31
Chapter 5. Trial Operation and Adjustment
•
Incorrect flame detector mounting angle (AUR355C)
•
Dirty flame detector sensing surface (AUR355C)
•
Tube unit deterioration (AUR355C)
•
Incorrect flame rod installation (AUR355B)
•
Area in contact with flame is insufficient.
•
Position of flame rod in flame is incorrect.
•
The flame rod insulator is at a high temperature (315 °C).
•
Flame rod is affected by the ignition transformer.
If the ignition transformer is close to terminal F of the flame rod, electrons
in the flame will be absorbed into the ignition transformer, and as a result,
sufficient flame voltage will not be achieved.
The voltage can be checked on the 7-segment display or by connecting a flame
meter to terminals 25 & 26 on the front connector. It is necessary to obtain a
monitor/communication connector (81447514-001) to connect the FSP136A100
and the AUR355.
Analog flame meter:
FSP136A100
Flame voltage
display
Handling Precautions
•
For the flame voltage output signal wires, use 600 V PVC-insulated cable (IEC
60227-3), 0.75 mm
2
or more in cross-sectional area. The wiring should be no
longer than 10 m.
•
The input impedance of a measuring instrument used with this device must
be 100 kΩ or more.
Содержание AUR355
Страница 10: ......
Страница 52: ......
Страница 53: ...Revision History CP SP 1454E Date Edn New Page No Description June 2021 1 ...