![Azbil ACTIVAL FVY5137J Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/azbil/actival-fvy5137j/actival-fvy5137j_specifications-and-instructions_3042658023.webp)
AB-7350-U
23
4) Lift and remove the cover from the base.
Figure 29. Cover removal from the base
Attaching the cover to the base
Attach the cover to the base and fix them by locking the 3 latches.
1) Attach the cover to the base by simultaneously inserting the 3 male latches of the cover to the 3 female latches of the base.
Equally press the force on each latch to the direction '4' in Fig. 29.
2) Keep pressing the force on each latch until they click.
3) Check that all of the latches are completely locked. If the latches are not completely locked yet, press the force on the
latches to the direction '4' in Fig. 29 so that the latches are completely locked.
Connecting the cable gland with three ports
Refer to the below table and tighten each part of the cable gland to connect it onto a wiring port (knockout) of this product.
Part of cable gland with three ports
Fastening torque
Lock nut of the base
16 in-lbs (1.8 N·m)
10 %
Seal connector for wiring port of the cover
16 in-lbs (1.8 N·m)
10 %
Plug for non-used port
15 in-lbs (1.7 N·m)
10 %
Cap of the seal connector
9 in-lbs (1.0 N·m)
20 %
1) Remove the terminal cover of the product.
2) Open a knockout for wiring port of the product. Remove the lock nut screwed on the base of the cable gland, and connect
the base onto the wiring port with the lock nut.
Figure 30. Connecting the base of the cable gland onto the wiring port
Knockout
for wiring port
Lock nut of the
cable gland base
Cover of the cable gland
Base of
the cable gland
1
2
Cover
Base
Lock nut
3
Latches
Plug for
non-used port
4