unit of Neosensor on the main unit of the Wall direct mounting kit with the 4 mo...

Страница 12: ...change Raising the Neosensor main unit 3 Set the depth change levers located on the bilateral sides on the main unit front surface at the lower position The levers are factory set at the upper positio...

Страница 13: ...ler Provide a controller with low pass filter 40 dB or higher removal ratio in normal mode that receives signals from Neosensor For insufficient removal ratio provide an isolator on the controller inp...

Страница 14: ...tput Moisture condensation on Neosensor Remove the cover Disconnect the power and air dry the Neosensor in a clean air Error in output Inappropriate installation location Inappropriate environmental c...

Страница 15: ...ody and or appliances while calibrating Carefully field calibrate Neosensor so that the heat on your hands do not affect the Neosensor After field calibration with the adjustment knobs the sensing acc...

Страница 16: ...ademark of Azbil Corporation in Japan or in other countries Specifications are subject to change without notice Building Systems Company http www azbil com Rev 1 0 Sep 2015 AB 7051 J AI 7051 Rev 0 0 P...

Отзывы: