Troubleshooting 

Problem… Check… 

Action… 

- No output 

generated 

 
 
- Unstable output 

- Check loose 

connection 

- Check Incorrect 

wiring  

- Check supply 

voltage  

- Check sensor 

damage 

- Re-connect the wire 
 
 
 
 
 
- Replace sensor   

- Slow response   
 
 
- Error in output 

- Check the sensor 

for water leakage or 
condensation 

- Check the installed 

location 

 
 
- Check the dust. 

soil. 

- Remove cover 

Dry the unit with no 
power. 

- Refer to the 

Installation 
instructions 

- Clean the cover 
- Replace the sensor
- Humifity one point 

adjustment 

3) Humidity one point adjustment 

When you find a calibration error in the humidity 
sensor, re-calibrate the sensor using the adjustment 
volume (VR1, VR2) located on the circuit board. The 
output value is increased by turning this volume in 
clockwise direction and decreased by turning it 
counterclockwise.      Use refelenced humidity meter of 
adequate accuracy.      A digital multimeter is 
recommended to check the output voltage. 

Parts Identification of Adjustment volume 

 

Cautions 

1. After unpacking, age the transmitter in the ambient 

atmosphere for at last 24 hours. 

2. To calibrate and adjust, take care the heat from 

human body or appliances. 

 

 
 

 

Fine adjustment volume (VR1)

Temperature element 

Humidity element

 

Rough adjustment volume (VR2) 