Setup strategy

The example below shows the relationship between the setpoint, 
offset and differentials. For this example the setpoint will be set 
to 20

°

C and the stage switching requirements are as shown in the 

table below.

Stage

Action

Switch On

Switch Off

Mid point

1

Cooling

> 28

°

C

< 24

°

C

26

°

C

2

Cooling

> 24

°

C

< 22

°

C

23

°

C

3

Heating

< 18

°

C

> 20

°

C

19

°

C

4

Heating

< 16

°

C

> 18

°

C

17

°

C

5

Heating

< 14

°

C

> 16

°

C

15

°

C

6

Heating

< 10

°

C

> 14

°

C

12

°

C

Once the setpoint and switching requirements have been defined 
the stage offsets and stage differentials can be calculated.

For Stage 1 Cooling

Stage Offset

= Stage mid point - Setpoint

= 26 - 20

= 6

Stage Differential

= Switch on - Switch off

= 28 - 24

= 4

The calculated values, listed below, should be entered using the 
set-up menu.

Setup option

Required value

Stage select

CCHHHH

S1 Offset

6

°

C

S1 Differential

4

°

C

S2 Offset

3

°

C

S2 Differential

2

°

C

S3 Offset

1

°

C

S3 Differential

2

°

C

S4 Offset

3

°

C

S4 Differential

2

°

C

S5 Offset

5

°

C

S5 Differential

2

°

C

S6 Offset

8

°

C

S6 Differential

4

°

C

Setback

Off

External Pot

None

The diagram below illustrates the relationship 
between the values set for the example. 

12

14

16

18

20

22

24

26

S1 Diff = 4

S3 Diff = 2

Setpoint = 20

Temperature

S2 Diff = 2

S4 Diff = 2

28

S4 ON

S4 OFF

S3 OFF

S3 ON

S2 ON

S1 ON

S2 OFF

S1 OFF

10

Stage 4

Stage 3

Stage 2

Stage 1

S2 Offset = 3

S1 Offset = 6

S3 Offset = 1

S4 Offset = 3

S5 Diff = 2

S5 ON

S5 OFF

Stage 5

S5 Offset = 5

S6 Diff = 4

S6 ON

S6 OFF

Stage 6

S6 Offset = 8

8

Содержание AX-ET-6

Страница 1: ...0 230Vac 15 Inputs Sensor 10K3A1 See Axio temperature sensor range Remote Setpoint 1 11kΩ For 4 C or 20 C Setback volt free timer input Close contact to activate setback LCD Display 2 lines by 8 characters Temperature Range 20 C to 120 C Stage Selection CCCCCC CCCCCH CCCCHH CCCHHH CCHHHH CHHHHH HHHHHH C cooling H heating Setpoint 10 C to 110 C Offset 0 to 50 C Differential 0 to 12 C Setback Range ...

Страница 2: ...y switching points to 2 C above the offset and 2 C below the offset MENU I NC DEC INC DEC I NC DEC Stage switching If the stage is set for cooling the relay will switch on when the temperature rises above the upper switching point and will switch off when the temperature falls below the lower switching point If the stage is set for heating the relay will switch on when the temperature falls below ...

Страница 3: ...on whilst a dash is shown when the stage relay is off Minimum On and Off times This function prevents over cycling of the output For example setting the minimum on time to 5 seconds will ensure any output stage is in on for a minimum of 5 seconds The Off time works in a similar way When the Actual temperature display is visible press three times to display the On value Press or to adjust the param...

Страница 4: ... Once the setpoint and switching requirements have been defined the stage offsets and stage differentials can be calculated For Stage 1 Cooling Stage Offset Stage mid point Setpoint 26 20 6 Stage Differential Switch on Switch off 28 24 4 The calculated values listed below should be entered using the set up menu Setup option Required value Stage select CCHHHH S1 Offset 6 C S1 Differential 4 C S2 Of...

Отзывы: