 CAUTION

Do not use silicon rubber cable, silicon adhesive or grease that contains silicon. Using such items might 

impair electrical continuity.

Wire the switch as shown in the figure below. (This figure is for the LS series.)

 

„

Installation

 CAUTION

• 

Tighten the screws according to the tightening torques indicated in the product specifications. Take care not to over-tighten 
the screws. Over-tightening may strip threads and damage other parts. Also, undertightening may impair performance 
such as the sealability of switches and other characteristics.

• 

When the limit switch is used in locations where it is subject to water, oil, dust or chips, it may allow ingress of them 
through conduit switch via the conduit. For this reason, take measures such as covering the switch after installation until 
wiring is completed. Be sure to use seal connectors that are compatible with the cable size when wiring.

Typical Tightening Torques

Series

Item

LS

SL1

Housing (front mounting screw)

M5

5 to 6 N•m

M4

1.3 to 1.7 N•m

Housing (rear mounting screw)

M6

5 to 6 N•m

M4nut 4 to 6 N•m **

Cover

M4

1.3 to 1. 7 N•m

-

Head

M3.5

0.8 to 1.2 N•m

-

Switch terminal

M4

1.0 to 1.4 N•m

M3

0.4 to 0.6 N•m

Lever (roller lever)

M5

4 to 5.2 N•m

-

** Attachment of nut on SL 1 plunger type                - None

 

„

Adjustment, Maintenance & Inspection

 CAUTION

• 

Set overtravel (OT) between 70 to 100% of the stipulated characteristic value. If OT is set too small, vibrations or impact 
may result in chattering of contact or contact failure.

• 

Prevents dogs from touching the lever. Failure to do so might result in the operating shaft deforming or faulty switch 
resetting.

 

„

Treating Conduits 

(Switches Not Provided With Cable)

 CAUTION

• 

Use seal connectors (PA1 series, to be ordered separately) or flexible piping (PA3 series, to be ordered separately) that en-
sure a sealing performance equivalent to or higher than IP67 for the conduits.

• 

Select connectors that match the outer diameter of the cable in use.

• 

Tighten connectors with a tightening torque of 8 to 12 N•m.

• 

Turn the connector compression nut 1.5 or 2 turns further after the cable feels firmly tightened.