Specifications/Instructions

1

AB-7487-U

Standalone Model 

Motorized Two-Way Valve with Flanged-End Connection 

(ANSI Class 125 / A126 Class B)

 

„

General

A

TM

 Model FVY51_FJ is a series of motorized two-

way valves with flanged-end connection. Rotary valve and 

actuator are integrated in a single unit.
In combination with the functions of a control valve, Model 

FVY51_FJ measures and controls flow. Model FVY51_FJ 

thus enables to control temperature for air conditioning by 

controlling chilled/hot water volume and to measure chilled/

hot water flow.

For such a high functionality, compact size and simple 

installation of Model FVY51_FJ are incomparable.
Model FVY51_FJ is operated by the following control signal.
1.   4–20 mA DC input
2.   2 to 10 V input  

Both provide proportional control in combination with a 

single loop controller (e.g., Model SDC35/SDC36)

Flow data stored in Model FVY51_FJ is retrieved via RS-485 

communication (Modbus protocol). The retrieved flow data is 

effective for energy-saving facility operation.

 

„

Features

  Compact and lightweight: 

Rotary valve actualizes small body and light weight.

  Valve and actuator integrated in a single unit.

  NEMA 4X and IP54 enclosure rating 

(Waterproof connectors are required to assure NEMA 4X 

and IP54)

  Valve for chilled/hot water control applicable to large Cv 

value, high rangeability, and low leakage.

  Durable actuator with low power consumption.

  Flow control/position control operation selectable:  

For flow control, flow characteristic is selectable 

(equal percentage or linear). For position control, flow 

characteristic is equal percentage.

  Model FVY51_FJ holds flow data effective for 

maintenance and energy-saving facility operation. The 

data is retrieved via RS-485 communication (Modbus 

protocol).

  In combination with the optional Display Panel (Model 

QY5010S2000) and the insertion-type temperature 

sensor (Model TY7830) or the temperature sensor for 

pipe surface (Model TY7820), pressure, temperature, 

and flow can be displayed on the Display Panel.

Note: The display panel, the insertion-type pipe temperature 

sensor, and the temperature sensor for pipe surface should be 

ordered separately.

IMPORTANT:

Do not use the data measured by this product for charging or dealing purposes.

© 2018 Azbil Corporation All Rights Reserved.

Содержание ACTIVAL+ FVY51 FJ Series

Страница 1: ...ct and lightweight Rotary valve actualizes small body and light weight Valve and actuator integrated in a single unit NEMA 4X and IP54 enclosure rating Waterproof connectors are required to assure NEM...

Страница 2: ...ency of use as basic parameters The recommended design life of this product is 10 years The recommended design life assumes that maintenance such as replacement of the limited life parts is carried ou...

Страница 3: ...eliable components etc 4 The use of redundancy CAUTION After installation make sure no fluid leaks from the valve pipe connections Improper piping may cause fluid leakage outside of the valve Do not p...

Страница 4: ...e arrow correct measurement and control of flow is not assured Do not loosen the yoke fixing screws or the actuator fixing screws Loose fixing screws lower flow measuring accuracy Note that the actuat...

Страница 5: ...y the actuator is certified with the UL cUL above Specifications For weight refer to the table shown in the section Dimensions Valve and actuator as a single unit specifications Item Specification Env...

Страница 6: ...i FVY51_FJ0051 2 50 65 145 psi FVY51_FJ0061 2 65 95 145 psi FVY51_FJ0081 3 80 125 145 psi Materials Body Gray cast iron A126 Class B Plug and stem Stainless steel Seat ring Heat resistant PTFE Gland p...

Страница 7: ...Wire connection Power control signal DI pulse output M3 5 screw terminal connection Temperature sensor Pt100 input 6 pin 3 pin 2 connector RS 485 communication 6 pin 3 pin 2 connector Display Panel 4...

Страница 8: ...curacy 0 72 F at 32 to 176 F 0 4 C at 0 to 80 C ambient temperature 1 08 F at 4 to 32 F 0 6 C at 20 to 0 C ambient temperature Error due to wiring length 0 27 F at 49 2 49 2 ft 0 15 C at 15 15 m in th...

Страница 9: ...2 x 4 core 0 3 mm2 164 ft 50 m 4 pin connector Temperature sensor Pt100 input Temperature sensor for pipe surface Pipe sensor 3 core cable assembled with the sensor 98 ft 30m 6 pin 3 pin 2 connector I...

Страница 10: ...9 5 51 0 79 0 75 4 35 3 FVY51_FJ008_ 3 7 99 3 94 10 35 4 92 7 48 6 0 87 0 75 4 44 1 Figure 1 Dimensions Parts Identification Figure 2 Parts identification Valve details 2 76 70mm L1 L t H1 H 5 43 138m...

Страница 11: ...rature Row T2 Return water temperature Reset switch Connector for Display Panel 24 V AC Power Port for Display Panel cable Port for temperature sensor Pt100 input cable Port for valve sensor cable Por...

Страница 12: ...installing the product with flange gasket do not use the rubber gasket or the gasket that goes inside the pipe Doing so might cause incorrect measurement and control of flow Install the product to a p...

Страница 13: ...all outdoors Install the product in a position allowing easy access for maintenance and inspection 12 305 mm clearance on top of and around the actuator 24 610 mm clearance on the front are required a...

Страница 14: ...must be installed always in upright position outdoors Do not mount Model FVY51_FJ with its actuator vertically below the valve on a vertical downflow pipe or with the valve sensor facing downward Cor...

Страница 15: ...e valve seat may get damaged causing fluid leakage due to the sealing material jammed inside the valve Before activating the product fully open in 100 position the valve and flush the pipes with the p...

Страница 16: ...se the product slowly turn the joint If shock is sent to the actuator the actuator might get damaged Do not touch the pin with a wrench tool when manually opening closing the product Disconnect the po...

Страница 17: ...rheating After wiring be sure to reattach the terminal cover Failure to do so may result in electric shock IMPORTANT The product is designed for 24 V AC power supply voltage Do not apply any other pow...

Страница 18: ...and 10 and correctly connect the wires to the M3 5 screw terminals Note that the wires of the temperature sensor Display Panel and RS 485 communication lines are connected to the connectors Figure 10...

Страница 19: ...B supply water temperature T2A T2B T2B Red White White Red Black White Pt100 A return water temperature Pt100 B return water temperature Pt100 B return water temperature Note Wire color of the inserti...

Страница 20: ...re Lightly pull out connected wires Figure 17 Wires connection to the 4 pin connector for Display Panel 4 Plug the connector into the actuator socket Note Completely plug the connector into the actuat...

Страница 21: ...o use a magnetic counter with a relay coil refer to Fig 28 and connect a protection diode to the input of the magnetic counter 3 Temperature sensor for pipe surface Since the 3 core cable of the tempe...

Страница 22: ...from the power To operate the two products with a single controller for example the two products must be powered by a single transformer Connection examples Power Controller e g Model SDC35 SDC36TC0 I...

Страница 23: ...ontroller and a single transformer Model FVY514FJ 2 10 V input Model FVY514FJ 2 10 V input 2 2 Controller e g Model SDC35 SDC36TD0 Isolator 1 Isolator 1 Power 3 3 1 2 5 6 7 8 1 2 5 6 7 8 Notes 1 Provi...

Страница 24: ...e master device SG FG Shielded Shielded 1 2 3 4 5 6 DA DA DB DB SG SG DA DB SG Figure 26 Connection example 5 wire RS 485 communication Model FVY513FJ This product Pulse counter 3 4 V 0 V Figure 27 Co...

Страница 25: ...pection detail Visual inspection Semiannual Fluid leakage from the gland and the flange face Loosened bolts Valve and actuator damages Operating status Semiannual Unstable open close operation Abnorma...

Страница 26: ...setscrew of the terminal cover 0 39 1 cm Figure 29 Check of the valve position detecting accuracy Disposal Dispose of this product as industrial waste in accordance with your local regulations Do not...

Страница 27: ...27 AB 7487 U This blank page was added for page layout purposes...

Страница 28: ...Kanagawa 251 8522 JAPAN AB 7487 U Rev 0 0 Mar 2018 ACTIVAL and ACTIVAL are trademarks of Azbil Corporation in Japan or in other countries This product complies with the following harmonised standards...

Отзывы: