AB-7487-U

 

„

Model Numbers

Model FVY51_FJ is the model for the valve and actuator integrated into a single unit.  

The model number label is attached to the yoke.

Base 

model 

Number

Actuator / Valve

Actuator

Valve

Generation

Description

Control 

signal

Rating / 

Material

Type

Fixed

Nominal 

size / Cv

FVY51

Motorized two-way valve with flanged-end connection

(Flow measuring and controlling functioned)

3

4 to 20 mA DC input, pulse output, RS-485 communication 

(Modbus protocol)

4

2 to 10 V DC input, pulse output, RS-485 communication 

(Modbus protocol)

F

ANSI Class 125 / A126 Class B 

J

NEMA 4X and IEC IP54 protected and standard torque type 

actuator with terminal block

00

Fixed

21

1" / 10 Cv value

22

1" / 16 Cv value

41

1½" / 25 Cv value

42

1½" / 40 Cv value

51

2" / 65 Cv value

61

2½" / 95 Cv value

81

3" / 125 Cv value

Notes:

1.  This product has acquired the following UL/cUL certification.

 

UL60730-1/-2-14, CAN/CSA E60730-1:15 / -2-14:13 

Rated impulse voltage : 330 V (Over Voltage Category I), Control pollution degree: 4 (3 for the inside of actuator), Type of action: 1.AB 

Use the class 2 power supply. 

UL50E 

Type 4 Enclosure

2.  Only the actuator is certified with the UL/cUL above.

 

„

Specifications

For weight, refer to the table shown in the section 

Dimensions

.

 

Valve and actuator (as a single unit) specifications

Item

Specification

Environmental 

conditions

Rated operating conditions

Ambient temperature

-4 to 122 °F (-20 to 50 °C)

(Do not allow the process fluid to freeze.)

Ambient humidity

5 to 95 % RH

Vibration

16.1 fps

2

 (4.9 m/s

2

) for 10 to 150 Hz

Shock

16.1 fps

2

 (4.9 m/s

2

)

Transport/storage conditions 

(in package)

Ambient temperature

-4 to 158 °F  (-20 to 70 °C)

Ambient humidity

5 to 95 % RH

Vibration

64.3 fps

2

 (19.6 m/s

2

) for 10 to 150 Hz

Installation locations

Indoor (salt air, corrosive gas, flammable gas, and organic solvent must be avoided.)

Outdoor (Use the outdoor cover etc. to be ordered separately. Direct sunlight, salt air, 

corrosive gas, flammable gas, and organic solvent must be avoided.)

Installation orientation

Installable in any position ranging from upright to sideways (90° tilted.) 

  * The valve sensor must face upward when tilted.

  * Always install in upright position outdoors.

Manual operation

Available

Insulation 

resistance

Between the case and terminal

Min. 5 MΩ (50 V DC)

Dielectric 

strength

Between the case and terminal 250 V AC for 1 min, leakage current 5 mA or less

Position for shipment

100 % (fully open) preset at factory.

Содержание ACTIVAL+ FVY51 FJ Series

Страница 1: ...ct and lightweight Rotary valve actualizes small body and light weight Valve and actuator integrated in a single unit NEMA 4X and IP54 enclosure rating Waterproof connectors are required to assure NEM...

Страница 2: ...ency of use as basic parameters The recommended design life of this product is 10 years The recommended design life assumes that maintenance such as replacement of the limited life parts is carried ou...

Страница 3: ...eliable components etc 4 The use of redundancy CAUTION After installation make sure no fluid leaks from the valve pipe connections Improper piping may cause fluid leakage outside of the valve Do not p...

Страница 4: ...e arrow correct measurement and control of flow is not assured Do not loosen the yoke fixing screws or the actuator fixing screws Loose fixing screws lower flow measuring accuracy Note that the actuat...

Страница 5: ...y the actuator is certified with the UL cUL above Specifications For weight refer to the table shown in the section Dimensions Valve and actuator as a single unit specifications Item Specification Env...

Страница 6: ...i FVY51_FJ0051 2 50 65 145 psi FVY51_FJ0061 2 65 95 145 psi FVY51_FJ0081 3 80 125 145 psi Materials Body Gray cast iron A126 Class B Plug and stem Stainless steel Seat ring Heat resistant PTFE Gland p...

Страница 7: ...Wire connection Power control signal DI pulse output M3 5 screw terminal connection Temperature sensor Pt100 input 6 pin 3 pin 2 connector RS 485 communication 6 pin 3 pin 2 connector Display Panel 4...

Страница 8: ...curacy 0 72 F at 32 to 176 F 0 4 C at 0 to 80 C ambient temperature 1 08 F at 4 to 32 F 0 6 C at 20 to 0 C ambient temperature Error due to wiring length 0 27 F at 49 2 49 2 ft 0 15 C at 15 15 m in th...

Страница 9: ...2 x 4 core 0 3 mm2 164 ft 50 m 4 pin connector Temperature sensor Pt100 input Temperature sensor for pipe surface Pipe sensor 3 core cable assembled with the sensor 98 ft 30m 6 pin 3 pin 2 connector I...

Страница 10: ...9 5 51 0 79 0 75 4 35 3 FVY51_FJ008_ 3 7 99 3 94 10 35 4 92 7 48 6 0 87 0 75 4 44 1 Figure 1 Dimensions Parts Identification Figure 2 Parts identification Valve details 2 76 70mm L1 L t H1 H 5 43 138m...

Страница 11: ...rature Row T2 Return water temperature Reset switch Connector for Display Panel 24 V AC Power Port for Display Panel cable Port for temperature sensor Pt100 input cable Port for valve sensor cable Por...

Страница 12: ...installing the product with flange gasket do not use the rubber gasket or the gasket that goes inside the pipe Doing so might cause incorrect measurement and control of flow Install the product to a p...

Страница 13: ...all outdoors Install the product in a position allowing easy access for maintenance and inspection 12 305 mm clearance on top of and around the actuator 24 610 mm clearance on the front are required a...

Страница 14: ...must be installed always in upright position outdoors Do not mount Model FVY51_FJ with its actuator vertically below the valve on a vertical downflow pipe or with the valve sensor facing downward Cor...

Страница 15: ...e valve seat may get damaged causing fluid leakage due to the sealing material jammed inside the valve Before activating the product fully open in 100 position the valve and flush the pipes with the p...

Страница 16: ...se the product slowly turn the joint If shock is sent to the actuator the actuator might get damaged Do not touch the pin with a wrench tool when manually opening closing the product Disconnect the po...

Страница 17: ...rheating After wiring be sure to reattach the terminal cover Failure to do so may result in electric shock IMPORTANT The product is designed for 24 V AC power supply voltage Do not apply any other pow...

Страница 18: ...and 10 and correctly connect the wires to the M3 5 screw terminals Note that the wires of the temperature sensor Display Panel and RS 485 communication lines are connected to the connectors Figure 10...

Страница 19: ...B supply water temperature T2A T2B T2B Red White White Red Black White Pt100 A return water temperature Pt100 B return water temperature Pt100 B return water temperature Note Wire color of the inserti...

Страница 20: ...re Lightly pull out connected wires Figure 17 Wires connection to the 4 pin connector for Display Panel 4 Plug the connector into the actuator socket Note Completely plug the connector into the actuat...

Страница 21: ...o use a magnetic counter with a relay coil refer to Fig 28 and connect a protection diode to the input of the magnetic counter 3 Temperature sensor for pipe surface Since the 3 core cable of the tempe...

Страница 22: ...from the power To operate the two products with a single controller for example the two products must be powered by a single transformer Connection examples Power Controller e g Model SDC35 SDC36TC0 I...

Страница 23: ...ontroller and a single transformer Model FVY514FJ 2 10 V input Model FVY514FJ 2 10 V input 2 2 Controller e g Model SDC35 SDC36TD0 Isolator 1 Isolator 1 Power 3 3 1 2 5 6 7 8 1 2 5 6 7 8 Notes 1 Provi...

Страница 24: ...e master device SG FG Shielded Shielded 1 2 3 4 5 6 DA DA DB DB SG SG DA DB SG Figure 26 Connection example 5 wire RS 485 communication Model FVY513FJ This product Pulse counter 3 4 V 0 V Figure 27 Co...

Страница 25: ...pection detail Visual inspection Semiannual Fluid leakage from the gland and the flange face Loosened bolts Valve and actuator damages Operating status Semiannual Unstable open close operation Abnorma...

Страница 26: ...setscrew of the terminal cover 0 39 1 cm Figure 29 Check of the valve position detecting accuracy Disposal Dispose of this product as industrial waste in accordance with your local regulations Do not...

Страница 27: ...27 AB 7487 U This blank page was added for page layout purposes...

Страница 28: ...Kanagawa 251 8522 JAPAN AB 7487 U Rev 0 0 Mar 2018 ACTIVAL and ACTIVAL are trademarks of Azbil Corporation in Japan or in other countries This product complies with the following harmonised standards...